11 12
No. Name
Default
Ranges
1 Sensor selec on 00: Floor sensor 00: Floor sensor
01: Room-in sensor
02: 01+00
03: Room-out sensor
04: 03+00
2 Room temp calibra on 0.0°C -5.0°C -- 5.0°C
3 Floor temp calibra on 0.0°C -5.0°C -- 5.0°C
4 Floor temp limit 35.0
C 20.0
C -- 50.0
C
5 Schedule 01: 5+1+1 00: 7
01: 5+1+1
6 Used for 00: Hea ng 00: Hea ng
01: Cooling
7 Adap ve func on 01: No 00: Adap ve
01: No
8 Located in 00: Home 00: Home
01: Office
9 Reset 00: No 00: No
01: Reset
00 Floor sensor: run by floor sensor(default).
01 Room-in sensor: run by built-in room sensor.
02 Room-in sensor and floor sensor: run by built-in sensor with floor temp limit.
03 Room-out sensor: run by external room sensor.
04 Room-out sensor and floor sensor: run by external room sensor with floor temp limit.
the room temp plummets.
2. : calibrate the temp detected by room sensor.
3. : calibrate the temp detected by floor sensor.
4. Floor temp limit: if you choose both sensors, floor temp limit must be set to protect floor.
5. Schedule: Select a weekly schedule for the event.
1. :
7: each day from Mon to Sun can be set individually.
5+1+1: 5 days from Mon to Fri have the same events, Sat and Sun can be set individually.
6. Used for
7.
the required temp has already been reached when the next event begins.
8. Located in: Home or Office.
9. Reset: all parameters are restored to default values.
8.5