Manual R2000-43-E Release: 1.03 © Elotech GmbH Page 5/24
IV. Connection Diagram: R2000 - 432
k4* k3 k2 k1 70
L / DC- 171
N / DC+ 272
3 73
A1 417 Option 74
A1 518 Analog Input 75
A2 619 76:
d 2: 0...10VDC+
76: L1 76
A2 720 77:
0...10VDC -
77: L1 77
8 21 78:
d 1: 0...10VDC+
78: L2 78
9 22 79:
0...10VDC -
79: L2 79
10 23 Zone: Sensor: 80: L3 80
Out 4 -11 Out 8 - 24 TC Pt100 81: L3 81
Out 3 -12 Out 7 - 25 - 60 Option 82
Out 2 -13 Out 6 -26 461 Heater current 83
Out 1 -14 Out 5 - 27 62 transformer
Com.+ 15 Com.+ 28 3- 63
GND GND
90
64
RxDou RxD in
91
- 65
TxD in RxDout
92
266
H A
TxDout TxDout
93
67
L B RxD in TxD in
94
1- 68 95
69
CAN
RS485 RS232 0/20mA
96
It is not permitted to connect the grounds of the sensor-inputs and bist. voltage-outputs with each other.
65: RTD 2. wire RTD 2. wire
66: 3-wire 1. wire 2-wire 1. wire
67: connection 3. wire connection 3. wire = jumper to 2. wire
jumper
jumper
67: RTD 3. wire RTD 3. wire = jumper to 2. wire
68: 3-wire 2. wire 2-wire- 2. wire
69: connection 1. wire connection 1. wire
„heat-only“ or „cool-only“ - controller: „heating-off-cooling“ - controller:
Control output OUT 1: Zone 1; „heating“ or „cooling“ „heating“
to
OUT 4: Zone 4; „heating“ or „cooling“ „heating
Control output OUT 5: Zone 1; „cooling“
to
OUT 8: Zone 4; „cooling“
Alarm Output A1: Alarm 1 ( Temperature- or heater current monitoring alarm A1 for all zones)
Alarm Output A2: Alarm 2 ( Temperature- or heater current monitoring alarm A2 for all zones)
Setpoint Controlling: K1: open = Setpoint 1 (SP1) valid
K1: closed = Setpoint 2 (SP2) valid, for all zones
Adjustment lock (LOC): K2: open = Adjustment lock only via „software code“ (see parameter: LOC)
K2: closed = Adjustment locked according to the choosen „software code“.
Setpoint changing: K3: open = individual setpoint adjustment for each zone
K3: closed = if setpoint has been changed in one zone,
this new setpoint is valid (will be overtaken) for all other zones automatically.
CAN-Interface, (Option):K4: open = CAN: „operational“. Operation only with CANopen protocoll.
K4: closed = CAN: „operational“ always active.
K4 must be closed, if the instrument is equipped with a CAN-interface but not used.
Input d1, (Option):0 ... 10 VDC, Display: Zone: d1
Input d2, (Option):0 ... 10 VDC, Display: Zone: d2
Heater current monitoring: 1 current – transformer / phase
Single phase operation: terminals 76,77: L1
Three-phase operation: terminals 76 – 81: L1, L2, L3