Salda MB-GATEWAY Manuel utilisateur

Remote control console
MB-GATEWAY
Quick Start Guide
P0114_AZ_0003
If connection fails (you have forgotten the password, IP address, etc.),
you can always restore to factory settings:
1. Switch o the power source;
2. Open the upper cover;
3. While holding the button pressed, switch on the power source;
4. Wait until the LED indications of the RJ45 connection begin ash-
ing;
5. The factory settings are restored as soon as the press-button is
released.
RESTORING TO FACTORY SETTINGS
Software upgrading requires a microSD card
SOFTWARE UPGRADING
1. Downloading (http://salda.lt/lt/products/category/products/) up-
grade FIRMWARE.BIN and writing it to the microSD root catalogue.
2. If writing through the FTP client, the power source should not be
switched o.
3. If writing when the microSD card is removed from the module, the
power supply of the module must be switched o when inserting the
card.
4. Insert the card and connect the power supply.
5. If the le is proper, the module begins the upgrading procedure. The
RJ45 LED lamps ash alternately around every 1 s. The power source
must not be switched o during this process.
6. After around 5 minutes, the module completes upgrading and
switches to the normal status.
7. After upgrading, FIRMWARE.BIN is erased automatically.
RJ45 connection LED indications
• Both LED indications ash slowly and evenly – the MB-GATEWAY
has no software installed.
• The LED indications ash slowly and alternately – the software
upgrading is in progress.
• LED indications do not light – no power source and/or connection
with the Ethernet network.
Should any problems arise in the course of upgrading, please address
the local distributor.
This module also has an FTP server, so the content of the microSD
memory card can be accessed and edited without removing the card.
The login data of the FTP server are the same as those of the pro-
tected WEB pages. Make sure to indicated Passive Mode in the FTP
client programme.
FTP SERVER
B2
B3
B5
B4
B6
B7
B8
B1
Number Function
Selecting the user environment language
Selecting the desired theme colour
Opening the MB-GATEWAY settings window
Opening the device settings window
Opening the automatics control window If the parameters of
RS485 communications line are set improperly or the device is
connected improperly, a message of failed search of the con-
trol panel is displayed upon pressing B4
Opening the help PDF window
The selected ventilation device is displayed
The displaying of this window at the time of the opening of the
page is activated/deactivated
B1
B2
B3
B4
B5
B6
B7
B8
TECHNICAL SPECIFICATIONS
Parameter Units Value
Anchoring Surface, DIN rail
Voltage [AC/DC] 12 V - 25 V (2 W) (included in the
supply with an AC/DC adapter)
Communications line Ethernet RJ45, ModBus RS485
Cable length [m] UTP cable (1 m)
RS485 communications cable with
RJ10/RJ45 plugs (2 m)
RS485 communications cable with
RJ10/RJ10 plugs (2 m)
Power source [mm]/[m] 73 x 40 x 38 mm/Cable – 1 m
Dimensions
(W x H x D)
[mm] 90 x 36 x 58
Package dimensions [mm] 140 x 110 x 86
Package weight [g] 340g ±10g
Protection class IP-20
Ambient temperature [°C] -20 +70
Relative humidity [%] 30-85 (without condensation)
SERVICE MODE
MB-GATEWAY service mode is triggered by holding down user button
for 2 seconds, while power is on. Service mode is indicated by slow
(constant period) ashing of orange RJ45 LED. MB-GATEWAY IP ad-
dress in service mode is 192.168.0.51
Deactivation of DHCP / setting of TCP/IP static parameters
1. In the computer, to which you will connect the device, you should
set the static parameters of the TCP/IP panel. These settings de-
pend on the OS (see OS documents):
• the IP address should be in a range 192.168.0.1 – 192.168.0.254
(except 192.168.0.51), for example, 192.168.0.11;
• subnet mask ‒ 255.255.255.0.
2. Connect MB-GATEWAY to the congured computer with a UTP
(RJ45) cable (included in the supply). If it fails to operate (the com-
puter fails to support Auto MDI-X), the computer and MB-GATEWAY
should be connected to the network switch.
3. Connect the power supply unit (included in the supply) and hold
down user button for 2 seconds until MB-GATEWAY switches into
the service mode. Test the network connection using PING from
Command Prompt: ping 192.168.0.51
4. In the address window of the internet browser (Google Chrome
is recommended), enter 192.168.0.51 (MB-GATEWAY IP address
in service mode).
5. In the Web page that appears, select B3 ‒ MB-GATEWAY setting
window. Switch o DHCP support. Set TCP/IP static parameters.
If it is planned to interconnect several MB-GATEWAY in the local
network, they must be assigned unique IP addresses. After restart,
MB-GATEWAY will be available in the network by the new IP ad-
dress you have assigned to it.
POSSIBLE ERRORS AND THEIR SOLUTION
Problem Solution
Time indications are not
saved after restarting the
equipment
Check whether the spare power battery
is inserted
Failed connection to the ven-
tilation unit (Connection lost
or Control board not found
message)
• Check the connection settings;
• Check the power source;
• Check the communication cables (Eth-
ernet, PRV/MCB);
• Check the communication conguration
switches on the MCB or miniMCB panel;
The WEB environment is not
displayed after entering the
IP address in the browser
window
Check whether the microSD card is
inserted properly
The MB-Gateway module
does not operate / the indica-
tors on the RJ45 connection
do not ash after connecting
a power source and commu-
nication cables
Address the supplier
DISPOSAL
• In managing the waste equipment, comply with eective rules.
• In order to reduce impact on the environment and public health, re-
move the equipment to an electronics waste site or container.
• For detailed information concerning processing, address the seller
supplier.
Waste electrical and electronic equipment

