| IWT-128 SERIES
TRANSMITTER AND BUS CO-ORDINATOR OPERATING MANUAL
Copyright © 2021 Sensata Technologies, Inc. Page 7
6. CALIBRATING THE IWT-128
When the unit is shipped the IWT-128 will be calibrated for the output type and range
noted on the side label if it is fitted. If this label is blank then the unit will be calibrated for
4-20 mA output.
The display is used to show scaled values of the inputs and outputs in the system, or ON
and OFF for digital inputs and outputs. The left button scrolls through the available
channels, and the right button scrolls through the available parameters. Whilst the button
is held down, the channel number is shown on the left of the screen, and the parameter is
shown on the right. The led on the display will flash every 3 seconds to indicate to the
user that the unit is operating. The display can be configured to remain on all the time or
switch off after 15 minutes.
Data is sent to the remote receiver for each channel at the TRANSMIT time rate.
6.1 Main menu
To access the main menu push and hold both buttons until OK is displayed.
These are the main menu options, use raise and lower buttons to cycle through:
1. CHANNEL (sec 6.2) 6. DZ zero (sec 6.4)
2. OUT SPAN (sec 6.3) 7. VIEW DSV (sec 6.5)
3. OUT ZERO (sec 6.3) 8. DISPLAY time (sec 6.6)
4. DSV Cc Pp (sec 6.4) 9. AGE age (sec 6.7)
5. DS span (sec 6.4) 10. TRANSMIT time (sec 6.8)
Note that menu options 1,2,3 are only available when the output is fitted.
To access the sub-menu of one of the main menu options, use raise or lower to cycle to
the option required then push and release both buttons. Change the parameter as
required.
To return to the main menu, push and release both buttons.
To exit from the main menu and return to run mode, press and hold both buttons for 2
seconds until OK is displayed on the screen.
After two minutes of inactivity from the front buttons when the main menu (or a sub-
menu) had been accessed, a timeout will occur and the unit will automatically return to
run mode.
6.2 Select IWT-128 Channel (1. CHANNEL)
If the IWT-128 has an output it must be allocated a channel number on the system, so
that its data values can be identified correctly by the remote receiver.
The channel number chosen must not be a duplicate of any other device within the
system.