WiMo 6CP10 Guide rapide

WIMO 6CP10
Secondary substation measuring and
monitoring unit
Operation and configuration
instructions
Technical description

WIMO 6CP10 Measuring and monitoring unit
Operation and configuration Wimotec Ltd
2Wimotec 24h support phone +358 (0)20 753 3264 WM6CP10.EN001

WImotec Ltd Measuring and monitoring unit
Operation and configuration WIMO 6CP10
WM6CP10.EN001 Wimotec 24h support phone +358 (0)20 753 3264 3
Table of Contents
1. General...................................................................................4
1.1. Unit features........................................................................4
1.2. Operating Safety................................................................4
2. User interface .........................................................................5
2.1. General................................................................................5
2.2. WIMO 6CP10 front panel ..................................................5
2.2.1. Display.........................................................................6
2.2.2. Keypad........................................................................7
2.2.3. Indicators ....................................................................7
3. Local panel operations .........................................................8
3.1. Navigating in menus..........................................................8
3.2. Operating levels.............................................................. 10
3.2.1. Opening configuration level................................. 10
3.2.2. Password handling ................................................. 11
4. Operating measures............................................................12
4.1. Default displays ............................................................... 12
4.2. Measured data ............................................................... 12
4.3. Operation indicators ...................................................... 17
4.4. Reading event register................................................... 18
4.5. Adjusting display contrast.............................................. 18
5. Configuration and parameter setting................................19
5.1. Principle of parameter setting ...................................... 20
5.2. Disturbance recorder menu DR.................................... 21
5.3. Configuring digital inputs DI .......................................... 22
5.4. Configuring digital output ............................................. 22
5.5. Configuration menu CONF............................................ 22
5.6. Protocol menu Bus.......................................................... 23
6. PC software...........................................................................26
6.1. PC user interface............................................................. 26
6.1.1. Using VAMPSET program ....................................... 26
6.2. Remote control connection.......................................... 26
7. Commissioning configuration.............................................27
7.1. Factory settings................................................................ 27
7.1.1. Configuration during commissioning .................. 27

WIMO 6CP10 Measuring and monitoring unit
Operation and configuration Wimotec Ltd
4Wimotec 24h support phone +358 (0)20 753 3264 WM6CP10.EN001
1. General
This part of the manual describes the functions of the
secondary substation measuring and monitoring unit WIMO
6CP10 and includes the unit operation instructions. It also
contains instructions for parameterization and configuration of
the unit and instructions for changing settings.
The second part of the publication includes detailed protection
function descriptions as well as application examples,
accessories and technical data sheets.
1.1. Unit features
WIMO 6CP10 secondary substation measuring and monitoring
unit is a compact multi-function monitoring device with
extensive measuring and calculation functions. Setting and
programming possibilities are comprehensive and versatile.
WIMO 6CP10 is ideal for secondary substation measuring and
monitoring management.
The unit measures currents, voltages and frequencies and
calculates following values:
•Active, reactive and apparent power
•Active and reactive energy
•Harmonics and THD of currents and voltages
•Programmable average value calculations
•One change over relay output
Further, the unit includes 3 configurable digital channels.
WIMO 6CP10 communicates with other systems using common
protocols, such as the Modbus RTU, ModbusTCP, Profibus DP,
IEC 60870-5-103 SPA bus, DNP 3.0.
1.2. Operating Safety
The terminals on the rear panel of the unit may
carry dangerous voltages, even if the auxiliary
voltage is switched off. A live current transformer
secondary circuit must not be opened.
Disconnecting a live circuit may cause dangerous
voltages! Any operational measures must be carried
out according to national and local handling
directives and instructions.
Carefully read through all operation instructions before any
operational measures are carried out.

WImotec Ltd Measuring and monitoring unit
Operation and configuration WIMO 6CP10
WM6CP10.EN001 Wimotec 24h support phone +358 (0)20 753 3264 5
2. User interface
2.1. General
WIMO 6CP10 secondary substation measuring and monitoring
unit can be controlled in three ways:
•Locally with the push-buttons on the device front panel
•Locally using a PC connected to the serial port on the front
panel or on the rear panel of the device (both cannot be used
simultaneously)
•Via remote control over the remote control port on the unit
rear panel.
2.2. WIMO 6CP10 front panel
The figure below shows the front panel of the unit and the
location of the user interface elements used for local control.
Figure 2.2-1. WIMO 6CP10 front panel
1. LCD dot matrix display
2. Keypad
3. LED indicators
4. RS 232 serial communication port for PC

