FOLDER LABEL DESCRIPTION RANGE DEFAULT M.U. Note
SEt Regulation SetPoint 0 °C/°F CutOut
CPr diF Differential 0 ... 30.0 2.0 °C/°F Related to SetPoint
CPr HSE Higher Set point adjustment limit LSE ... HdL 50.0 °C/°F Minimum User can adjust
SetPoint
CPr LSE Lower Set point adjustment limit LdL ... HSE -50.0 °C/°F Maximum User can adjust
SetPoint
CPr dOF Compressor Antishort cycle 0 ... 255 0 min Minutes
dEF dtY Defrost Mode 0 ... 2 0 num Electrical Defrost (1=HotGas)
dEF dit Interval between defrost 0 ... 255 6 h/min/sec Hours
dEF dCt defrost interval Counting mode 0 ... 3 3= RTC
models / 1 num Time elapses since start of
last defrost
dEF dEt Maximum duration of Defrost 1 ... 255 30 h/min/sec Minutes
dEF dSt Defrost termination temperature -302.0 ... 1472.0 6.0 °C/°F
dEF dPO Execute a Defrost at Power On n/y n flag
FAn FSt Evaporator Fan Stop temperature -302.0 ... 1472.0 6.0 °C/°F
FAn Fdt Fan delay after defrost 0 ... 255 0 min Minutes
FAn dt Drip time 0 ... 255 0 min Minutes
FAn dFd Fan Stop during defrost n/y y flag
ALr HAL Maximum alarm threshold LAL ... 1472.0 50.0 °C/°F
ALr LAL Minimum alarm threshold -302.0 ... HAL -50.0 °C/°F
ALr dAO defrost Alarm Override 0 ... 999 60 min Alarm delay after
defrost
ALr tAO Temperature Alarm Override 0 ... 255 0 min Temperature alarm delay
diS LOC Lock keyboard n/y n flag
diS PA1 Password 1 (USr) 0 ... 999 0 num
diS ndt number display type n/y y flag
diS CA1 Offset Probe 1 -30.0 ... 30.0 0.0 °C/°F Regulation Probe
diS CA2 Offset Probe 2 -30.0 ... 30.0 0.0 °C/°F Defrost termination Probe
diS ddL Lock display during defrost 0 ... 2 2 num Display shows “DEF”
CnF H00 Probe Type 0/1 1 flag 0=PTC; 1=NTC
depending on model
CnF H42 Defrost termination Probe presence n/y y flag Always present
HOW TO CHANGE THE SET POINT
• Press and release the SET button.
• The Top Display shows SET, the bottom display shows the value
• Use the UP & DOWN buttons to adjust the Set Point’s value
• Press ESC for display to return to normal
HOW TO ENTER THE USER LEVEL (USR) AND ALTER PARAMETER VALUES
• Press & Hold the SET button for 3 seconds until the display changes to
show USr
• Press & release SET to enter USr (User Level).
• The first parameter is displayed. Top display shows the parameter label,
Bottom display shows parameter value.
• Using the UP & DOWN buttons, go to the desired parameter
• Press & release SET, then using the UP & DOWN buttons, adjust the para-
meter’s value.
• Press ESC several times to return to normal display
ALL OTHER PARAMETERS ARE CONTAINED IN INSTALLER LEVEL (InS)
Entering Installer Level (InS):
You should only need to do this for more advanced applications. Here the
parameters are arranged in folders (Compressor / Defrost / Fans etc)
• Press & Hold the SET button for 3 seconds until the display changes to
show Usr
• Use the UP or DOWN button to display InS
• Press & release SET to enter InS (InStaller Level).
• The first parameter folder is displayed
• Keep pressing SET until you see the folder you want
• Press the UP or DOWN button, the first parameter is displayed. Top
display shows the parameter label, Bottom display shows parameter value.
• Using the UP & DOWN buttons, go to the desired parameter
• Press & release SET, then using the UP & DOWN buttons, adjust the para-
meter’s value.
• ress ESC several times to return to normal display
FOR MORE DETALED INFORMATION READ ON Technical Sheet p/n
9IS44058
cod. 9IS44112-1 - GB - rel. 07/08 © Eliwell Controls s.r.l. 2008 All rights reserved.
Eliwell Controls s.r.l.
Via dell’Industria, 15 • Zona Industriale Paludi • 32010 Pieve d’Alpago (BL) ITALY
Telephone +39 0437 986 111 • Facsimile +39 0437 989 066
Sales
+39
0437
986
100
(Italy)
•
+39
0437
986
200
(other
countries)
•
E-mail
[email protected]www.eliwell.it