ADJUSTMENT DAMPING (0 till 25 sec)
In P106 an electronic damping can be adjusted between 0 and 25 seconds.
This can be done with the push buttons [↑] (up) and [↓] (down).
Always confirm by pushing once at [PROG].
INDICATION OF PROCESS TEMPERATURE (READ OUT ON DISPLAY)
1. Push [PROG] until "100" is shown on the display.
2. Push 7 times at [↑], go to [P107].
3. Push [PROG] to confirm this. Now the process temperature appears on the
display (Indication: +/-2°C).
This will remain on the display. To get the actual pressure back on the display you have to push
again on P107 until the actual pressure appears on the display again.
TEMPERATURE IN °F OR °C
The temperature of the transmitter is standard adjusted at °F (FAHR). When pushing at [↑] in
P108, this will change into °C (CELC). Always confirm by pushing once at [PROG].
READ OUT ON DISPLAY
Curr (0) = current (4 - 20 mA)
Unit (1) = pressure unit (See conversion table)
PErC (2) = percentages (0 - 100%)
TEnP (3) = temperature (°F of °C) Indication of process temperature, accuracy depending on sensor position.
HECt (4) = hectoliter (only in combination with P111)
Cb n (5) = Cubic meter (only in combination with P111)
Ltr (6) = Liters (only in combination with P111)
FREE (7) = Free adjustable scale (only in combination with P111)
As standard the transmitter read out is in mA (0).To change this, follow the next steps:
1. Push [PROG] until "100" is shown on the display.
2. Push 9 times at [↑] / SPAN till "109" appears on the display.
3. Confirm with [PROG].
4. Push once at [↑].
5. Push [PROG] to confirm this.
The transmitter will now read mH2O (mWC).
The pressure unit can be changed with the conversion table in P104.
1 = mH2O (=mWC), 3 = bar, 5 = psi, 11 = inchH2O (inchWC).
The read out can also be in 0 - 100%. Select P109, option 2.
SIMULATION OF CURRENT (4-20 mA)
The transmitter can be used as a simulator of a current between 4 - 20 mA.
This can be done in P110 with the push buttons [↑] and [↓].
The user can perform a current simulation (Curr) or a pressure simulation (Unit).
Current-simulation (Curr)
To perform a current-simulation follow the next steps:
1. Push [PROG] until "100" is shown on the display.
2. Push 10 times at [↑] / SPAN till "110" appears on the display.
3. Confirm with [PROG].