TX7930 Handheld Programmer
Installation& Operation Manual
4050100262-Rev1.2-1217
TANDA UK
Specifications aresubjectto changew ithout prior notice
3 Programming
Note: The Tanda device are equipped with variety of features and options that user can select or
programonsite according to the project requirement and application. This manual cannot contain
all theinformation’s for each device. We recommend referring to the specific device operation
manual for more details.
For TX7100 Intelligent Optical Smoke detector refers to Operation Manual 4050100265
For TX7110 Intelligent Heat Detector refers to Operation Manual 4050100263
For TX7120 Intelligent Optical Smoke and Heat Detector refers to Operation Manual 4050100264
For TX7130 Conventional Beam Detector refers to Operation Manual 4050100256
For TX7140 Addressable Manual Call Point refers to Operation Manual 4050100269
For TX7200 Addressable Input Module refers to Operation Manual 4050100266
For TX7210 Addressable Input/output Module refers to Operation Manual 4050100267
For TX7220 Addressable Dual Input/output Module refers to Operation Manual 4050100268
For TX7300 Addressable Sounder Strobe refers to Operation Manual 4050100270
For TX7320 Addressable Sounder refers to Operation Manual 4050100271
3.1 To Read
Selecting this feature allow user to view the device details and configurations. For example in TX7110
Intelligent Heat detector.
1. Switch-on the programmer, then press button “Read” or “1” to enter to Read mode (Figure 6).
The programmer will displaythe configurationafter few seconds. (Figure 7)
2. Press “Exit” key to go back Main Menu. Press “Power” key to switch off the programmer.
3.2 To Write
Selecting this feature allow user to write the new address number the device. For example in TX7100
Intelligent Optical Smoke detector.
1. Connect the programming cable to Z1 and Z2 terminals (Figure 2). Press “Power” to switch on
the unit.
2. Switch-on the programmer, then press button “Write” or number “2” to enter Write Address
mode (Figure 8).
3. Input the desire device address value from 1 to 254, and then press “Write” to save the new
address (Figure 9).
2. Write T
3. R/W Config 7
4. Set
Category: A1R
ID: 123456789012
Address:Uniquenumber
assigned
Category: Detectortype
ID: Detectorserial number