Distech Controls ECLYPSE ECY-TU-203 Manuel utilisateur

ECLYPSE™ ECY-TU-203 Connected
Terminal Unit Controller
Product Description
The ECLYPSE Connected Terminal Unit Controller (ECY-TU) is designed to control terminal units such as fan coil units, chilled beams, ceilings, and
heat pumps.
It integrates a control, automation and connectivity server, a power supply, and dedicated I/Os in one convenient package. Each model supports BAC-
net/IP communication and is listed as a BACnet Building Controller (B-BC) and feature wired and wireless advanced IP connectivity for efficient and reli-
able installation.
The ECY-TU comes with an embedded web server that enables web-based application configuration and an HTML5 visualization interface. It also fea-
tures embedded scheduling, alarming, and logging. Control logic and graphic user interface can be customized as required for the application.
Moreover, as part of the Smart Room Control solution, these controllers can control lighting fixtures (DALI, ON/OFF, dimming) and shades/sunblind mo-
tors (24 VDC or 100-240 VAC, up/down and angle rotation) through additional expansion modules.
General Installation Requirements
For proper installation and subsequent operation of each controller, pay special attention to the following recommendations:
£Upon unpacking the product, inspect the contents of the carton for shipping damages. Do not install damaged modules.
£Avoid areas where corroding, deteriorating, or explosive vapors, fumes or gases may be present.
£Ensure the mounting surface can support the controller, DIN rail, and any user-supplied enclosure.
£Allow for proper clearance around the controller’s enclosure, and wiring terminals to provide easy access for hardware configuration and mainte-
nance, and to ventilate heat generated by the controller.
£The controller’s datasheet specifies the power consumption (amount of heat generated), the operating temperature range, and other environmental
conditions the controller is designed to operate under.
£Ensure that all equipment is installed according to local, regional, and national regulations.
£If the product is used and/or installed in a manner not specified by Distech Controls, the functionality and the protection provided by the product may
be impaired.
£SELV (Separated Extra Low Voltage) inputs/outputs must be connected to other SELV equipment inputs/outputs.
£PELV (Protective Extra Low Voltage) inputs/outputs must be connected to other PELV equipment inputs/outputs.
£It is recommended that the controller(s) be kept at room temperature for at least 24 hours before installation to allow any condensation that may
have accumulated due to low temperature during shipping/storage to evaporate.
Installation Guide

2 / 15
£Orient the controller with the ventilation slots towards the top to permit proper heat dissipation. When installed in an enclosure, select one that pro-
vides sufficient surface area to dissipate the heat generated by the controller and by any other devices installed in the enclosure. A metal enclosure
is preferred. If necessary, provide active cooling for the enclosure.
£Do not drop the controller or subject it to physical shock.
£The controller must be installed in an appropriate ventilated enclosure, which minimum dimensions are 240 x 240 x 100 mm.
£If the controller is to be mounted on a metallic support, this same metallic support is to be connected to a protective earth.
£Equipment without terminal block covers must be wall-mounted or DIN rail-mounted inside a supplementary enclosure (rated as IP20 or better) that
can only be accessed by qualified personnel.
£Equipment with terminal block covers can only be wall-mounted on a flat surface that is sufficiently large to provide space around the equipment. In
this installation scenario, conductors must be made inaccessible and wiring must comply with local wiring regulations and methods appropriate for
fixed equipment installation in a building (the use of trunking for example).
£UL-compliant installation requires the product to be installed in a certified electrical safety box.
Any type of modification to any Distech Controls product will void the product’s warranty.
Operating, handling, or servicing this product should be ensured by a qualified operator. Turn off the power
before any kind of servicing.
Take reasonable precautions to prevent electrostatic discharges to the product when installing, servicing, or
operating it. Discharge any accumulated static electricity by touching a grounded object with your hand before
handling the product.
Device Markings (Symbols)
Certain markings (symbols) can be found on the controller and are defined as follows:
Symbol Description
CE marking: This device conforms to the requirements of applicable EC directives.
UKCA marking: This device conforms to the requirements of applicable Great Britain regulations.
Double Insulation
marking: These controllers are built using double insulation.
Products must be disposed of at the end of their useful life according to local regulations.
Read the Hardware Installation Guide for more information.
For indoor use only.
UL marking: This device conforms to the requirements of the UL certification.
FCC marking: This device complies with FCC rules part 15, subpart B, class B.
Warning Symbol: Significant information required. Refer to the Hardware Installation Guide.
HIGH VOLTAGE Symbol: Direct contact will cause electrical shock or burn.
Alternating Current
Direct Current
Line
Neutral
Functional Earth. (CEI 60417 n° 5018)

