3
OVERVIEW
The VarCom 1600 and 2600 Capacitor Controls utilize user selectable functions and
parameters to control switched capacitor banks. The VarCom 1600 controls with time,
temperature and voltage and the VarCom 2600 add Amps and KVAR control.
TIME - The Control will close the capacitor bank when the user selected CLOSE TIME occurs.
The Control will open the capacitor bank when the user selected OPEN TIME occurs. Both
settings are subject to the weekend settings.
OLTAGE - The Control will close the capacitor bank when the sensed line voltage drops
below the user selected CLOSE VOLTS setting. The Control will open the capacitor bank
when the sensed line voltage rises above the user selected OPEN VOLTS setting.
TIME WITH OLTAGE O ERRIDE - The Control will function according to the time mode,
except the time mode operating conditions will be overridden by voltage conditions
according to the volt mode function.
TEMPERATURE - For Summer Schedule (defined by CLOSE TEMP greater than OPEN TEMP
setting) - the Control will close the capacitor bank when the sensed ambient temperature
rises above the user selected CLOSE TEMP setting. The Control will open the capacitor bank
when the sensed ambient temperature drops below the user selected OPEN TEMP setting.
For Winter Schedule (defined by OPEN TEMP greater than CLOSE TEMP setting) - the Control
will close the capacitor bank when the sensed ambient temperature drops below the user
selected CLOSE TEMP setting. The Control will open the capacitor bank when the sensed
ambient temperature rises above the user selected OPEN TEMP setting.
TIME WITH TEMPERATURE O ERRIDE - The Control will function according to the time
mode, except the time mode operating conditions will be overridden by temperature
conditions according to the temp mode function.
TEMPERATURE WITH OLTAGE O ERRIDE - The Control will function according to the
temp mode, except the temp mode operating conditions will be overridden by voltage
conditions according to the volt mode function.
TIME WITH OLTAGE AND TEMPERATURE O ERRIDE - The Control will function according
to the time mode, except the time mode operating conditions will be overridden by
temperature conditions according to the temp mode function and/or by voltage conditions
according to the volt mode function. Voltage will override both time and temperature.
AMPS - The control will close the capacitor bank when the line amps drop below the user
selected Amps setting. The control will open the capacitor bank when the line amps rise
above the user selected Amps setting.
AMPS WITH OLTAGE O ERRIDE - The Control will function according to the Amps
settings, except the Amps setting operating conditions will be overridden by voltage
conditions according to the volt mode function.
K AR - The Control will close the capacitor bank when the line KVAR rises above the user
selected KVAR setting. The Control will open the capacitor bank when the line KVAR drops
below the user selected KVAR setting.
K AR WITH OLTAGE O ERRIDE - The Control will function according to the KVAR
settings, except the KVAR setting operating conditions will be overridden by voltage
conditions according to the volt mode function.