FE GX200 Series Manuel utilisateur

Fuji Electric Co., Ltd.
USER’S MANUAL
Uninterruptible Power Supply
GX200 Series (1.5kVA, 3kVA)
Model M-UPS015AE2S
M-UPS015AE2R
M-UPS030AE2B
M-UPS030AE2R
M-UPS030AE2C
INR-HG5980

For safe use
High-safety uses
This product is designed and manufactured for the general use, such as
general office use and personal use, and is not designed and manufactured
for uses (control of nuclear reactions at the nuclear facilities, aircraft flight
control, air traffic control, mass transport control, medical life support
systems, and missile launch control in weapon systems, etc.) that require a
high degree of safety, and can cause death or serious injury if the required
safety is not maintained. Do not use this product without carrying out
measures to ensure the required safety for such a use. If using this product
for such a use, consult with our sales representatives.
Prevention of radio interference
Important
This product is class A information technology device based on the
standards of the Voluntary Control Council for Interference by Information
Technology Equipment (VCCI). Use of this product in a residential area
may cause radio interference. In this case, the user may be required to
take appropriate action.
Prevention of Harmonic Current Interference
The products are based on the JIS C61000-3-2.
All rights reserved. Copyright Fuji Electric Co., Ltd. 2012
i
Handling of this manual
This manual contains important information for safe use of the product.
Please read this instruction manual carefully before using the product to
ensure that you fully understand the product.

ii
Attention: Information in this manual is subject to change without notice.
Caution about Safety
Warning Indicates high risk of death or serious injuries when the
Important
The condition of the UPS
LED Indications
Lit
Flashing
Out
Ca ution
Following warning signs are included to prevent the user from damaging
the UPS and the connected devices.
product is not used properly.
Improper use could cause mild injuries and damage the
UPS and the connected device.
“Important” indicates caution about the use of the UPS.
Warning Signs
LED Indications
Symbols

iii
Caution about safety
Electric shock Do not remove the cover of the UPS.
High voltage parts inside UPS may cause electrical shock.
CAUTION
“CAUTION” indicates that slight or moderate injury may
result, the UPS or user's property may be damaged.
Electric
shock Injury
Do not insert fingers or sticks into a cooling fan or ventilation
hole. Doing so may cause electric shock or injury.
Electric shock Only maintenance personnel must perform the maintenance
including the replacement of battery and cooling fan.
Connect the AC input plug to a grounded power outlet, or
connect the ground wire to the ground terminal. (class D
grounding)
Commercial power supplies usually have electrodes on
the grounded and ungrounded sides, in addition to the
grounding electrode (earth). Check before connecting.
Connecting in reverse may cause malfunction by noise or
electric shock.
Warning "Warning" indicates that death or serious injury may occur.
Electric
shock Failure
When inspecting or servicing the UPS, turn off the power
to the connected device (equipment connected to the
UPS) and the UPS. For M-UPS015AE2S, pull the AC input
plug on the back of the UPS from the input power outlet.
For M-UPS015AE2R and M-UPS030A2E□, turn off the
input breaker on the rear of the UPS and disconnect the
AC input terminals (R, S). Failure to do so may cause
electric shock.
•List of important warnings: Risks when UPS is not used correctly

Caution about safety
iv
Injury Do not step on or put an object on the UPS.
Doing so may cause injury.
Injury
Damage
The UPS is heavy. Caution in handling the UPS.
Take out the UPS in a level and flat place.
The weight of the UPS is as follows:
M-UPS015AE2S : 24 kg (12 kg without batteries)
M-UPS015AE2R : 26 kg (14 kg without batteries)
M-UPS030AE2B : 47 kg (23 kg without batteries)
M-UPS030AE2R : 42 kg (18 kg without batteries)
M-UPS030AE2C : 48 kg (24 kg without batteries)

Caution about safety
v
Damage
This UPS is not designed for medical equipment that comes in
contact with the human body.
Do not place objects affected by magnetism near the UPS.
Have the voltage set within the range of the input connected device.
Failure to do so may damage the connected device.
Replace the battery with a new one specified by Fuji.
Using unspecified batteries or mixing old and new batteries may
cause UPS failure or trouble.
When performing a rolling blackout, or when unplugging the AC
input plug from the input power outlet, or when turning off the input
breaker on the rear of the UPS, make sure that the RUN LED
(green) is flashing slowly (1.6 second cycle).
When the distribution board breaker is turned off, the AC input plug
is unplugged from the input power outlet, or the input breaker on the
back of the UPS is turned off, the built-in battery is discharged
because the condition is the same as a power failure when the RUN
LED is lit.
This may cause battery deterioration and shorten the battery
replacement cycle.
Warning label
Never remove the labels.

