enware AQUABLEND 2500 Manuel utilisateur

Part No. IS127
AQUABLEND 2500
25MM THERMOSTATIC
MIXING VALVE
For use in Australia
Call 1300 369 273
www.enware.com
Enware Australia Pty Limited
9 Endeavour Rd Caringbah NSW 2229 Australia
Ph: +61 2 8556 4000 Fax: +61 2 8556 4055
I00045_Aug _16


1
Aquablend 2500 Thermostatic Mixing Valve
Call 1300 369 273
www.enware.com
Contents
Introduction 2
Warranty 3
Safety 5
Product Range 5
Physical Description 6
Recommended Pressures & Temperatures 7
Flow Sizing Graph 8
Technical Description 9
Installation 10
Commissioning of the valve 12
Maintenance and servicing 15
Fault Finding 18
Spare Parts 20
Enware reserves the right to change any product specication or information
contained in this publication, at any time and without notice. Every care
has been taken to ensure accuracy in the Preparation of this publication
which has been issued for guidance only. No liability can be accepted for
any consequences which may arise as a result of its application. Enware =
trade mark of Enware Australia Pty Limited - A.C.N. 003 988 314
Aquablend TMV’s are exclusively manufactured for Enware Australia Pty Limited by
Reliance Worldwide, 27-28 Chapman Place, Eagle Farm, Qld, 4009 Australia.

2
Aquablend 2500 Thermostatic Mixing Valve
Call 1300 369 273
www.enware.com
Introduction
The ENWARE AQUABLEND 2500 Thermostatic Mixing Valve
is a high performance Thermostatic Mixing Valve suitable for a
wide range of applications. The valve is designed to comply with
AS4032 - Thermostatic Mixing Valves. The mixing valve has the
following features:
• Complies with the requirements of AS4032 -
Thermostatic Mixing Valves,
• Provides high stability of mixed water temperature even
under changing inlet conditions,
• Ensures rapid shut down of mixed outlet ow in the
event of hot or cold water supply failure,
• Designed for quick and simple in-situ servicing,
• Suitable for installation into AS3500 compliant systems
with hot water temperature as low as 55°C
• Fitted with a Tamper Resistant temperature adjustment
mechanism.

3
Aquablend 2500 Thermostatic Mixing Valve
Call 1300 369 273
www.enware.com
Warranty
The ENWARE AQUABLEND 2500 Thermostatic Mixing Valve is
guaranteed free from manufacturing defects for a period of 24
months, subject to the conditions outlined below:
Enware Product Warranty
Subject to the warranty conditions and exclusions set out below
ENWARE valves are warranted to be free from defects in material
and/or workmanship for a period of 24 months service life and if
found by ENWARE to be so defective will be replaced as set out
below. If the valve is sold by a party other than ENWARE then it
is sold by that seller as principal and the seller has no authority
from ENWARE to give any additional warranty on behalf of
ENWARE.
The benets of this warranty are in addition to all other rights
and remedies which the purchaser may have under the Trade
Practices Act (Cwth) or similar laws of each State and Territory
in Australia.
Warranty Conditions:
1. The valve must have been installed by a licensed plumber
in accordance with the ENWARE Installation Instructions and
Application Guidelines supplied with the valve, and in accordance
with the National Plumbing and Drainage Code AS3500 (the
Code) current at the date of installation and all relevant statutory
and local requirements in the State or Territory in which the valve
is installed.
2. Where the valve is installed outside the boundaries of a
metropolitan area as dened by ENWARE, the cost of transport
insurance and travelling shall be the purchaser’s responsibility.
(Refer to the ENWARE scale of fees for replacement of valves).
3. Where the valve comprises part of a hot water system,
installation of that system must be in accordance with its
manufacturer’s recommendations, the Code and all relevant
statutory and local State or Territory requirements.
4. The valve must be returned to ENWARE with a fully & correctly
completed ENWARE Warranty Claim Form.

