Advanced Setting 1. Room Temp Calibration: Calibrate the room temp detected by room sensor.
2. Floor Temp Calibration: Calibrate the floor temp detected by floor sensor.
3&4. Anti-frozen function: This option allow you to bring warmth to your plant and pet with a lower
temp. In hydronic heating system, it will keep away from freezing.
5. Floor temp limit: If you choose both sensors, floor temp limit must be set to protect floor.
6. Temp tolerance: The value is 1°C. The thermostat start to work when the actual temp is 1°C lower
than set temp and stop to work when the actual temp is 1°C higher than set temp.
7. °F/°C: °C and °F can be selected.
8. Sensor selection:
Floor sensor: Run by floor sensor.
Room sensor: Run by room sensor.
Both sensors: Run by room sensor with floor temp limit.
9. Schedule: Select a weekly schedule for the Edit. There are 2 options:
7: each day from Mon to Sun can be set individually.
5+1+1: 5 days from Mon to Fri have the same events, Sat and Sun can be set individually.
10. Output delay: This option help you avoid inadvertent operation on heating.
11. Adaptive function: After several days of installation and use, Adaptive function ensures that the
required temp has already been reached when the next event begins.
12. Open window: This function only works when room sensor or both sensors is selected. The
thermostat with this function will shut off automatically for 15 min when the window opens, as it can
detect that the room temp plummets.
13. Language: There are four lanuages:
English/German/Spanish/French.
14&15. Power Set & Energy Use: This option allows you to enter the various data used to calculate
energy use. Then use this information to calculate electricity consumption.
16. Factory Reset: All parameters are restored to default values.
No.
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
Default
0.0°C
0.0°C
ON
5.0°C
30°C
1.0°C
°C
Floor
5+1+1
0S
OFF
OFF
English
0W
-
-
Name
Room Temp Calibration
Floor Temp Calibration
Anti-frozen Switch
Anti-frozen Temp
Floor Temp Limit
Temp Tolerance
°F/°C
Sensor Selection
Schedule
Output Delay
Adaptive Function
Open Window
Language
Power Set
Energy Use
Factory Reset
Ranges
-5.0°C -- 5.0°C
-5.0°C -- 5.0°C
ON/OFF
5.0°C -- 15°C
20.0°C -- 50°C
0.5°C/1.0°C/2.0°C/3.0°C
°F/°C
Floor/Room/Both
7/5+1+1
0S/30S/60S/90S
ON/OFF
ON/OFF
English/German/Spanish/French
0W -- 4500W
-
NO/YES