3 / 15
General Wiring Recommendations
Risk of Electric Shock: Turn off power before any kind of servicing to avoid electric shock.
£All wiring must comply with electrical wiring diagrams as well as national and local electrical codes.
£To connect the wiring to a device, use the terminal connectors. Use a small flat screwdriver to tighten the terminal connector screws once the wires
have been inserted (strip length: 0.25’’ (6mm), maximum tightening torque 0,4 Nm (3.45 in-lb)).
£Comply with all network and power supply guidelines outlined in the Network Guide.
£Keep wiring separate according to their function and purpose to avoid any ambient noise transmission to other wires. Use strapping to keep these
wires separated. For example, keep power, hazardous voltage, SELV, PELV, network, and input wiring separate from each other.
£Keep input and output wiring in conduits, trays or close to the building frame if possible.
£Power type cables (i.e. for power, 3-wire voltage and current inputs and outputs) should be kept apart from other types of wiring to avoid any ambi-
ent noise transmission to other wires.
£Keep all wires away from high speed data transmission cables (for example, Ethernet, etc.).
£Conductors must be made inaccessible and wiring must comply with local wiring regulations and methods appropriate for fixed equipment installa-
tion in a building.
£Installation must be carried out in a fashion such that double insulation integrity is maintained.
£The maximum number of devices on one trunk should be below 50 devices to ensure proper communication and reduce leakage current effect.
£If all controllers are connected to the Same Main supply voltage with proper GFI, the default current will be limited by the GFI. The current leakage
value of a single controller is below < 0,5 mA rms.
£Each controller has a leakage current at the ground of less than 0.5 mA rms. This leakage current must be taken into account when designing the
electrical installation to protect against electrical shock in the case where a shielded ethernet cable is used.
£Always use unshielded cabling with a minimum Category 5 (CAT5) cable for ethernet communications.
£In a case when shielded ethernet cables are used, a functional earth must be connected to the functional Earth input or COM input of each con-
troller. The functional earth connection can also be done using the ports of the switch used to ensure a return path to the ground for leakage current.
The differential protection to the earth must be adapted accordingly.
£Do not connect the universal inputs, analog/digital outputs or common terminals to earth or chassis ground (unless stated otherwise and/or using
shielded Ethernet cable).
Module Enclosure Dimensions
5.71145.00
5.54
140.84
5.60142.22
Front
2.2456.88
Profile
Millimeters [Inches]
0.246.04
5.07
128.76
0.246.04
5.08129.01
0.317.990.317.99
Back
0.051.38
Figure1: Dimensions without terminal covers

4 / 15
145.00
194.85
Front
Profile
5.71
7.67
Front
2.2456.88
Profile
Millimeters [Inches]
1.30
0.31
7.99
Back
5.07128.76
1.3033.04
33.04
5.08129.01
Back
0.31
7.99
Figure2: Dimensions with terminal covers
Mounting Instructions
The controller can be mounted on a DIN rail for fast installation and easier maintenance. The controller also has four mounting holes to be mounted in a
panel or on a wall.
If the controller is to be installed out of an electrical box, it is a must to use the optional terminal block cover.
Ensure that the mounting surface can support the controller, DIN rail, and any site-supplied enclosure.
The controller must be mounted in a horizontal position as indicated in this guide to ensure proper airflow and
heat dissipation. Any other position may cause excess heat accumulation and may result in a damaged
controller.
Mounting Positions
The controller’s mounting orientation must be horizontal with controller’s back attached to a vertical wall surface.
Figure3: Permitted Mounting Position

5 / 15
DIN Rail-Mounted Installation
1. Securely mount the DIN rail horizontally on the wall.
2. Clip the controller onto the DIN rail.
Figure4: DIN-rail mounted controller
3. To detach the controller from the DIN rail, use a flat screw driver to pull down on the release clip located at the bottom center of the controller and pull
it off the DIN rail, bottom first.
Din Rail Release Clip
Figure5: Typical DIN Rail-Mounting Release Clip
Wall-Mounted Installation
Figure6: Mounting hole positions
1. Use the mounting holes to mark the location of any holes that need to be drilled.
2. Drill the holes.
3. Clean the surface
4. Mount the module using a No. 8 slotted hex, size: 1/4" or equivalent mounting hardware appropriate to the wall material type.
Figure7: Appropriate Mounting Hardware (Field Supplied)