4
Aquablend 2500 Thermostatic Mixing Valve
Call 1300 369 273
www.enware.com
5. Where the valve is replaced under warranty the replacement
valve carries a new warranty as detailed herein.
Warranty Exclusions:
Replacement work will be carried out as set out in the ENWARE
Warranty above, but the following exclusions may cause the
warranty to become void, and may incur a service charge
including cost of parts where:
6. Damage has been caused by accident, Acts of God, misuse,
incorrect installation of the hot water system of which the valve
forms a part or attempts to disassemble the valve.
7. It is found that there is nothing wrong with the valve.
8. The failure of the valve is due in part or in whole to faulty
manufacture/installation of the hot water system of which the
valve forms part.
9. The valve has failed directly or indirectly as a result of
excessive water pressure or temperature outside the Application
Guidelines, thermal input or corrosive environment.
10.The valve has failed due to foreign matter either from
installation or the water supply.
11.The failure of the valve is due to scale formation in the
waterways of the valve.
12.The failure of the valve is due in part, or in whole, to installation
not in conformance with the requirements of the Code.
13.ENWARE reserves the right to change its specications
without prior notice and will not accept liability for any claim
arising from such change.
14.Subject to any statutory provisions to the contrary, claims for
damage to furniture, carpets, walls, foundations or any other
consequential loss either directly or indirectly due to leakage
from the valve are also excluded from warranty cover.
TM = Trademark of
Enware Australia Pty Limited (ENWARE)
9 Endeavour Road, Caringbah NSW 2229
© All rights reserved 1996

5
Aquablend 2500 Thermostatic Mixing Valve
Call 1300 369 273
www.enware.com
Safety
The ENWARE AQUABLEND 2500 Thermostatic Mixing Valve
is a high performance valve designed to give stable and
dependable operation, provided it is installed, commissioned,
operated and maintained as per the recommendations outlined
in this manual. It should be noted however that this valve should
not be considered as an alternative to adequate supervision and
duty of care during its use and operation.
Note: When installed, the mixing valve, inlet controls, pipework
and the surrounding area may become hot, which may cause
burn injuries. Precautions should be taken to ensure that these
surfaces cannot cause such injuries.
Product Range
The ENWARE AQUABLEND 2500 Thermostatic Mixing Valve
is available complete with inlet service ttings. The inlet to the
ttings is 3/4” BSP female, the outlet from the valve is 1” BSP
male. The service ttings consist of isolating ball valves, strainers,
pressure test points and non-return valves. The strainers can be
serviced and cleaned without disturbing the installation (refer to
Maintenance & Servicing Pg 15).
The inlet service ttings also incorporate union type ttings
enabling the thermostatic mixing valve to be removed from its
installation without disturbing its pipework.
The ENWARE AQUABLEND 2500 Thermostatic Mixing Valve is
also available without inlet ttings as an option.
The schematics and dimensions of these valves with their
corresponding order codes are shown in below.
Figure 1.1
AQUABLEND
2500 – CHROME
FINISH
With 3/4” Female
Thread Inlet
Fittings – Dry
Weight 3.0kg
ATM725

6
Aquablend 2500 Thermostatic Mixing Valve
Call 1300 369 273
www.enware.com
Physical Description
Figure 1.2 located below shows a general arrangement drawing
of the ENWARE AQUABLEND 2500 Thermostatic Mixing
Valve showing the method of operation. Hot and cold water is
supplied to each side of the valve respectively. The hot water
enters through a port below the piston, the cold water enters
above the piston. Upon entry the water begins to blend and
enters the mixing tube. At this point the mixed water contacts the
thermostatic wax element. The element will extend or contract to
match the water temperature it is exposed to causing the piston
to move, thereby regulating the amounts of hot and cold water
entering the valve. This maintains the mixed water temperature
at a constant temperature.
If for instance the inlet hot pressure dropped, the ow of hot water
into the valve would be reduced. Therefore the element would
see mixed water at a reduced temperature. This would cause the
element to contract. This would move the piston downwards as
to close off more of the cold port restricting cold ow therefore
opening more of the hot port and hence reducing the cold ow
rate. This has the effect of the valve attempting to restore itself to
its original temperature setting.
Similarly if the hot inlet temperature dropped, the element would
again see blended water at a lower temperature and therefore
the element would again contract reducing the cold port piston
gap and hence supply more hot water and less cold. Once again
the valve attempts to restore itself to its original setting. This will
occur for all changing conditions including changes to ow rate,
inlet temperatures and inlet pressures.
In the event of a sudden loss of the cold water supply the piston
will shut off the hot port thus stopping any ow through the valve.
The valve will also shut down the cold supply if there is a hot
water failure.
Figure 1.2
General
Arrangement
Drawing