vi
Caution for Use
Important
Do not install and store the UPS in the following places:
Outdoor location
Exposed to the wind and rain
Extremely humid and dusty
With corrosive gas or salt
Direct sunlight
Near sparks or heating element
Extremely hot or cold, where the temperature fluctuates greatly
With vibration and shock
Do not perform the battery check in succession.
When the battery check is performed, the internal battery actually discharges
to check the voltage. Consecutive battery checks may cause battery
degradation and shorten the battery replacement cycle.
If the UPS is not used for a long time, charge the battery every two
months.
Charge the battery by operating the UPS for 12 hours or more every two
months. After charging the battery, perform the battery check.
If the UPS is not used for a long period of time, the battery may become over-
discharged due to self-discharge, rendering the UPS unusable.
Disposal of used battery has legal restrictions
Please follow any local, county, regional or state guidelines for the disposal of
batteries.
Do not block the vent hole and cooling fan, do not use UPS where the air
is not well ventilated.
The UPS is equipped with vents and cooling fans to cool the inside of the
UPS; the internal and ambient temperatures of the UPS may deviate from the
rated specifications.
Replace the cooling fan periodically.
Continued use after the fan has reached the end of its service life may cause
the internal temperature of the UPS to exceed its rating.

Caution for Use
vii
The allowable voltage between the UPS input electrical cable and ground is
250VAC.
Applying a voltage of 250 VAC or higher may damage the filter circuit in the input
section.
The input surge voltage withstand capability of this device is 2kVpeak (1.2 x
50μsec).
Applying a surge voltage exceeding 2kV peak may damage the filter circuit in the
input section.
The input voltage of the UPS is 160VAC to 288VAC.
If the input voltage is different from the above, prepare a transformer for voltage
conversion other than this product. If a voltage outside the input voltage range is applied,
the UPS may be damaged.
The input voltage of the UPS should not exceed the input voltage range of
connected equipment.
During bypass operation, the input voltage to the UPS is directly output as output
voltage. If a voltage exceeding the input voltage range of the connected equipment
is applied, the connected equipment may be damaged.
Avoid single wire grounding on the output side.
The UPS is not insulated between input and output. Doing so may cause
malfunctions or failures due to noise.
When connecting the UPS to a 3-phase power supply, be sure to connect
the grounding side of the 3-phase power supply to the grounding electrode on
the AC input of the UPS.
Connect the grounded phase of the three-phase power supply system to the
grounded pole of the AC input of the device. Connection to an ungrounded power
supply may cause malfunction.
Voltage variation: from 160Vac to 288Vac
Frequency variation: within 5% of rated frequency (less than 1Hz per second)
Voltage waveform distortion: 5% or less
Voltage zero-cross condition: No more than one zero-crossing during one cycle
50Hz or 60Hz
4 zero crossings - NG

viii
Contents
Introduction............................................................................................................................... i
1 Unpacking
1.1 Opening the package...........................................................................................1
Opening the package
Contents of the package
2 Overview
2.1 Name and Main Function of Each Part .............................................................. 2
2.2 How the Product Works.................................................................................... 5
During normal operation
Battery power failure
Automatic bypass operation
Manual bypass operation
3 Installation
3.1 Installing the UPS ................................................................................................ 7
Caution about installation
Determining an installation location
Installation Method
3.2 Connecting the cable .........................................................................................12
Caution about connecting the cable
Preparation before connection
Connecting the output cable
Connecting the input cable
3.3 Interface port ...................................................................................................... 16
CN1 (standard monitoring interface)
CN2 (PC interface)
Setting up the Output Voltage ........................................................................... 18
3.4
4 Running
4.1 Turning on the UPS.............................................................................................. 20
Check cable connections
Turning on the UPS
Turn ON the power for connected equipment
4.2 Turning off the UPS ............................................................................................. 23
Turning off the connected device
Turning off the UPS
5 Maintenance
5.1 Inspection ............................................................................................................. 25
Daily Maintenance
5.2 Operation for Planned Power Outages .............................................................. 27
Operation before planned power outage
Operation after planned power outage
5.3 Inspecting the Battery........................................................................................... 29
Checking UPS status
Using the manual check function
Charging the battery

Contents
ix
6 Troubleshooting
6.1 Warning Beep Sound ...................................................................................... 39
6.2 Operation Mode List ....................................................................................... ... 40
LED Flashing Type
Warning Sound Type
List of motion modes
5.4 Replacing the Battery ........................................................................................ 33
Timing of battery replacement
Method of battery replacement
Disposal and storage of battery
5.5 Replacing the Cooling Fan ................................................................................ 36
Timing of cooling fan replacement
Method of cooling fan replacement
5.6 Storing UPS ........................................................................................................ 38
Pre-Storage Operations
UPS stored longer than two months
7 Appendix
7.1 Rated specification............................................................................................. 45
7.2 Additional Description for UL Type................................................................... 47
Autres manuels pour GX200 Series
1
Ce manuel convient aux modèles suivants
5
Table des matières
Autres manuels FE UPS
Manuels UPS populaires d'autres marques

Pylontech
Pylontech Victron & Pylontech US5000 Manuel utilisateur

Tecnoware
Tecnoware EVO DSP PLUS MM 6.8 Manuel utilisateur

Mecer
Mecer ME-1000-WTU Manuel utilisateur

Mustek
Mustek PowerMust 530(B) Plus Manuel d'installation et d'exploitation

Emerson
Emerson Liebert NXL series Manuel utilisateur

MAKELSAN
MAKELSAN BOXER SERIES Manuel utilisateur