C Series
Single Channel
Temperature Transmitter
Website: http://www.anpe.cn
Service Tel: +86(25)-84459479
Address: New Power industrial Park, Luhe Economic Development Zone, Nanjing, China
Postcode: 211500
Nanjing New Power Electric Co., Ltd.
604040203400001
< 300 ℃
≥ 300 ℃
< 500 ℃
≥ 500 ℃
< 100 ℃
≥ 100 ℃
± 0.3 ℃
± 0.1% F.S.
± 0.5 ℃
± 0.1 % F.S.
± 0.1 ℃
± 0.1 % F.S.
Range Accuracy
Input
K/E/J/N/T
S/B/R/WRe-series
Pt100/Cu100
Cu50/BA1/BA2
1
2
3
4
5
6
4 mA ~ 20 mA
1 V ~ 5 V
0 mA ~ 10 mA
0 V ~ 5 V
0 V ~ 10 V
0 mA ~ 20 mA
X
User customized signal type
Number Output signal
Single input, single output
Power supply
Output
+
-
9
10
5
6
+
-
RL
-
+
R8 R7 R6 R5 R4 R 3 R2 R 1
DIN Rail
R3
R1
DIN Rail
2-wire
Input
3-wire
3
2
1
1
2
3
RTD
RTD
TC
-
+
CJC
Single input, double output
9
10
+
-
Power supply
-
+
R8 R7 R6 R5 R4 R 3 R2 R 1
DIN Rail
R3
R1
DIN Rail
2-wire
Input
3-wire
3
2
1
1
2
3
RTD
RTD
TC
-
+
CJC
Output1
5
6
+
-
RL
Output2
7
8
+
-
RL
mFollow mode: Whatever input fault status (except
breakage), the output follows the input within measuring
range. And the maximum value would not exceed the
110% of the upper limit of the measuring range (e.g.
When the output signal type is 0 ~ 20 mA, the minimum
output value may be 0 mA, the maximum output value
would not exceed 22 mA).
mWhen the thermocouple input, compensation conductor
should be directly connected to the input terminals, do not
connect other material lead, otherwise will cause
measurement error.
mDIN rail power supply function is selectable at ordering.
èDimension
Width × Height × Depth: 12.8 mm × 110 mm × 117 mm
Default: Terminals powered
PB: BUS powered
X
Default: null
The second output signal
note
The first output signal
note
XX
NPWD-C DX
.TC: thermocouple input
.RTD: thermal resistance input
Default: thermocouple or
thermal resistance input
èIntroductions
This temperature transmitter converts the thermocouple/
thermal resistance signals to current or voltage signals. DIN
rail power supply function can be selected in ordering.
The input, output, and power supply are galvanically isolated
from each other. You can use handheld programmer to
modify parameters or to calibrate the apparatus.
èParameters
Power supply:
Connection type: Terminals (9+, 10-) or DIN rail connector
Rated voltage: 18 V DC~60 V DC (Recommended voltage:
24 V DC)
Input (1, 2, 3):
TC: K, E, S, B, J, T, R, N, WRe3 - WRe25, WRe5 - WRe26,
2/3-wire RTD: Pt100, Cu100, Cu50, BA1, BA2
The input signal needs to be determined when ordering and
can also be programmed. Other signal types is required
special customization, please see the product label for details.
Line resistance: ≤ 20 Ω per line
Output (5, 6; 7, 8):
Output current: 0(4) ~ 20 mA; 0 ~ 10 mA
Output voltage: 0(1) ~ 5 V; 0 ~ 10 V
Output ripple: ≤ 5 mV (Load resistance: 250 Ω)
rms
Load resistance: 0(4) ~ 20 mA: ≤ 550 Ω; 0 ~ 10 mA: ≤ 1.1 kΩ
0(1) ~ 5 V: ≥ 1 MΩ; 0 ~ 10 V: ≥ 2 MΩ
Transmission characteristics (25 ℃ ± 2 ℃):
Response time: ≤ 0.5 s
Temperature drift: 30 ppm/℃
Cold junction compensation accuracy: ± 1 ℃ (Preheated
for 10 minutes)
Cold junction compensation range: -20 ℃ ~ +60 ℃
Electromagnetic compatibility: Accordance to IEC 61326-3-1
Dielectric strength (1 mA leakage current, 1 minute test
time):
≥ 1500 V AC (Input /Output/Power supply)
Insulation resistance: ≥ 100 MΩ (Input /Output/Power supply)
Ambient conditions:
Operation temperature: −20 ℃ ~ +60 ℃
Relative humidity: 10% RH ~ 90% RH (40 ℃)
Atmosphere pressure: 80 kPa ~ 106 kPa
Storage temperature: −40 ℃ ~ +80 ℃
Power dissipation:
0.8 W (24 V DC, single output)
1.2 W (24 V DC, double output)
èModel rules
NOTE:Output signal
èWiring diagram