WIMO 6CP10 Measuring and monitoring unit
Operation and configuration Wimotec Ltd
6Wimotec 24h support phone +358 (0)20 753 3264 WM6CP10.EN001
2.2.1. Display
WIMO 6CP10 is provided with a backlit LCD dot matrix
display. The display has 128 x 64 dots, which enables showing
21 characters in one row and eight rows at the same time. The
display is divided into sections as shown in the next figure
Figure 2.2.1-1 Sections of the LCD dot matrix display
1. Main menu column
2. Heading of active menu
3. Possible navigating directions (push buttons)
4. Measured/adjustable quantity
5. Measured/set value

WImotec Ltd Measuring and monitoring unit
Operation and configuration WIMO 6CP10
WM6CP10.EN001 Wimotec 24h support phone +358 (0)20 753 3264 7
2.2.2. Keypad
You can navigate in the menu and set the required parameter
values using the keypad and the guidance given in the display.
The key pad is composed of four arrow keys, one cancel key and
one enter key.
Figure 2.2.2-1 Keys on the keypad
1. Enter and confirmation key (ENTER)
2. Cancel key (CANCEL)
3. Up/Down [Increase/Decrease] arrow keys (UP/DOWN)
4. Keys for selecting submenus [selecting a digit in a
numerical value] (LEFT/RIGHT)
NOTE!
The term, which is used for the buttons in this manual, is
inside the brackets.
2.2.3. Indicators
The unit is provided with two LED indicators:
Figure 2.2.3-1. Operation indicators of the unit
Power Auxiliary voltage switched on
Alarm Programmable alarm indicator

WIMO 6CP10 Measuring and monitoring unit
Operation and configuration Wimotec Ltd
8Wimotec 24h support phone +358 (0)20 753 3264 WM6CP10.EN001
3. Local panel operations
The local panel is being used to read measured values, to set
parameters and to configure unit functions. Some parameters,
however, can only be set by means of a PC connected to one of
the local communication ports. Further some parameters are
factory set.
3.1. Navigating in menus
All the menu functions are based on the main menu/submenu
structure:
1. Use the arrow keys UP and DOWN to move up and down in
the main menu.
2. For moving to a submenu, repeatedly push the RIGHT key
until the required submenu is shown. Correspondingly,
push the LEFT key to return to the main menu.
3. Push the ENTER key to confirm the selected submenu.
4. Push the CANCEL key to cancel a selection.
5. Pushing the UP or DOWN key in any position of a sub-
menu, when it is not selected, brings you directly one step
up or down in the main menu.
The active main menu selection is indicated with black back-
ground color. The possible navigating directions in the menu
are shown in the upper-left corner by means of black triangular
symbols.

WImotec Ltd Measuring and monitoring unit
Operation and configuration WIMO 6CP10
WM6CP10.EN001 Wimotec 24h support phone +358 (0)20 753 3264 9
Figure 3.1-1. Principles of the menu structure and navigation in the menus
6. Push the INFO key to obtain additional information about
any menu item.
7. Push the CANCEL key to revert to the normal display.

WIMO 6CP10 Measuring and monitoring unit
Operation and configuration Wimotec Ltd
10 Wimotec 24h support phone +358 (0)20 753 3264 WM6CP10.EN001
3.2. Operating levels
The unit has two operating levels:
User level
and
Configuration
level
. The purpose of the configuration level is to prevent
accidental change of unit configurations, parameters or
settings.
USER level
Use: Possible to read e.g. parameter values,
measurements and events
Opening: Level permanently open
Closing: Closing not possible
CONFIGURATION level
Use: The configuration level is needed during the
commissioning of the unit. E.g. the scaling of
the voltage and current transformers can be
set.
Opening: Default password 0002
Setting state: Push ENTER
Closing: The level is automatically closed after 10
minutes idle time. Giving the password 9999
can also close the level.
3.2.1. Opening configuration level
1. Push the LEFT key and the RIGHT key on the front panel
simultaneously.
Figure 3.2.1-1. Opening the operating level
2. Enter the password needed for the desired level: the
password can contain four digits. The digits are supplied
one by one by first moving to the position of the digit using
the RIGHT key and then setting the desired digit value
using the UP key.
3. Push the ENTER key.
Table des matières
Autres manuels WiMo Instrument de mesure
Manuels Instrument de mesure populaires d'autres marques

Endress+Hauser
Endress+Hauser Proline Promag 50 Caractéristiques techniques

Siemens
Siemens SITRANS F Coriolis FCT030 Manuel de la liste des pièces

KLINGER
KLINGER CMF V Series Manuel utilisateur

EXFO
EXFO FTB-2 Manuel d'exploitation et d'entretien

Keysight
Keysight M8290A Manuel utilisateur

ADTEK
ADTEK MW-5 Manuel utilisateur