TX6356 Sentro Humidity Sensor
Contents
1. Product Overview 4
1.1 Operating Features 5
1.2 Application 5
1.3 Product Options 5
1.4 Dimensions 6
1.5 Technical Information 7
1.6 Electrical Details 8
1.7 Sentro Module 9
2. Certification 10
2.1 Australia 10
3. Installation 12
3.1 Safety Precautions 12
3.2 Tools and Test
Equipment Required 12
3.3 Siting Recommendations 12
3.4 Connections 13
3.4.1 0.4 to 2 V Analogue Output
Signal 13
3.4.2 4 to 20 mA Analogue Output
Signal 13
3.4.3 5 to 15 Hz Output Signal 14
3.4.4 Dual Relay Contact 14
3.4.5 RS485 Data Output Signal 14
4. Setup and Calibration 16
4.1 Controls and Indicators 16
4.2 Software Menus 18
4.3 Navigation 19
4.4 Power-up 20
4.5 Main Menu 21
4.5.1 Sentro Setup 22
4.5.2 Output Setup 27
4.5.3 Module Setup 38
4.5.4 Exit 45
4.6 Support 45
5. Operation 46
5.1 Dual Relay Contact Output
Signal 46
5.1.1 To Reset a Latched Relay 46
6. Diagnostics and
Maintenance 48
6.1 Diagnostic Messages 48
6.2 Maintenance 48
6.2.1 Introduction 48
6.2.2 Sentro Humidity Sensor
- Check 49
6.2.3 Sentro Humidity Sensor
- Clean 50
6.2.4 Sentro Humidity Sensor
Output Signal - Check 50
6.2.5 Sentro Humidity Sensor
- Function Test 51
6.3 Disposal 51
6.4 Maintenance Records 52
6.5 Maintenance and
Calibration Log 53
Disclaimers 54
Trademarks 54
Contact Details 54
Document History 54
www.trolex.com

4 TX6356-UM-EN-01
1. Product Overview
TX6356.06.
01/02/03/04/
05/06
Sentro Humidity Sensor with bottom projecting sensor head.
For safety monitoring of humidity, in heavy duty applications.
12 V dc - intrinsically safe - Group 1 Underground Mining
TX6356.00.
01/04/05/06
Sentro Humidity Sensor with bottom projecting sensor head.
For safety monitoring of humidity, in heavy duty applications.
24 V dc - General Purpose
www.trolex.com

TX6356 User Manual
TX6356-UM-EN-01 5
1.1 Operating Features
• High accuracy humidity sensor with calibrated input sensing modules
• Choice of output signals:
- 0.4 to 2 V analogue
- 4 to 20 mA analogue
- 5 to 15 Hz analogue
- RS485 addressable Modbus datacomms
- Dual relay contacts
• Large backlit LCD screen provides clear sensor information and diagnostic data
• Two programmable setpoints for inbuilt visual alarms
• Easy access terminal chamber with large, vibration secure, terminals for
connecting heavy plant cables
• Sensing range: 10 to 90% RH non-condensing
• Sensing accuracy: +/- 5%
1.2 Application
Fixed point humidity sensor for safety monitoring of humidity in heavy-duty
applications. Suitable for use in mining, storage areas, process plants, utilities and
oil & gas.
1.3 Product Options
Bottom Projecting Sensor
Output
Order Reference
Group 1 Underground
Mining Ex ia
General Purpose
4 to 20 mA output TX6356.06.01 TX6356.00.01
0.4 to 2 V output TX6356.06.02 N/A
5 to 15 Hz output TX6356.06.03 N/A
RS485 output TX6356.06.04 TX6356.00.04
Dual relay contacts -
normally closed
TX6356.06.05 TX6356.00.05
Dual relay contacts -
normally open
TX6356.06.06 TX6356.00.06
www.trolex.com

6 TX6356-UM-EN-01
1.4 Dimensions
www.trolex.com

TX6356 User Manual
TX6356-UM-EN-01 7
1.5 Technical Information
Humidity sensing range 10 to 90% non-condensing
Accuracy +/- 5%
Linearity ±2% FS
Operating temperature
range
-20 to +40°C
Storage temperature limits -20 to + 60°C
Protection classification Housing - dust and waterproof to IP65
Sensor head - protected to IP54
Housing material Reinforced polymer
Sensor housing material Polycarbonate
Nett weight 750 g
Information display 128 x 64 dot graphic backlit LCD screen
Mounting Two 6.5 mm diameter fixing holes with Unistrut
6946 indents
Cable entries 1 x M20
Electrical connections 4 mm barrier/clamp terminals with circuit
segregation barriers
Conductors A maximum of two per terminal
Conductor size A maximum of 2 x 2.5 mm²
Terminal torque • 2.4 Nm maximum
Vibration limits Vibration limits (EN 60079-29-1):
• 10 to 30 Hz - 1.00 mm total excursion
• 31 to 150 Hz - 19.6 m/s2acceleration peak
Impact limits 20 joules (housing)
Output Signals • 0.4 to 2 V
• 4 to 20 mA
• 5 to 15 Hz
• Dual relay contacts (normally open OR
normally closed)
• RS485 data
Alarms Programmable General and High alarm levels
with LED indicators
www.trolex.com

