1.3.1.1 Network Bay Extender Panel
Each network bay extender panel provides 81
square inches (522.5 square cm) of cable routing
space (enough for 1280 RG59 cables). The panel
comes with nine cable management brackets that
secure and channel the circuit cables. Telect
recommends two extender panels for each fully
provisioned DNI-3 network bay. This provides
adequate cable routing space for cables going to
and coming from the DNI-3 network bay.
1.3.2 Tools and Equipment
No special tools or equipment are required.
1.4 Installation Procedure
1. Align the DNI-3 chassis mounting holes with the
mounting holes of the network bay.
2. Insert four 24 x 1/2" mounting screws (two on
each side) into the mounting holes and securely
tighten them.
3. Route the DCS IN cables to one side of the net-
work bay. Tie-wrap the cables in place within
the extender panel cable management brackets.
4. Starting at the lowest DNI-3 panel and working upward, connect the DCS IN cables to the
NE-1 IN termination points on the rear of the DNI-3 panels.
5. Secure the DCS IN cables to the wire management tray via the tie-down slots.
6. Route the DCS OUT cables to the opposite side of the network bay. Tie-wrap the cables in
place within the extender panel cable management brackets.
7. Starting at the lowest DNI-3 panel and working upward, connect the DCS OUT cables to the
NE-1 OUT termination points on the rear of the DNI-3 panels.
8. Secure the DCS OUT cables to the wire management tray via the tie-down slots.
9. Route the NE IN cables to the same side of the network bay as the DCS IN cables. Tie-wrap
the cables in place within the extender panel cable management brackets.
10. Starting at the lowest DNI-3 panel and working upward, connect the NE IN cables to the NE-
2 IN termination points on the rear of the DNI-3 panels.
11. Secure the NE IN cables to the tie-down bar.
12. Route the NE OUT cables to the same side of the network bay as the DCS OUT cables. Tie-
wrap the cables in place within the extender panel cable management brackets.
Existing
Network
Bay
Extender
Panel
Figure 4 - Installing the DNI-3