6 / 15
Power Wiring
Voltage 24 VAC; ±15%; Class 2
Maximum Consumption 2 A
This is a Class 2 Product. Use a Class 2 transformer only (rated at 100 VA or less at 24 VAC) to power the
controller(s).
When calculating a controller’s power consumption to size the 24 VAC transformer, you must also add the external loads the controller is going to supply,
including the power consumption of any connected subnet modules.
It is recommended to wire only one controller per 24 VAC transformer. Do not connect more than 5 controllers to a single transformer.
Use an external fuse on the 24 VAC side (secondary side) of the transformer to protect all controllers against power line spikes.
Maintain consistent polarity when connecting controllers and devices to the transformer. That is, the COM terminal of each controller and each peripheral
should be connected to the same terminal on the secondary side of the transformer.
The COM terminals of the controller are internally wired to the ground terminal of the power supply connector.
Connecting a peripheral or another controller to the same transformer without maintaining polarity between these
devices will cause a short circuit.
The following diagram shows the recommended wiring of the controller with and without a 3-wire peripheral. This configuration applies either to a daisy-
chain configuration or configuration with separate transformers.
System Ground
S
1
24V
2
COM
24 VAC
AC Power
Source
(Mains)
Fuse: 2A
Max. Fast
Acting
Figure8: Power Wiring

7 / 15
Input Wiring
Input options must be properly configured in EC-
gfx
Program to ensure correct input readings. For terminal block connector wiring best practices, see
General Wiring Recommendations. Inputs can be connected as follows.
Before connecting a sensor to the controller, refer to the installation guide of the equipment manufacturer.
£For a wire length less than 10’ (3m), either a shielded or unshielded 18AWG wire may be used.
£For a wire up to 33’ (10m) long, a shielded 18AWG wire is recommended.
£The shield of the wire should be grounded on the controller side only and the shield connection to the
ground should be kept as short as possible.
£If functional Earth is connected, input circuits will be PELV.
£If functional Earth is NOT connected, input circuits will be SELV.
Sensor Input Type Input Designa-
tion
Input Connection Diagram
£Dry Contact input.
£Pulsed input.
£UIx
£DIx
£SIx
UIx, DIx or SIx
COM
To Digital Input
Digital Dry Contact
NO-NC
£Pulse input used with a 2-wire sensor powered by its own power source.
£This input supports a maximum input frequency of 100Hz (5ms minimum
ON/OFF) for DIx, or 1Hz (500ms minimum ON/OFF) for UIx and SIx.
£Connect the pulse input according to the figure for a pulse meter that can
pull-down a +3.3VDC supply with a 1kΩ (for DIx) or 10kΩ (for UIx and SIx)
pull-up resistor (Internal supply type).
£DIx
£UIx
£SIx
Pulse Meter
Output
Controller
Pulse
Input
Equivalent
Circuit
UIx or DIx
COM To Pulse Count
Accumulator
+
-
10 kവ+5 VDC
£Thermistor Input (for example, 10kΩ type II and III). £UIx
£SIx
UIx or SIx
COM
To Analog-To-
Digital Converter
RTD/
Thermistor
£Resistive input, maximum 350kΩ (for example, use with 10kΩ and 100kΩ
potentiometers).
£UIx
£SIx
UIx or SIx
COM
To Analog-To-
Digital Converter
3RWHQWLRPHWHUNവ
£Voltage input used with a 3-wire 0 to 10VDC or 0 to 5VDC sensor powered
by an external 24 AC/DC power supply.
£UIx
AC
+
Common
0-10V
Sensor
UIx
COM To Analog-To-
Digital Converter
24VAC
£Voltage input used with a 0 to 10VDC or 0 to 5VDC sensor powered by its
own power source.
£UIx
+
-
0-10V
Sensor
UIx
COM
To Analog-
To-Digital
Converter

8 / 15
Output Wiring
Output options must be properly configured in EC-
gfx
Program to ensure correct output values. The table below shows the available output wiring meth-
ods. Outputs can be connected as follows.
Before connecting an output device (actuator, relay, etc.) to the controller, refer to the datasheet and installation
guide of the equipment manufacturer.
£For a wire length less than 10’ (3m) long, either a shielded or unshielded 18AWG wire may be used.
£For a wire length up to 33’ (10m) long, a shielded 18AWG wire is recommended.
£The shield of the wire should be grounded on the controller side and the shield connection to the ground
should be kept as short as possible.
£For relay and triac outputs; select appropriately-sized wiring suitable to the current load.
Relay Contact Outputs
The relay contact outputs (DO1, DO2 & DO3) can switch up to 3 A (inductive / resistive - total of all fan relay contact outputs) for fan speed control.
£Fan relay contacts are unpowered and an external power supply is required (max 277VAC).
£The fan relay contact outputs are normally open.
£All fan relay contact output connectors accept wires between 1 mm² (17 AWG) and 1.5 mm² (16 AWG). Select proper gauge according to the cur-
rent load.
£It is recommended to use an appropriate external protection when connected to a highly inductive load.
Description Designation Connection Diagram
Fan speed DO1-DO2-DO3
DO
1DO
3
DO2
Un
M
3
2
1
Line-
to-Neutral AC Power Source
NeutralLine
3 A Fuse
Fan
Electric Heater
The relay contact output (DO4-C4) can switch up to 9 A (resistive) for electric heater control up to 277 VAC. For example, this output can handle electric
heaters up to 2 kW @ 230 VAC.
£If more power is needed, a relay must be connected to the relay contact output.
£The heater relay outputs are unpowered. You must use the same Live conductor (power source) to power the heater as the one used to power the
controller.
£All digital relay contact outputs are normally open.
£All relay contact output connectors accept wires between 1.5 mm² (16 AWG) and 2.5 mm² (14 AWG). Select proper gauge according to the current
load.
£It is recommended to use an appropriate external protection when connected to a highly inductive load.
£It is recommended to use a 10 A fast-acting, high-breaking fuse to protect the heater relay contact output against short circuit/overload conditions.
Description Designation Connection Diagram
Electric heat DO4-C4
Cx
DOx
Fuse
Electric Heater
Safety Thermostat
Electric Heater
Power Supply
(same live conductor
as the controller)
Relay Contact outputs - Electric Heater (IElectric Heater < IMax )
L
N
DOx
Cx A2
A1
L
N
Polarization
Voltage
s
(same live conductor
as the controller)
Fuse
Relay
Electric Heater
2-Line Main
Power Disconnect
Electric Heater
Power Supply
Relay Contact outputs - Electric Heater (IElectric Heater > IMax )

