6. BUS VARIANTS
6.1. ETHERNET/IP (CE.99225)
The module uses Class 1 (explicit) messaging.
For configuration the EDS file is available at the following link:
https://www.anybus.com/support/file-doc-downloads/compactcom-30-series-specific/?ordercode=AB6224
If the link is not reachable, please contact the Elesa customer service.
The EDS allows the PLC to recognize the UC-RF on the Ethernet/IP bus. Then it is needed to configure
all the I/O instances as described below (refer to Appendix A for status and command word definition).
Input assembly UC-RF PLC
Instance 0x64h (100 DEC), 224 bytes transfer as follows:
• offset 0x00 - channel 1 - 4 bytes actual quote, followed by 2 bytes status word
• offset 0x06 - channel 2 - 4 bytes actual quote, followed by 2 bytes status word
• ...
• offset 0xD2 - channel 36 - 4 bytes actual quote, followed by 2 bytes status word
• offset 0xD8 - current network ID
• offset 0xD9 - UC-RF status
• =0 - UC-RF waiting for networkID
• =1 - networkID initialized, scanning enabled channels in progress
• =2 to 255 reserved
• offset 0xDA - reserved
• offset 0xDB - reserved
• offset 0xDC - 4 bytes software release
Output assembly PLC UC-RF
Instance 0x96 (150 DEC), 224 bytes transfer as follows:
• offset 0x00 - channel 1 - 4 bytes target, followed by 2 bytes command word
• offset 0x06 - channel 2 - 4 bytes target, followed by 2 bytes command word
• ...
• offset 0xD2 - channel 36 - 4 bytes target, followed by 2 bytes command word
• offset 0xD8 - config byte
• offset 0xD9 - config byte content
• 0x00 - invalid config byte
• 0x01 - config byte contains network ID
• 0x02 to 0xFF reserved
• offset 0xDA - reserved
• offset 0xDB - reserved
• offset 0xDC - reserved
• offset 0xDD - reserved
• offset 0xDE - reserved
• offset 0xDF – reserved