FE GX200 Series Manuel utilisateur

USER’S MANUAL
Uninterruptible Power Supply
GX200 Series (5kVA, 7.5kVA, 10kVA)
Model M-UPS050AD2B
M-UPS075AD2B
M-UPS100AD2B
INR-HG5687

For Safe Use
High-safety uses
This product is designed and manufactured for the general use, such as
general office use and personal use, and is not designed and manufactured for
uses (control of nuclear reactions at the nuclear facilities, aircraft flight control,
air traffic control, mass transport control, medical life support systems, and
missile launch control in weapon systems, etc.) that require a high degree of
safety, and can cause death or serious injury if the required safety is not
maintained. Do not use this product without carrying out measures to ensure
the required safety for such a use. If using this product for such a use, consult
with our sales representatives.
Prevention of radio interference
Important
This product is class A information technology device based on the standards of
the Voluntary Control Council for Interference by Information Technology
Equipment (VCCI). Use of this product in a residential area may cause radio
interference. In this case, the user may be required to take appropriate action.
Prevention of Harmonic Current Interference
M-UPS050AD2B conforms to the Guideline of harmonic restraint measures for
general-purpose UPS.
M-UPS075AD2B and M-UPS100AD2B conform to IEC61000-3-12.
All Rights Reserved, Copyright
c
○ Fuji Electric Co., Ltd. 2011
i
•Handling of this manual
This manual contains important information for safe use of the product.
Please read this instruction manual carefully before using the product to
ensure that you fully understand the product.

ii
Attention: Information in this manual is subject to change without notice.
Caution about Safety
Warning Indicates high risk of death or serious injuries when the
Important
The condition of the UPS
LED Indications
Lit
Flashing
Out
Ca ution
Following warning signs are included to prevent the user from damaging
the UPS and the connected devices.
product is not used properly.
Improper use could cause mild injuries and damage the
UPS and the connected device.
“Important” indicates caution about the use of the UPS.
Warning Signs
Symbols

iii
Caution about Saf et y
List of important warnings: Risks when UPS is not used correctly
Electric Shock Do not remove the cover of the UPS.
High voltage parts inside UPS may cause electrical shock.
"Caution" indicates that slight or moderate injury may occur
and the UPS or user's property may be damaged.
Electric
Shock Injury
Do not insert fingers or sticks into the cooling fan or the vent
hole. Doing so may cause electric shock or injury.
Electric shock Maintenance including daily inspections (battery replacement,
cooling fan replacement, etc.) should be performed by a
professional technician. Failure to do so may cause electric
shock.
This UPS requires grounding (Class D grounding or higher).
When connecting to the input power supply, connect a ground
wire to the AC input protective grounding terminal. Failure to
do so may cause electric shock.
Electric
Shock Failure
When connecting this UPS to the input power supply, connect the
active wire to the AC input 1/R and L2/S terminals and the
inactive wire to the ground terminal. Also, connect the ground
wire to the AC input protective ground terminal. Similarly, in the
connection between the output of the UPS and the connecting
device, connect the hot wire side wires to the AC output terminals
l1/U and l2/V and the ground wire to the output ground terminal.
Incorrect connection may cause noise, malfunction, failure, or
electric shock.
When maintaining the connected device, be sure to turn off
the power supply to the connected device. Turn off the
breaker on the distribution board and disconnect the AC input
terminals.
Failure to do so may cause electric shock.
Warning
Caution
Warning "Warning" indicates that death or serious injury may occur.

Caution about Safety
iv
Injury Do not step on or put an object on the UPS.
Injury
Damage
The UPS is heavy. Caution in handling the UPS.
Take out the UPS in a level and flat place. The weight of the
UPS is as follows:
•M-UPS050AD2B: 63kg (without battery: 29kg)
•M-UPS075AD2B: 127kg (without battery: 59kg)
•M-UPS100AD2B: 127kg (without battery: 59kg)
Fire
Damage
This UPS can be installed laying down.
When installing the UPS lying down, it should only be
tilted to the right side (clockwise) when viewed from the
front.
NG OK

Caution about Safety
v
Damage This UPS is not designed for medical equipment that comes in
contact with the human body.
Do not place objects affected by magnetism near the UPS.
Have the voltage set within the range of the input connected device.
Failure to do so may damage the connected device.
Do not operate the voltage setting switch while the UPS is operating.
The changed voltage will be output when the UPS is restarted, which may
cause damage to the connected equipment. Also, the output voltage cannot
be changed even if it is operated while the UPS is operating.
Replace the battery periodically.
Replace the battery with a new one specified by Fuji Electric. Using
unspecified batteries or mixing old and new batteries may cause UPS
failure or trouble.
When performing a rolling blackout, or when unplugging the AC input
plug from the input power outlet, or when turning off the input breaker
on the rear of the UPS, make sure that the RUN LED (green) is flashing
slowly (1.6 second cycle).
When the distribution board breaker is turned off, the AC input plug is
unplugged from the input power outlet, or the input breaker on the back of
the UPS is turned off, the built-in battery is discharged because the
condition is the same as a power failure when the RUN LED is lit. This may
cause battery deterioration and shorten the battery replacement cycle.
Warning label
Never remove the labels.