9 / 15
Triac Outputs
Triac outputs can be used to turn equipment and devices on and off (two-state outputs) and to control valve and damper actuators using Pulse Width
Modulation (PWM).
£Triac output: 24 VAC (Max: 600 mA)
£To measure the state of a triac output, an external load must be connected.
£Triac output connectors accept wires between 1 mm² (17 AWG) and 1.5 mm² (16 AWG). Make sure the wires are suitable for the connected loads.
£If functional Earth is connected, triac output circuits will be PELV.
£If functional Earth is NOT connected, triac output circuits will be SELV.
Description Designation Connection Diagram
Thermal Valve DO5-DO6
DOx
DOx
COM
Thermal Valves
Proportional valve: requires two Triac outputs DO5-DO6
DOx
DOx
COM
Proportional Valve
Analog Outputs
Analog outputs are configured to provide a linear signal ranging from 0 to 10 VDC.
£Analog output connectors accept wires between 0.75 mm² (18 AWG) and 1.5 mm² (16 AWG).
£If an analog actuator is being controlled, connect the 0 to 10 VDC output, along with an external 24 VAC power source, to the analog actuator.
£The onboard 24 VAC power supply can be used to power 0-10 V actuators.
£If functional Earth is connected, analog output circuits will be PELV.
£If functional Earth is NOT connected, analog circuits will be SELV.
Control Output Type Designation Connection Diagram
0 to 10VDC voltage output AOx
0
-
10
V
Common
AOx
COM
0 to 10VDC voltage output controlling an analog actuator powered by an
external 24VAC power source
AOx
AOx
COM
0
-
10
V
~
or
+
Actuator
or
-
24
VAC
0 to 10VDC voltage output controlling an analog actuator powered by the
controller
AOx
AOx
COM
0-10
V
~ or +
Actuator
or -
24V~

10 / 15
Digital/Analog Outputs
£Digital Analog Outputs can be used as 24 VAC Triac outputs (using 24V~ / DOx pin) or as analog outputs (using AOx pin).
£24V~ / DOx pin and AOx pin cannot be used simultaneously on the same Digital Analog output.
£If functional Earth is connected, digital analog output circuits will be PELV.
£If functional Earth is NOT connected, digital analog circuits will be SELV.
Control Output Type Designation Connection Diagram
0 to 10VDC voltage output AOx
0
-
10
V
Common
AOx
COM
0 to 10VDC voltage output controlling an analog actuator powered by an
external 24VAC power source
AOx
AOx
COM
0
-
10
V
~
or
+
Actuator
or
-
24
VAC
0 to 10VDC voltage output controlling an analog actuator powered by the
controller
AOx
AOx
COM
0-10
V
~ or +
Actuator
or -
24V~
Thermal Valve 24V~ / DOx
DOx
DOx
COM
Thermal Valves
Proportional valve: requires two Triac outputs 24V~ / DOx
DOx
DOx
COM
Proportional Valve
Table des matières
Manuels Terminal tactile populaires d'autres marques

Wincor Nixdorf
Wincor Nixdorf iPOS plus Advanced Manuel utilisateur

Ingenico
Ingenico AXIUM EX4000 Manuel utilisateur

Heisei Electronics
Heisei Electronics Q-POS 815 Manuel utilisateur

Amano
Amano MTX-15 Manuel utilisateur

FLOWBIRD
FLOWBIRD CWT Compact Touch Manuel utilisateur

Demco
Demco SP7 Manuel utilisateur