8
LINKING ACTIONS
In addition to having properties and being linked to
controller data, components can have “Actions” which will be
performed, for example when a component such as a button
is clicked. To set an action select “Actions…” on the right-
click menu then click the “lightening” symbol alongside the
action type. A further menu level then allows you to set the
action such as “Go to page”, “Set variable” or even “Execute
command” which will execute a line of BASIC. The BASIC
line can include colon “:” separators to allow some multi-line
sequences to be executed.
USING CHINESE FONTS WITH UNIPLAY
The Uniplay panel runs Windows 7 Embeded and has Microsoft
JhengHei font installed both in standard and bold thickness.
These fonts should also be selected in Motion Perfect so that
they can be correctly rendered on both the Uniplay HMI and
the PC. If other fonts are selected they may render in the
editor on the PC but will not appear on the Uniplay.
SOFTWARE INSTALLATION
The UNIPLAY HMI device software runs on the Windows
operating system installed on the panel. No additional
software installation is required to use the Uniplay HMI
system. Installation of any additional software on the device
by users will invalidate the warranty.
INSTALLATION ENVIRONMENT
The Uniplay is designed for industrial use. The temperature
operating range is 0 to 50°C It may not be suitable for using in
certain outdoor applications.
NEMA I/P RATING
The Uniplay front bezel is NEMA 4/IP65 rated. When installed
properly in a NEMA 4/IP64 panel, the NEMA 4 rating of the
panel will not be compromised. This means that uids will not
enter the panel during wash downs.
ELECTRICAL ENVIRONMENT
The Uniplay 7 / 10 has been tested to conform to European
CE requirements. This means that the circuitry is designed to
resist the eects of electrical noise. This does not guarantee
noise immunity in severe cases. Correct wire routing and
grounding will insure proper operation.
MECHANICAL ENVIRONMENT
Avoid installing units in environments where severe
mechanical vibration or shocks are present.
ENVIRONMENTAL CONSIDERATIONS
• The Uniplay are to be used indoors as built in displays.
Make sure that the display are installed correctly and that
the operating limits are followed.
• Do not operate the unit in areas subject to explosion
hazards due to ammable gases, vapours or dusts.
• The unit should not be installed where large temperature
variations and/or high humidity is present. This will cause
condensation in the device.
• Do not install Uniplay in environments where have
inammable gases.
MOUNTING
Care should be taken when locating equipment behind the
unit to ensure that a.c. power wiring, PLC output modules,
contactors, starters and relays, and any other source of
electrical interference are located away from the back of
the unit. Particular note should be taken to the position of
variable speed drives and switching power supplies. Their
input and load cables should be screened to a central star
earth point.