Trolex TX6649 Manuel utilisateur

TX6649
Uninterruptible Power Supply
(UPS) with Intrinsically Safe
Output and 25 Ah Battery
Backup
User Manual

rev A
1.1 Operating Features
1.2 Application
1.3 Product Options
1.4 Dimensions
1.5 Technical Information
3.1 Safety Precautions 11
3.1.1 Handling 11
3.2 Tools and Test Equipment
Required 1
3.3 Siting Recommendations 1
Positioning Re 1
1
1
1
1
1
1
1
4.2.2 Diagnostics
4.2.3 Connectivity
4.2.4 Support
3.4.Group Areas
4.1 Technical Maintenance
4.2

rev A
The TX664Power Supply converts an ac supply voltage into a stabilised and
regulated Intrinsically Safe source of power to approved sensors and electronic
control devices.

rev A
• Input voltage options: 110 V ac or 230 V ac
• Input supply is protected by two primary fuses
• Intrinsically Safe output voltage: 12 V dc
• Output circuit is resistively limited in accordance with certification standards for
Intrinsically Safe, ia, equipment
• Output circuit incorporates voltage regulation, current limiting and continuous
short circuit protection
• Robust stainless steel housing
• Integral Ah back-up battery with automatic uninterrupted power transfer and
charge to full capacity
• Output relay contact to signal power failure
• Analogue output signal to indicate battery charge condition
•
• Mining
• Tunnelling

rev A

rev A
Input voltage 110 V ac ± 10% or 230 V ac ± 10%-50/60 Hz
Output voltage 12 V dc
Output current 750 mA
Output ripple/noise 150 mV max
Line regulation <5% over the input voltage range
Load regulation <5% over 0 to 90% of load current
<10% between 90% and 100% of load current
Voltage limiting Over voltage detection with crowbar protection and
short circuit protection
Current limiting Automatic current limiting of the intrinsically safe
output also limits the current to less than the
rupturing capacity of the output protection fuse.

rev A
Max. operating
temperature
–20°C to +40°C
Storage
temperature
–20°C to +70°C
Humidity 0 to 95% RH, non-condensing
Vibration limits / low
frequency
0.25 mm peak, sinusoidal vibration in the range
10 Hz to 100 Hz in 3 perpendicular planes
Medium frequency 2g peak, sinusoidal vibration in the range 10 Hz to
600 Hz in 3 perpendicular planes
Mechanical shock 1000 shocks of 40g minimum in 3 perpendicular
planes
Housing material Stainless steel
Back-up battery Sealed lead-acid. Ah
Automatic charge control to full capacity
Automatic uninterrupted output power transfer
following input power failure
Power fail indication Relay contacts change state on power failure.
Contact rating: 0.25 A at 30 V dc max.
Charge condition Analogue output signal proportional to the charge
level of the battery
Choice of 0.4 V to 2.0 V or 4 to 20 mA signals
Battery life 6 years at 20°C
3 years at 30°C
1.5 years at 40°C
Net weight 35 kg
Important note Following initial commissioning or long periods of
storage the TX664requires a minimum of
24 hours charge time before the batteries will be at
full capacity.

ATEX (European Union) certification for use in underground mines (Group I).
Complies with ATEX Directive 2014/34/EU.
Standards:
EN IEC 60079-0:2018
EN 60079-5:2015
EN IEC 60079-7:2015+A1:2018
EN 60079-11:2012
IECEx (International) certification for use in underground mines (Group I).
Standards:
IEC 60079-0:2017
IEC 60079-5:2015
IEC 60079-7:2015+AMD1:2017
IEC 60079-11:2011
EAC certification for use in underground mines in Eurasian Customs Union
(including Russia).
.1. Underground mines
.2. The following Specific Conditions of Use apply to the ATEX and IECEx certificates
rev A
listed above:
Product Code: Ex Certificate Number: Ex Certification Code:
TX6649.35(.xx…).19
25 Ah UPS Power Supply
CML 21ATEX2404X
IECEx CML 21.0048X
I M2(M1) Ex eb q [ia Ma] I Mb (see Note 1)
I M1 Ex ia I Ma (see Note 2)
Ta = -20 ˚C to +55 ˚C
TX6649.35(.xx…).14
25 Ah UPS Power Supply RU C-GB.AA87.B.00155/19
PП Ex e q [ia Ma] I Mc X (see Note 1)
PO Ex ia I Ma X (see Note 2)
Ta = -20 ˚C to +40 ˚C
Note 1 –applies when mains powered
Note 2 –applies when powered from the backup battery

rev A
1. Make sure that all covers on Ex e housings and their fixing devices are properly
secured in compliance with statutory regulations before switching on the input
supply.
2. Never remove the cover of an Ex e housing whilst the input supply is
connected. Isolate elsewhere before removing the cover in accordance with
statutory regulations.
3. The housing of all power supplies must be securely earthed in compliance with
statutory regulations.
4. Carry out a current consumption audit to ensure that the maximum current
loading of the power supply is not exceeded.
5. Ensure that the installation of the power supply, particularly with regard to the
connecting cables, complies with the certification parameters (section 2.1).
6. The Ex e housing must be inspected and maintained regularly in accordance
with statutory regulations.
7. All cables entering the mains input terminal chamber must be terminated with
suitable, certified cable entry devices.
8. Do not drill holes in the Ex e housing or modify it in any way.
9. The battery contains corrosive substances and must be disposed of in the
correct way.
10. Please return the complete unit to Trolex or an approved distributor for servicing
and replacement.
www.trolex.com

rev A
The TX664may be located in hazardous area
The equipment
Installation shall be carried out in accordance with the applicable code of
practice by suitably trained personnel.
Mount horizontally as shown in the illustrations on pages 4 and
See Technical section 1.5.
0.4 to 2 V dc Battery charge level monitor
4 to 20 mA Battery charge level monitor
Relay
No special tools are needed.
Autres manuels pour TX6649
1
Manuels UPS populaires d'autres marques

Pylontech
Pylontech Victron & Pylontech US5000 Manuel utilisateur

Tecnoware
Tecnoware EVO DSP PLUS MM 6.8 Manuel utilisateur

Mecer
Mecer ME-1000-WTU Manuel utilisateur

Mustek
Mustek PowerMust 530(B) Plus Manuel d'installation et d'exploitation

Emerson
Emerson Liebert NXL series Manuel utilisateur

MAKELSAN
MAKELSAN BOXER SERIES Manuel utilisateur