Watts HKV2013AF Series Manuel utilisateur

Series HKV2013AF
1" Stainless steel heating circuit manifold with flow meters
Installation and operating manual
EN
WattsWater.eu

EN
2 HKV2013AF-IM-DE-W-UK-03-2023-Rev.2 | Part no. 10086671
Contents
1 General information ....................................................... 2
1.1 Requirements ................................................................ 2
1.2 Product conformity ........................................................ 2
1.3 Product features............................................................ 2
2 Safety............................................................................ 2
2.1 Safety notices................................................................ 2
2.2 Intended use ................................................................. 2
2.3 Foreseeable misuse....................................................... 2
3 Technical specification................................................... 3
4 Pressure-temperature diagram ...................................... 4
5 Pressure loss diagram ................................................... 5
6 Dimensions.................................................................... 7
7 Components overview................................................... 8
8 Installation and commissioning ...................................... 9
8.1 Pipe installation.............................................................. 9
8.2 Shutting off the heating circuit ....................................... 9
8.3 Flushing and filling the circuits........................................ 10
8.4 Adjusting the flow rate ................................................... 11
9 Disposal ........................................................................ 12
10 Warranty........................................................................ 12
1 General information
1.1 Requirements
The installer or user must read, understand and observe this in-
stallation and operating manual before carrying out any operation.
The heating manifold may only be fitted, adjusted and maintained
by trained specialist personnel. Trainees may only work on the
product under the supervision of an experienced person. The
manufacturer will only accept any liability in line with statutory pro-
visions if the above instructions have been adhered to.
All instructions in this installation and operating manual are to be
observed when using this heating manifold. This manual is an in-
tegral part of the product and must be available to all users
throughout its entire service life. This manual is protected by
copyright and may not be altered without the manufacturer’s per-
mission.
1.2 Product conformity
The HKV2013AF Series heating manifold conforms to DIN EN
1264-4 "Water based surface embedded heating and cooling sys-
tems".
1.3 Product features
• Stainless steel round pipe manifold on mounting bracket
• G 1 male thread with flat sealing on both sides.
• Shut-off flow meter with particularly low pressure loss.
• Regulating and shut-off valve with M30 × 1.5 adaptation.
• Fastening, air vent key and sticker set for identifying the heat-
ing circuit included in delivery.
• In option: Ball valve and end set for flushing, filling and venting.
2 Safety
2.1 Safety notices
!
WARNING
WARNING indicates a danger arising through incorrect behaviour
(e.g. misuse, disregarding notices, etc.) that may cause serious
physical injury or death.
!
CAUTION
CAUTION indicates a potentially dangerous situation that may
cause minor or slight injuries if the appropriate safety precautions
are not in place.
NOTICE
NOTICE indicates a situation that may cause material damage if
the corresponding precautions are not taken.
2.2 Intended use
The manifolds are used for distributing and regulating the flow rate
in low temperature floor heating or cooling systems.
2.3 Foreseeable misuse
The following is regarded as foreseeable misuse:
• operating the heating circuit manifold contrary to the specifica-
tions;
• making modifications to the heating circuit manifold not agreed
with the manufacturer;
• using replacement or wear parts not approved by the manu-
facturer.

EN
HKV2013AF-IM-DE-W-UK-03-2023-Rev.2 | Part no. 10086671 3
3 Technical specification
Hydraulic data
Max. operating pressure 10 bar (see Pressure-temperature diagram)
Medium temperature from -10 to 80 °C (see Pressure-temperature diagram)
Media Water or water with glycol as per VDI 2035
Connections
Primary circuit and end set G 1 male thread
Heating circuit G ¾ eurocone male thread
Tightening torque G ¾ screw fittings 25-30 Nm 25-30 Nm; G1 screw fittings 55 Nm
Connection for actuator M30 x 1.5 / closing point 11.8 mm / stroke 2.5
Manifold
Manifold Stainless steel 1.4301
Flowmeter CW617N, PPS
O-rings EPDM
Flat seals AFM/2
End set (optional) CW617N

EN
4 HKV2013AF-IM-DE-W-UK-03-2023-Rev.2 | Part no. 10086671
4 Pressure-temperature diagram
12
10
80
6
4
2
0
20 30 40 50 60 70 80 90
A
B
C
Temperature [°C]
Pressure [bar]
Pressure-temperature diagram
A: 100% water
B: 70% water, 30% propylene glycol
C: 70%, 30% ethylene glycol

EN
HKV2013AF-IM-DE-W-UK-03-2023-Rev.2 | Part no. 10086671 5
5 Pressure loss diagram
0
10
100
1.000
100 1.000 10.000
2
3
5
4
6
7
8
912
-
[mbar]
Pressure loss
[L/h]Flow rate
Manifold pressure loss diagram
Outlets

EN
6 HKV2013AF-IM-DE-W-UK-03-2023-Rev.2 | Part no. 10086671
10
10
1
100
100
1.000
1.000
[mbar]
Pressure loss
[L/h]Flow rate
Control valve pressure loss diagram
Number of rotations
0.25
1.0
0.5
2.5
1.5
2.0
0.25: Kv 0.33
0.50: Kv 0.56
1.00: Kv 0.85
1.50: Kv 1.02
2.00: Kv 1.14
2.50: Kv 1.20
The adjustment diagram already allows for the specific pressure losses in the flow meter, flow control valve and 2 compression fittings.

