Air cooled water chillers and heat pumps with radial fans
IDRA - RSC Series
Use, installation and maintenance manual 10
GB
IDRA RSC H 9 -17
Size 9 14 17
Cooling capacity (1) [kW] 8,4 12,7 16,0
Input power (1) [kW] 2,8 4,1 5,1
Heating capacity (2) [kW] 9,0 13,3 16,7
Compressors type Hermetic scroll
Compressors / circuits 1/1 1/1 1/1
Input power (each) [kW] 2,8 4,1 5,1
Max. input power (each) [kW] 5,57 7,18 8,5
Input current (each) [A] 4,7 6,9 8,6
Max. input current (each) [A] 9,7 12,5 14,8
Start-up current [A] 45,0 67,0 76,0
Capacity steps 1 1 1
Evaporators / number Plate heat exchanger/1
Liquid flow [m3/h] 1,4 2,2 2,8
Available static pressure [kPa] 43,0 60,0 47,0
Storage tank volume [l] 40 48 48
Fans Radial
Number 1 2 2
Air flow [m3/h] 2500 6000 6000
Available static pressure [Pa] 109 140 140
Max. input power (each) [kW] 0,52 0,74 0,74
Max. input current (each) [A] 3,8 7,4 7,4
Sound pressure level [dB(A)]
At 1 m from fan mouth [dB(A)] 66 71 71
Dimensions and weights
Length [mm] 1154 1154 1154
Width [mm] 679 753 753
Height [mm] 900 1350 1350
Weight [kg] 167 247 266
Refrigerant charge [kg] 2,9 3,2 3,6
(1) External air temp. 35°C, evap. water in/out temp. 12/7°C
(2) Water temp. 40/45°C, external air temp. 5°C
Size 9 14 17
Total electrical data (400 V - 3 ph - 50 Hz)
Nominal input power [kW] 3,3 5,6 6,6
Max. input power [kW] 6,09 8,66 9,98
Nominal input current [A] 8,5 21,7 23,4
Max. input current [A] 13,5 27,3 29,6
Max. start-up current [A] 48,8 81,8 90,8