Field wiring
All wiring from the supply and to the gas valve carries mains voltage (230v ac nominal). The current edition of the IEE Wiring
Regulations should be strictly adhered to, wiring and connections should be made by a suitably qualified electrician or competent
person.
The field wiring voltage to the interlock inputs is reduced to 24 volts, do not connect mains to the air pressure switch terminals,
e-stop, analogue input/output 0-10v control, gas detector or fire alarm terminals.
Please follow the first fix wiring schedule set out below:
1) Main supply 2 core + E 1.5mm (as per regulatory requirements)
2) Gas valve 2 core + E 1.5mm (as per regulatory requirements)
3) Pressure switches 2 core + E 1.5mm (YY type cable)
4) Fire alarm interlock (if req) 2 core + E 1.5mm (FP type cable)
5) Emergency stops 2 core + E 1.5mm (YY type cable)
6) Gas detection equipment, If fitted, 3 core screened (CY type cable)
7) Gas pressure switch, if fitted, 2 core + E 1.0mm (YY type cable)
8) 0-10v signal wiring, if fitted, 2 core 1.0mm (CY type cable)
KVM SF Dip switch settings
On the fascia pcb there are 6 dip switches. Below is their function:
1. OFF (gas proving disabled) ON (gas proving enabled)
2. OFF (supply & extract fans used) ON (extract only)
3. OFF (CO2 detector not fitted) ON (CO2 detector fitted)
4. OFF (extractor sensed on spare input terminals) ON (extractor fan sensed on board current sensors)
5. OFF (supply sensed on spare input terminals) ON (supply fan sensed on board current sensors)
6. OFF (temp sensor fitted in kitchen space) OFF (temp sensor fitted in canopy)
INSTALLATION
GUIDE
KVM-SF
Where multiple supplies enter a control
panel, perhaps in a current sensing
interlock. It is preferable that each supply
is on the same phase. If this can’t be
achieved, then additional warning labels
should fixed in a suitable location on the
control panel.
The advice given on these
instruction pages,
specifically to cable types
and ratings may change
depending on cable lengths
and installation conditions.
If you are not sure about
any of the cable types or
ratings then contact our
technical support team.