7
Aquablend 2500 Thermostatic Mixing Valve
Call 1300 369 273
www.enware.com
Recommended Pressures & Temperatures
MIXED OUTLET TEMPERATURE
Temperature Adjustment Range 35°-50°Celsius
INLET TEMPERATURES
Cold Supply Minimum 5° Celsius
Maximum 30° Celsius
Hot Supply Minimum 55° Celsius
Maximum 90° Celsius
Hot to Mix Temperatures
Differential for Stable
Operation
Minimum 10° Celsius
Cold to Mix Temperatures
Differential for Stable
Operation
Minimum 5° Celsius
FLOW RATES
To ensure stable outlet
conditions Minimum 6 litres/minute
Maximum 85 litres/minute
DYNAMIC INLET PRESSURES
Hot & Cold Inlet Pressures Minimum 10kPa
Maximum 500kPa
STATIC INLET PRESSURES
Hot & Cold Inlet Pressures Maximum 1000kPa
INLET PRESSURE RATIO
Maximum inlet pressure ratio for stable
operation. (Hot : Cold or Cold : Hot)
5:1 (either
supply)
NOTE: For optimum operation it is recommended that the hot & cold
water supply pressures be balanced to within +/- 10%.
NOTE: Notwithstanding the above, compliance with AS3500 must be
maintained.

8
Aquablend 2500 Thermostatic Mixing Valve
Call 1300 369 273
www.enware.com
Flow Sizing Graph
The ENWARE AQUABLEND 2500 Thermostatic Mixing Valve is
suitable for many applications. The Headloss Characteristic for
Mixed Outlet Flowrate versus Balanced Inlet Pressure is shown
Graph 2.1 below. It is important that the valve is not oversized
for its intended application.
HEADLOSS CHARACTERISTICS OF AQUABLEND 2500
with Inlet Fittings
(with mix temperature at 42°C at Valve Outlet)
Pressure Drop
(Balanced Inlet Pressure) - kPa
Graph 2.1 - Headloss Characteristics
Note: To ensure optimum performance the minimum outlet ow
of the mixing valve during operation should be at least
6 litres/minute.
It is important that the valve is sized such that the ow rates
from the outlets are not less than those listed in AS3500.1. The
pipework between the valve and the system must be sized in
accordance with AS3500.1 to ensure the water velocity in the
pipework is within allowed limits.
If the valve is to be installed and operated under unequal inlet
pressures then it is the lower inlet pressure that will determine the
outlet ow rate. However, for optimum performance and stability
it is recommended that the valve is installed with balanced
dynamic inlet pressures (+/- 10%).
Mixed Outlet Flowrate - Litres per minute
Table des matières
Autres manuels enware Unité de contrôle
Manuels Unité de contrôle populaires d'autres marques

Festo
Festo Compact Performance CP-FB6-E Manuel de la liste des pièces

Elo TouchSystems
Elo TouchSystems DMS-SA19P-EXTME Manuel utilisateur

JS Automation
JS Automation MPC3034A Manuel utilisateur

JAUDT
JAUDT SW GII 6406 Series Guide rapide

Spektrum
Spektrum Air Module System Manuel utilisateur

BOC Edwards
BOC Edwards Q Series Manuel utilisateur