Page 2 / 7 Issue date: 20.02.2023
Thermokon Sensortechnik GmbH, Platanenweg 1, 35756 Mittenaar, Germany · tel: +49 2778 6960-0 fax: -400 www.thermokon.com· email@thermokon.com
DPA+_(LCD)_Dual_RS485_Modbus_Datasheet_en-us © 2023
»SECURITY ADVICE – CAUTION
The installation and assembly of electrical equipment should only be performed by authorized personnel.
The product should only be used for the intended application. Unauthorised modifications are prohibited! The product must not
used in relation with any equipment that in case of a f
ailure may threaten, directly or indirectly, human health or life or result in
danger to human beings, animals or assets. Ensure all power is disconnected before installing. Do not connect to live/operati
•Local laws, health & safety regulations, technical standards and regulations
•Condition of the device at the time of installation, to ensure safe installation
•
This data sheet and installation manual
Before installation, commissioning and operation, make sure that the correct pressure gauge has been selected with regard to measuring range,
design and, based on the specific measuring conditions, the suitable medium in contact with the medium. Pressure gauges may only be installed
and serviced by trained specialist personnel authorized by the plant operator. Failure to observe the relevant regulations may result in serious
physical injury and/or damage to property.
»TECHNICAL DATA
Measuring values differential pressure, volume flow
Medium air or other non-flammable/non-aggressive gases
Output voltage 0..10 V or 0..5 V, min. load 10 kΩ
(live-zero configuration via Thermokon USEapp)
Network technology RS485 Modbus, RTU, half-duplex, baud rate 9.600, 19.200, 38.400 or 57600, parity: none (2 stopbits), even
or odd (1 stopbit), Fail-safe Biasing required
Power supply 15..35 V = or 19..29 V ~ SELV
Power consumption max. 2,3 W (24 V =) | max. 4,3 VA (24 V ~)
Measuring range velocity 0… 750.000 m³/h (default), optionally configured via Thermokon USEapp
Measuring range pressure
*selectable at the device
type 250
0..+1 | 0..+0.4 | 0..+0.2 | 0..+0.1 |
-0.1..+0.1 | -0.2..+0.2 | -0.4..+0.4
| -0.6..+0.6 inchWC
type 2500
0..+10 | 0..+8 | 0..+6 | 0..+4 | -0..+2
| 0..+1 | 0..+0.4 | -0.4..+0.4
inchWC
type 7000
0..+28 | 0..+20 | 0..+16 | 0..+12 |
0..+10 | 0..+8 | 0..+6 | 0..+4
inchWC
Accuracy pressure
*deviation from calibration
reference device (calibrator)
at range
<1 inchWC: typ. ±0.004 inchWC
at range
≤2 inchWC: ±0.02 inchWC,
>2 inchWC: ±0.04 inchWC
at range
≤8 inchWC: ±0.04 inchWC,
>8 inchWC: ±0.10 inchWC
Zero-point adjustment
(manual)
3 month at range:
≤2 inchWC: 6 month
>2 inchWC: 12 month
12 month
Zero-point adjustment
(automatic)
automatic zero-point adjustment (optional)
Max. working overpressure 160 inchWC
Sensor piezo measuring element
Inputs
(optional)
2IN
2x input for NTC10k or floating contact
Display
(optional)
LCD 1.14x1.38 in. with RGB backlight,
units, pressure: Pa, inchWC, volume flow: m3/h, cfm (configurable)
Enclosure
(type-dependent)
without LCD
enclosure USE-L, PC, pure white, with removable
cable entry
with LCD
enclosure USE-L, PC, pure white, cover PC,
transparent, with removable cable entry
Protection IP65 according to EN 60529
Cable entry M25, for wire max. Ø=7 mm, seal insert for fourfold cable entry
Connection electrical Mainboard
removable plug-in terminal, max. 14AWG
Plug-in card
removable plug-in terminal, max. 16AWG
Connection mechanical pressure connection male Ø=0.2 in / Ø=0.25 in., connection tube: PVC, soft
Ambient condition +14..+122 °F, max. 85% rH short term condensation
Mounting screw mounted onto flat surface, prepared for mounting on DIN rail TS35 (35x7,5 mm) according to
EN 60715