INSTALLATION AND SETTING INSTRUCTIONS
9
41.0
In the electr c panel there s an outlet for fan motor (MV) control.
If the appl ed electr c load s lower than that shown n the table set forth hereunder, such outlet can be
used d rectly; otherw se t can be used to operate a relay and/or contactor.
Fan motor power - table:
TYPE 1-2-3-7-8-9 -10 5-11 6-12
Power kW 0,5 0,75 1,1 1,5
A paper vers on of the w r ng d agram s ncluded n the appl ance. It s an ntegral part of these nstruct ons
and we recommend keep ng t carefully.
In order to ensure that the mach ne works properly, some bas c parameters should be checked. Act vate the
mach ne and:
•Check that the vent lat on un t starts after max. 30 s from the burner act vat on.
Wh le the warm a r heater s normally work ng (after approx. 20 m nutes of un nterrupted work ng), perform
the follow ng operat ons:
•Measure the a r flow, as t s cruc al to get an opt mal room heat ng and furthermore s necessary n
order to adequately cool the heat exchanger. The absence of any k nd of res stance on the a r flow
generated by the fan s essent al. Therefore, avo d any obstacles h nder ng a r supply and return.
•Check that there s no fuel leakage.
•Check that the fuel flow s correct by read ng the meter.
•Check the combust on parameters.
•Check that the nstalled safety dev ces do not operate anomalously.
•On the remote control panel, lower the set-po nt to a value lower than the room temperature and
check that only the burner turns off and that the fan un t does not s multaneously stop.
•Check that the fan works for 3 m nutes after the burner has stopped, before stopp ng as well.
•Check that the thermal grad ent s equal to the one spec f ed n the TECHNICAL DATA paragraph.
The thermal grad ent s the d fference between the a r outlet and a r nlet temperature. S nce the a r
outlet temperature s not constant through ts outlet sect on, n order to get th s value, several
temperature measurements have to be carr ed out (throughout ts outlet sect ons) and then the
ar thmet cal mean has to be calculated.
•Check that the a r pressure gauge of the burner s correctly cal brated, so that t stops f the
comburent a r s not enough - s nce th s m ght cause a non hyg en c combust on
All the checks above mentioned should be performed in all the arranged working
conditions (max and min).