9
Main Window
RS5-4SRSEN.VHF.xxxxx
SN XXXXXX
>1.ID
2.Repeat (1-9) times 3
3.Repeat Test (1-9) times 2
4.Test every (1-240) hours 24
5.Test after reset (1-240) hours 1
>6.Inputs
?
The number of the program;
The serial number of the transmitter;
The subscriber’s number of the transmitter;
The number of message repetition;
The number of communication tests;
The periodicity of communication tests (every 24
hours).
The first test after RESET pressing (1-24 hours.);
Switchover into the settings of input parameters.
The message for v7P version
Main Window:
RS5.1-4SRPEN.VHF.xxxxx
SN XXXXXX
>1.ID
2.Repeat (1-9) times 3
3.Repeat Test (1-9) times 2
4.Test every (1-240) hours 24
5.Test after reset (1-240) hours 1
>6.Inputs
>7.Paradox
?
The number of the program;
The serial number of the transmitter;
The subscriber’s number of the transmitter;
The number of message repetition;
The number of communication tests;
Periodicity of communication tests (every 24 hours).
The first test after RESET pressing
(1-24 hours.);
Switchover into the settings of input parameters.
Switchover into the settings of security central control
panel.
The parameters signed “>” have additional Dialog Windows to set an exact value,
those signed “*” can be switched on and off. Parameters are set using the keys from
the digital part of the keyboard. For example, to change the parameter No 3, the key [3]
should be pressed. If the appropriate value of the parameter is required, the note
[value] is displayed on the monitor. Below this note the appropriate value is entered
than pressing the key [Enter].
5. The subscriber’s number, the number of message repetition, periodicity of
communication test signals are entered from the Main Window. The appropriate input
type: NO, NC, EOL can be set from this Window as well. Select the appropriate input
and perform the changes by pressing the key of input number.
Time of vibration resistance contacts can be determined from this Window. After
pressing the key [S] you will see the list of inputs. Select appropriate input and change
the parameter, by entering necessary value. The parameter you enter is repeated for
the time of 20ms.
The mode of all input control [K] is assigned to a single input. Given error in such
input, all other inputs are controlled. The codes of false inputs or communication test
signals are transmitted to the central monitoring station. The time of transmitting the
next signal of communication test left unchanged in this case.
Table 3 presents additional methods to change operating parameters.