Troubleshooting
Georg Fischer Signet LLC, 3401 Aerojet Avenue, El Monte, CA 91731-2882 U.S.A. • Tel. (626) 571-2770 • Fax (626) 573-2057
For Worldwide Sales and Service, visit our website: www.gfsignet.com • Or call (in the U.S.): (800) 854-4090
For the most up-to-date information, please refer to our website at www.gfsignet.com
3-8350.090-1 Rev. H 01/12 English © Georg Fischer Signet LLC 2012
Ordering Information
Mfr. Part No. Code Description
3-8350-1 159 000 192 Temperature transmitter Field mount
3-8350-1P 159 000 193 Temperature transmitter Panel mount
3-8350-2 159 000 194 Temperature transmitter Field mount with relays
3-8350-2P 159 000 195 Temperature transmitter Panel mount with relays
3-8350-3 159 000 196 Temperature transmitter Field mount with dual input/output
3-8350-3P 159 000 197 Temperature transmitter Panel mount with dual input/output
Accessories
Mfr. Part No. Code Description
3-8050 159 000 184 Universal mounting kit
3-8052 159 000 188 3/4” Integral mounting kit
3-8052-1 159 000 755 3/4" NPT mount junction box
3-8050.395 159 000 186 Splashproof rear cover
3-8050.396 159 000 617 RC Filter kit (for relay use)
3-0000.596 159 000 641 Heavy duty wall mount bracket
3-5000.598 198 840 225 Surface Mount Bracket
3-9000.392 159 000 368 Liquid tight connector kit for rear cover (includes 3 connectors)
3-9000.392-1 159 000 839 Liquid tight connector kit, NPT (1 piece)
3-9000.392-2 159 000 841 Liquid tight connector kit, PG13.5 (1 piece)
3-9900.396 159 001 701 Angle Adjustment Adapter Kit
Display Condition Possible Causes Suggested Solutions
Check Sensor?
• Sensor not wired properly.
• Sensor connected to 8350 while power
is on.
• Defective sensor.
• Correct sensor wiring.
• Recycle power with all sensors connected.
• Replace defective sensor.
Too much error
CHECK SENSOR
The value entered in Set Temperature
field is greater than 20 °C (36 °F)
deviation from sensor input. (The 8350
allows a maximum of 20 °C offset.).
• Confirm calibration values.
• Replace defective sensor.
Reset to Factory
Calibration
Value in SET TEMPERATURE field
is -999.
Entering "-999" in this field will remove all user
calibration input and restore the factory values.
Open Collector is always
activated
• Hysteresis value too large.
• Defective transmitter.
• Change the hysteresis value
• Replace transmitter
Value must be
400 or less
Value entered in Output PlsRate field is
greater than 400.
Select a maximum pulse rate of 400 pulses per
minute or less.