8 TX6356-UM-EN-01
Menu configuration • Security code protection
• Setpoint level and mode adjustment
• Data output protocol configuration
• Flow units selection
• Duty display text entry
Fault indication • Loss of communications
• Sensing module absent
• Sensor over-range
1.6 Electrical Details
0.4 to 2 V Output Signal - 3/4 wire - remote powered
Supply voltage Group 1 10 to 14 V dc
Minimum line load
Group 1 10 K ohms
Supply current
Group 1 20 mA @ 12 V dc
4 to 20 mA Output Signal - 3/4 wire - remote powered
Supply voltage Group 1 10 to 14 V dc
General Purpose 18 to 28 V dc
Maximum line load
Group 1 220 ohm at 12 V dc
General Purpose 500 ohm at 24 V dc
Supply current
Group 1 48 mA @ 12 V dc
General Purpose 40 mA @ 24 V dc
5 to 15 Hz Output Signal - 3/4 wire - remote powered
Supply voltage Group 1 10 to 14 V dc
Maximum line load
Group 1 Opto isolated to 2 mA
maximum
Supply current
Group 1 20 mA @ 12 V dc
www.trolex.com

TX6356 User Manual
TX6356-UM-EN-01 9
Dual Relay Contacts
Supply voltage Group 1 10 to 14 V dc
General Purpose 20 to 28 V dc
Contact rating
Group 1 5 A at 230 V dc
General Purpose 5 A at 230 V dc
Supply current
Group 1 60 mA
General Purpose 35 mA
RS485 Data Output
Supply voltage Group 1 10 to 14 V dc
General Purpose 14 to 28 V dc
Data protocol
Group 1 and
General Purpose
RS485 Modbus
Supply current
Group 1 25 mA
General Purpose 40 mA
1.7 Sentro Module
Plug-in pre-calibrated sensing module with standardised output data.
• The sensing module stores all the necessary data about its type identification,
sensing range and specific calibration. This data is automatically recognised by
the Sentro when the sensing module is loaded into the module bay
• The sensing modules are pre-calibrated so they can be replaced at any time by
a replacement sensing module
• The sensing module will identify itself when plugged into the sensor housing
and auto configuration will take place
• All Sentro sensing modules have two output alarm signals for General alarm
and High alarm. Default values are entered during manufacture and these can
be changed to preferred values
• The two alarm signals can be set to illuminate built-in flashing LED indicators
• The two alarm signals can be set to operate the General alarm and High alarm
relays on the Dual Relay Contact version of the Sentro.
www.trolex.com

10 TX6356-UM-EN-01
2. Certification
2.1 Australia
Ex certified for use in underground mines: TX6356.06.xx
Ex Certificate Number: IECEx ITA 14.0006X
Ex ia I Ma (-20°C ≤ Ta ≤ + 40°C)
Conditions of Safe Use
The following safety parameters are applicable to the Sentro 1 TX6356 Humidity
Sensor/Transmitter.
Input Parameters
Model
Field Screw
Terminals
Ui li Ci Li Pi
TX6356.06.01
(4 to 20 mA)
5 WRT 6 14.4 V * 1 0 0 -
1 WRT (2 or 3) - - - - -
TX6356.06.02
(0.4 to 2 V)
5 WRT 6 14.4 V * 1 0 0 -
1 WRT (2 or 3) - - - - -
TX6356.06.03
(5 to 15 Hz)
5 WRT 6 14.4 V * 1 0 0 -
1 WRT 2 16.5 V - 0 0 2.5 W
TX6356.06.04
(RS485)
5 WRT 6 14.4 V * 1 0 0 -
1 WRT 2
2 WRT 3
6.88 V * 1 0 0 -
TX6356.06.05
(dual relay
normally closed)
5 WRT 6 14.4 V * 1 0 0 -
1 WRT 2 30 V * 1 0 0 -
3 WRT 4 30 V * 1 0 0 -
TX6356.06.06
(dual relay
normally open)
5 WRT 6 14.4 V * 1 0 0 -
1 WRT 2 30 V * 1 0 0 -
3 WRT 4 30 V * 1 0 0 -