PROGRAMMER FOR START, FLAME SUPERVISION
AND SAFE STOP OF BURNER
PRODUCT: PRG-SE-C
- O2 TECHNICAL SHEET 1/11
Costumer Service 55 11 3019-1616
For further det ils see technic l bulletin
SELCON SISTEMAS ELETRÔNICOS DE CONTROLE LTDA
CNPJ 56 935 877/0001-29
Street Américo Samarone, 502 • CEP 04284-000 • Moinho
Velho • São Paulo • SP • Tel Fax: (55 11) 3019-1616
http://www.selcon.com.br
Representative or Distributor:
1/11
SELCON
Automação Industrial
Selcon Ltda., keeps the right to modify this technical sheet
when never it is necessary
–
February/10
•
A
PPLICATION
Programmer PRG-SE-C-O2 equipment recommended for start, flame supervision and safe stop for
any type of burner for up to two stages of flame, in commercial applications or industrial and fuels gas
or light liquids, with a cycle of use do not continuum (on/off burner Period in less than 24 hours)
For use in closed combustion camera, the user should provide safe system of pre-purge
before each sequence of start, or require the programmer PRG-SE-C-O2 with purge timer coupled,
since that the times offered are appropriate for application
Entry for flame sensor for ionization See electrode sensors for ionization, line SEL-HT-I (standard) or
SEL-HT-E (electrode mounted on a drawing or sample of the client)
This roduct meets the requirements of the standard NBR 12313 of ABNT-review
Se t./2000.
•
T
ECHNICAL
D
ATA
⇒
⇒⇒
⇒
Watch dog micro process – safe failure.
⇒
⇒⇒
⇒
Supply/frequency: 90 a 250Vca 50/60 Hz ± 3% or 24Vcc (-10 +20%).
NOTE: To su ly network CA, consisting of hase/neutral, should consider the
ossible need for its reversal (terminals 9 and 10), for flame sensor circuit not
lose sensitivity and therefore the ca acity to detect signal of flame. See below
diagram for the connections AC and DC.
⇒
⇒⇒
⇒
Consumption of energy: 5 VA
⇒
⇒⇒
⇒
Protection against tension outbreaks
⇒
⇒⇒
⇒
Protection fuses retardate the internal circuitry (0,25A) and for the control outputs (6,3A)
⇒
⇒⇒
⇒
Temperature of work: 0 at 60 ºC
⇒
⇒⇒
⇒
Storage ambient temperature:
-
5° a 65 °C
⇒
⇒⇒
⇒
Maximum relative humidity of environment in operation: 90% (40 ± 2°C) – NBR 5291
⇒
⇒⇒
⇒
Flame Sensor : Ionization.
⇒
⇒⇒
⇒
Minimum current flame for supply of 90 at 250Vca: 2 microampers dc (uA).
⇒
⇒⇒
⇒
Minimum current flame for supply in 24 Vcc: 7 uA microampers dc (uA).
NOTE: The cable of flame sensor must be installed se arately from other cables that
are art of the command set of the burner. The best ty e of cable recommended for
this ur ose is used for ignition.
⇒
⇒⇒
⇒
Protection against short circuit failure sensor ionization for mass.
⇒
⇒⇒
⇒
Blocking with local signaling (type LED) and remote (contact of relay N.A.)
⇒
⇒⇒
⇒
With verification of premature flame or false flame signal, before starting the burner.
⇒
⇒⇒
⇒
Purge Time: 10 or 20 seconds (see field code for request)
⇒
⇒⇒
⇒
Maximum time for confirmation of contact closure of the
PS
of combustion air: 5 sec.