vi
Caution for Use
Important
Do not install and store the UPS in the following places:
Outdoor location
Exposed to the wind and rain
Extremely humid and dusty
With corrosive gas or salt
Direct sunlight
Near sparks or heating element
Extremely hot or cold, where the temperature fluctuates greatly
With vibration and shock
Do not perform the battery check in succession.
When the battery check is performed, the internal battery actually discharges
to check the voltage.
Consecutive battery checks may cause battery degradation and shorten the
battery replacement cycle.
If the UPS is not used for a long time, charge the battery every two
months. Charge the battery by operating the UPS for 12 hours or more every
two months. After charging the battery, perform the battery check.
If the UPS is not used for a long period of time, the battery may become over
discharged due to self-discharge, rendering the UPS unusable.
Disposal of used battery has legal restrictions
Please follow any local, county, regional or state guidelines for the disposal of
batteries.
Do not block the vent hole and cooling fan, Do not use UPS where the air
is not well ventilated.
The UPS is equipped with vents and cooling fans to cool the inside of the UPS;
the internal and ambient temperatures of the UPS may deviate from the rated
specifications.
Replace the cooling fan periodically.
Continued use after the fan has reached the end of its service life may cause
the internal temperature of the UPS to exceed its rating.

Caution for Use
vii
The allowable voltage between the UPS input electrical cable and ground is
250VAC.
Applying a voltage of 250 VAC or higher may damage the filter circuit in the input
section.
The allowable input surge voltage of this UPS is 5kV peak (1.2 x 50μs).
However, when the UPS model is "-UC" or "-C", it is 2kV peak (1.2 50μs).
Applying a surge voltage exceeding 5kV peak ("-UC" and "-C" are 2kV peak) may
damage the filter circuit in the input section.
The input voltage range of the UPS is 160VAC to 288VAC.
When input voltage is different from the rated voltage, install a transformer
outside the UPS to convert the voltage. Applying a voltage higher than the input
voltage range may damage UPS.
Connect the UPS to the input power supply within the rated input voltage
range of the connection device.
This UPS can operate up to 288 VAC. However, the input voltage of general
equipment is 200 VAC ±10%. Therefore, if a voltage of 220 VAC is applied to the
UPS and switched to bypass operation, a voltage exceeding the specification will
be applied to the connected equipment. The input voltage should be in
accordance with the specifications of the connected equipment.
Do not apply single-line grounding on the output side.
There is no insulation between the input and output of the UPS. Therefore, do not
single wire ground the output side. Noise or malfunction may cause trouble to the
connected device.
When connecting the UPS to a power supply unit with a leakage
breaker, select a leakage breaker that takes into account the total
leakage current of the UPS and the leakage current of the connected
equipment.
When connecting the UPS to a 3-phase power supply, be sure to connect the
grounding side of the 3-phase power supply to the grounding electrode on
the AC input of the UPS.
Connecting to an ungrounded power supply may result in malfunction.

Caution for Use
viii
When using a generator temporarily during a planned power outage, use a
generator that meets the following specifications.
Connecting a generator that does not meet the following specifications to the input
section of the UPS may cause the UPS to malfunction or be damaged.
Voltage regulation: depend on the input specification of the connected device
Frequency variation: within 5% of rated frequency
Voltage waveform distortion: within 5%
Voltage zero-cross condition: No more than one zero-crossing during one cycle
50Hz or 60Hz
4 zero crossings - NG

ix
Contents
Introduction ................................................................................................. i
1 Unpacking
1.1 Opening the Package ............................................................................. 1
2.1 Name and Main Function of Each Part .............................................. 2
2.2 How the Product Works ....................................................................... 5
3
During normal operation
Battery power failure
Automatic bypass operation
Manual bypass operation
Installation
3.1
Installing the UPS ................................................................................. 7
Caution about installation
Determining an installation location
Installation method
3.2
Connecting the Cable ........................................................................... 12
Caution about connecting the cable
Preparation before connection
Connecting the output cable
Connecting the input cable
3.3
Interface Port ....................................................................................... 16
CN1 (No-voltage contact signal interface)
CN2 (RS-232C interface)
3.4
Setting up the Output Voltage ............................................................... 18
The setup procedures of the rated output voltage
4 Running
4.1
Turning on the UPS............................................................................. 20
Check cable connection
Turning on the UPS
Turning on the power to the connected device
4.2
Turning off the UPS ............................................................................ 23
5
Turning off the connected device
Turning off the UPS
Maintenance
5.1
Inspection ............................................................................................ 25
Daily Maintenance
2 Overview
Opening the package
Contents of the package
Autres manuels pour GX200 Series
1
Ce manuel convient aux modèles suivants
3
Table des matières
Autres manuels FE UPS
Manuels UPS populaires d'autres marques

Pylontech
Pylontech Victron & Pylontech US5000 Manuel utilisateur

Tecnoware
Tecnoware EVO DSP PLUS MM 6.8 Manuel utilisateur

Mecer
Mecer ME-1000-WTU Manuel utilisateur

Mustek
Mustek PowerMust 530(B) Plus Manuel d'installation et d'exploitation

Emerson
Emerson Liebert NXL series Manuel utilisateur

MAKELSAN
MAKELSAN BOXER SERIES Manuel utilisateur