75.5323.01 ALLEGION SAFETY MODULE 8310-889 20180702 Page 3 of 475.5323.01 ALLEGION SAFETY MODULE 8310-889 20180702 Page 3 of 4
PROGRAMMING
1. Apply power.
RED LED = When the door is closed and someone steps into the safety zone, this indicates that it will ignore
any activation signal it receives. Therefore, the door will remain closed until the HMSS safety zone is clear.
Once the safety zone is clear and the door has been activated, a normal opening cycle will commence.
GREEN LED = If someone steps into the safety zone when the door is open, the Safety Module’s green LED
will indicate that the HMSS will be connected to the activation circuitry of the door thus holding the door open
for as long as someone is in its pattern.
2. SET LOCK-OUT TIME DELAY
The lock-out time delay for the door closing cycle must be set using the six DIP switches located on the front
of the unit. A 0 to 31 second lock-out time delay can be achieved. The lock-out time delay must be set so
that the HMSS does not send a safety signal during the closing cycle. As soon as the door reaches the jamb,
the Safety Module should reactivate the HMSS.
3. SET TIME DELAY ON SAFETY MODULE
Check to make sure that the Safety Module locks out the HMSS for the entire closing cycle of the door. If the
scanner sends a safety signal (scanner red light on) anytime during the closing cycle, the time delay set on the
Safety Module must be increased. If the door goes into safety swing as soon as it starts to close and you have
a time delay set for the length of the closing cycle, ensure that the AC power is being switched on and off at
the point of connection for the red and black wires. Correct any faults before proceeding.
4. SET DIP SWITCHES
Set the DIP switches according to the chart on page 4 to achieve the desired lock out time delay. The DIP
switches are configured to send a binary coded input to the microprocessor to establish the correct lock out
time delay.
For example:
The normal closing cycle of an automatic door lasts about 7 seconds. In order to get the proper closing lock-
out time delay needed for the closing cycle of the door, the DIP switches need to be set according to the chart
on page 4 for 7 seconds (Default Setting). To get the proper lock-out time delay DIP switches 1, 2, and 3 must
be in the ON position and DIP switches 4 thru 8 must be in the OFF position.
OFF
ON
7654321
green LED (safety beams)
red LED (lock-out time)
8
RED LED
(safety)
GREEN LED
(activation)