SAFETY INSTRUCTIONS AND WARNINGS
Basic safety instructions.
1. Make sure that the equipment is operated only within the speci-
ed temperature interval.
2. Protect the equipment inside against the penetration of moisture.
3. Protect the equipment against direct sunlight.
4. Protect the equipment against mechanical damage (shocks,
scratches, etc.).
5. Installation works may be performed only by a qualied person.
6. Electrical connection shall be performed in compliance with the
circuit diagrams and technical requirements specied by the man-
ufacturer.
7. Protect the equipment against the penetration of foreign objects.
The MB-GATEWAY network module is intended for the connec-
tion of SALDA ventilation units to the computer (Ethernet) net-
work:
• Ventilation units and other appliances controlled by PRV control-
lers (RIS EKO 3.0, RIRS EKO 3.0, Smarty 3R VER/VEL 3.0), MCB/
Mini-MCB (Smarty, modular and compact ventilation units);
• Modbus-controlled units.
Functions of the module
• TCP/IP Modbus gateway;
• BACnet/IP gateway;
• IPv4 protocol;
• DHCP protocol;
• NetBIOS/hostname;
• WEB server;
• FTP server;
• Formation of Modbus commands/responses to HTTP queries;
• authorised login;
• automated data transmission between Modbus devices;
• data logger;
• dateTime synchronization;
• module software upgrading through the microSD memory card
(the upgrade can also be written through the FTP client);
• RTC;
• galvanically insulated RS485 communications line.
DESCRIPTION
Attention!
• Some clauses of this Guide may be inapplicable to your equipment – it
depends on the type of the control panel of the unit.
• Always choose accessories manufactured by Salda UAB. Otherwise,
no warranty would apply.
• 1 x MB-GATEWAY unit;
• 1 x power source;
• 4 x power source adapters;
• 1 x microSD card (in the MB-GATEWAY unit) with an SD adapter;
• 1 x UTP cable (RJ45 ↔ RJ45);
• 1 x MCB cable (RJ10 ↔ RJ45);
• 1 x PRV cable (RJ10 ↔ RJ10);
• Quick Start Guide.
MB-GATEWAY ACCESSORIES
MB-GATEWAY INSTALLATION
The MB-GATEWAY installation diagram of is shown on Fig. 1. Instal-
lation stages:
1. Connect MB-GATEWAY to the ventilation unit.
• Use an MCB cable with RJ10 ↔ RJ45 connection (included in
the supply), so that to connect with the ventilation unit equipped
with an MCB or miniMCB control panel (Fig. 2, 3);
• Use a PRV cable with RJ10 ↔ RJ10 connection (included in the
supply), so that to connect with the ventilation unit equipped with
a PRV control panel (Fig. 4);
2. Connect MB-GATEWAY to the network switch with a UTP cable
(included in the supply).
3. Connect the supply source (included in the supply).
4
MCB MiniMCB
PRV
PRV cable
MCB cable
MCB cable
UTP cable
LED indications of the RJ45 connection:
• The green LED indication lights continuously and the orange one
ashes in random intervals ‒ MB-GATEWAY has successfully con-
nected to the Ethernet network;
• The green LED indication does not light – no connection with the
network switch;
• The green LED indication lights continuously and the orange one
begins ashing in equal time intervals after around 30 s from switch-
ing on power supply – the service mode is set for MB-GATEWAY
(read the Service Mode).
32
1
INSTALLATION
The module can be installed (Fig. 5) in any position convenient to
the user (it is recommended to install it on a rail, while ensuring the
conditions listed below)
• ambient temperature: -20°C to +70°C;
• relative humidity: 30% to 85% (no condensate is allowed);
• protection against vertically dripping water drops (IP 20).
5
According to the factory settings (by default), MB-GATEWAY host-
name is MBGW plus the last six symbols of the MAC address (Fig.
7), e.g. mbgw900154.
In the window that appears (Fig. 8), enter the login data: according
to the factory settings (by default), the login name is admin and the
password is admin.
6
7 8
If you have done everything properly, MB-GATEWAY Web interface
will open.
MB-GATEWAY WEB INTERFACE
In the address window of the internet browser (Google Chrome is rec-
ommended) (Fig. 6), enter MB-GATEWAY hostname.
Table des matières
Autres manuels Salda Unité de contrôle
Manuels Unité de contrôle populaires d'autres marques

Festo
Festo Compact Performance CP-FB6-E Manuel de la liste des pièces

Elo TouchSystems
Elo TouchSystems DMS-SA19P-EXTME Manuel utilisateur

JS Automation
JS Automation MPC3034A Manuel utilisateur

JAUDT
JAUDT SW GII 6406 Series Guide rapide

Spektrum
Spektrum Air Module System Manuel utilisateur

BOC Edwards
BOC Edwards Q Series Manuel utilisateur