3
IMPORTANT SAFETY INSTRUCTIONS
SAVE THESE INSTRUCTIONS
• UV Light in operation; disconnect unit from power supply before
servicing; failure to follow warnings may result in severe eye damage
and electrical shock
• To prevent damage to the unit, operating environment temperature
must never exceed 200 oF (93 oC)
• DO NOT use this unit with an extension cord
• To reduce the risk of electric shock, this equipment may have a
grounding type plug that has a third (grounding) pin; this plug will
only fit into a grounding type power outlet; if the plug does not fit
into the outlet, contact qualified personnel to install the proper
outlet; DO NOT alter the plug in any way
• This unit is equipped with a universal ballast that operates at
nominal voltages between 100 and 240 VAC, 50/60 Hz
• To Reduce the Risk of Electric Shock – DO NOT use in wet or damp
locations; this equipment emits UV-C radiation; DO NOT locate
equipment in any location allowing direct line-of-sight to vents,
returns, or other duct openings
DO NOT connect this unit to any voltage source above 32 volts;
doing so will cause damage to the unit
WARNING
Location for Protective Earth Line.
CAUTION
• Wiring and installation of this unit must be done by a licensed HVAC
contractor or electrician; failure to do so will void warranty of the
product
• When the unit is installed in a roof mounted HVAC system, the unit
must be protected from the elements
Read this manual in its entirety before using your ActivePure®Induct Guardian I.
Keep out of the reach of children.
• Live voltage may be present
• Power Connection Requirements: This device is designed to operate using a 24 VAC, 40Va
transformer. Transformers supplied with a straight cooling or HVAC system may be used to
power the device but must be verified it’s capable of handling the additional device load before
installation. If the system transformer is not capable of handing the extra load, a separate 24 VAC,
40Va transformer MUST be used. Do not connect the device to any power source with a voltage
less than 22 VAC and a maximum of 32 VAC. Doing so will cause damage to the device
• Disconnect power at the breaker or fuse panel before servicing unit; always follow OSHA lockout
procedures to prevent accidental exposure to electrical energy
• If installed near a furnace or where emergency heat coils could raise the temperature inside the
plenum, cycle the AC unit through three full heating cycles assuring that the temperature never
exceeds 200 °F (93 ° C).The ActivePure®Cell must not exceed 200 °F (93 °C)
• If the unit is hard wired, be sure the power to the unit is o; always follow OHSA electrical lockout
safety requirements to prevent accidental release of energy during service or maintenance
activities
• Never aempt to check operation of the ActivePure®Cell(s) by direct observation; severe eye
damage can result; use the indicator lamps on the boom of the ballast on