EN
HKV2013AF-IM-DE-W-UK-03-2023-Rev.2 | Part no. 10086671 7
6 Dimensions
L3
L5
L2
L4
55 50
L1
G1″
G1″
G1″G1″
25
37
210
62
41
16
3574,5
G ¾″
G ¾″
G1″
G1″
G ¾″
G¾″
G1″
M10x1
G1″
A
B
C
Outlets
2 3 4 5 6 7 8 9 10 11 12
L1 = HKV 160 210 260 310 360 410 460 510 560 610 660
L2 = HKV + KFE90 (C) 209 259 309 359 409 459 509 559 609 659 709
L3 = HKV + Q1 (B) 219 269 319 369 419 469 519 569 619 669 719
L4 = KH (A) + HKV + KFE90 (C) 271 321 371 421 471 521 571 621 671 721 771
L5 = KH (A) + HKV + Q1 (B) 281 331 381 431 481 531 581 631 681 731 781

EN
8 HKV2013AF-IM-DE-W-UK-03-2023-Rev.2 | Part no. 10086671
7 Components overview
CB
A
1 2
3
4
5
6
A B C
Components
1 Manifold supply
2 Flow meter with shut-off function
3 Wall brackets
4 Manifold return
5 Heating circuit connection
6 Control valve with protective cap
Optional accessories
A Ball valve set KH
B End set Q1: Flushing, filling, draining, venting
C End set KFE90: Flushing, filling, draining, venting

EN
HKV2013AF-IM-DE-W-UK-03-2023-Rev.2 | Part no. 10086671 9
8 Installation and commissioning
!
WARNING
Hot water!
Severe scalding possible.
• Allow the product to cool before carrying out any maintenance,
cleaning or work repair.
• Do not put hands into hot water when draining the product.
8.1 Pipe installation
1. Cut the plastic, copper or multilayer pipe to length perpendic-
ular and deburr / calibrate. Push the clamping ring nut over
the pipe.
2. Push the grab ring onto the pipe and insert the hose nozzle.
3. Push the conical end of the pipe all the way into the connec-
tion on the manifold.
4. Tighten the clamping ring nut by hand. Push the plastic, cop-
per or multilayer pipe up to the stop.
5. Hold the outlet screw connection using a 24 mm open-end
wrench or spanner and tighten the clamping ring nut using a
30 mm open-end spanner (approx. 25-30 Nm). Fit the pipe
without any tensile, compressive or torsional forces.
Do not exceed the max. torque stated in the installation in-
structions for the compression joint used.
8.2 Shutting off the heating circuit
1. The valves on the return can be closed, e.g. for flushing and
filling the heating circuit. To do this, put the protective cap on
the valve and close it by turning it clockwise.
2. The flow meter can be closed with a air vent key. However,
this is not necessary for filling and flushing the circuits.
If the flow meter is shut off, the following opening sequence
must be observed in order to avoid malfunction or damage.
First, open the flow meter, then the control valve.

EN
10 HKV2013AF-IM-DE-W-UK-03-2023-Rev.2 | Part no. 10086671
8.3 Flushing and filling the circuits
!
CAUTION
Material damage!
Opening shut-off valves quickly produces pressure surges.
• Always open shut-off valves slowly and in a controlled manner.
üAll flow meters must be completely open.
üThe system pressure must not exceed 3 bar when flushing
and filling.
1. Close ball valves 1 and 2 on the manifold.
2. Close all valves on the return using the protective caps.
3. Attach the flushing and filling hose to the fill and drain valve 3
on the supply side; the discharge outlet on fill and drain valve
4 must be open.
4. Completely open the valve on the circuit to be flushed using
the protective cap.
5. Flush the circuit with clear water.
6. Once flushing is over, close the control valve and flush/fill the
next circuit.
7. Once the flushing and filling procedures are complete, remove
the hose from the end set (fill and drain valves 3 and 4).
8. When venting using the end set Q1 and KFE90, follow illustra-
tions A and B on this page.
9. The protective end caps are to be fully closed off once the
system has been flushed and filled.
1
2 3
4 B
A