Setup & Programming the Operating Parameters in the Telguard Digital
When the Telguard is received from the factory and is powered up for the first time, it is immediately ready for
registration, provided the default settings are what you want (note: activation form must be sent to Telular). The STC
LED # 2 will flash to indicate any failure conditions. The Mode LED # 3 will be on and the STC 1 and STC 2 relays will
be tripped. If changes are required to the default settings, the Telguard can be programmed using a line-mans butt-set
connected to T & R Test Points or a POTS phone connected to J7 (black connector where the C/C is normally
connected).
TO PROGRAM THE Telguard Digital
A. Put the line-mans butt-set in talk mode or pick up the POTS phone.
B. Connect power to the Telguard, when ready for programming you will hear 2 beeps.
C. Press #, *, this will put the Telguard into a Master Access programming mode, 2 beeps.
D. Enter changes required. The syntax for programming a specific memory location is as follows:
MEMORY LOCATION (3-digits), will respond with 2 beeps, then VALUE, will respond with 2 beeps.
E. Then press *, you will hear 2 beeps then hang up. This saves the change and exits the programming mode.
MEM LOC. FIELD DEFAULT SETTING
831 Mode of operation 1 1= Telco Primary/Cellular Backup
2 = Cellular Primary/Telco Backup
833 C/C Reporting Format 09 01= 4x2 pulse, 40pps 2300 hz 02= 4x2 pulse, 20pps 2300 hz
03= 4x2 pulse, 20pps 1400 hz 04= 3x1 pulse, 40pps, 2300 hz
05= 3x1 pulse, 20pps, 2300 hz 06= 3x1 pulse, 10pps, 1400 hz
07= Radionics IIe or IIIa
2
08 = Contact ID
09 = Auto Format Detect
11 = SIA2 (300 Baud) 12 = DMP
850 STC 1 Trip Output Reporting
Normally Open
04 Enter the SUM TOTAL of the events that you wish to trip the
STC relay by ADDING the corresponding values:
00 = STC Trip Input Not Used
01 = AC Failure 04 = LFC 16 = RFC
02 = Low Battery 08 = NSC 31 = All
851 STC 2 Trip Output
Reporting
Normally Closed
27 Enter the SUM TOTAL of the events that you wish to trip the
STC relay by ADDING the corresponding values:
00 = STC Trip Input Not Used
01 = AC Failure 04 = LFC 16 = RFC
02 = Low Battery 08 = NSC 31 = All
852 STC Trip Delay for LFC and NSC 2 1=30 Seconds 6=30 minutes
2=60 Seconds 7=45 minutes
3=3 minutes 8=60 minutes
4=10 minutes 9= 24 hours
5=20 minutes
861 CFC Number of Events 0 0 = disabled 2 = 4 attempts
1 = 2 attempts 3 = 8 attempts
862 CFC between Events 1 1 = 30 seconds 3 = 70 seconds 5 = 90 seconds
2 = 60 seconds 4 = 80 seconds 6 = 99 seconds
872 AC Failure Delay 02 0-24 hours, default = 2 hours
899 Factory Default Unit
NOTE: SPECIAL LED INDICATIONS DURING ACTIVATION
If the Telguard fails to confirm registration it will be displayed on the LEDS:
SYSTEM STATUS LEDS REGISTRATION INDICATIONS
ALL LEDS FLASHING FAILED REGISTRATION – SIGNAL TOO WEAK
LED #1 & LED #4 FLASHING REGISTRATION ERROR – CALL TECH SUPPORT
LED #1 ON REGISTRATION SUCCESSFUL
LED #2 ON SOLID NOT REGISTERED NEED TO CONNECT PANEL AND TRIP ZONE
On either a FAILED or REGISTRATION ERROR, the unit MUST BE RESET BY PUTTING THE J10 (RSSI jumper)
in the ‘SHORTED’ position. The registration message MUST BE RESENT or the TELGUARD will transmit all
signals through the telco connection.