Contents
1. Safety Precautions 5
1.1 Before Connecting 5
1.2 In Using 6
2. Introduction 7
2.1 Features 7
2.2 Specications 8
2.3 Equipment Interface Instruction 9
3. Safe handling of lithium batteries Guide 12
3.1 Schematic Diagram of Solution 12
3.2 Explanation of Symbol 13
3.3 Tools 13
3.4 Safety Gear 14
4. Installation 14
4.1 Package Items 14
4.2 Installation Location 16
5. Trouble Shooting Steps 20
5.1 Problem determination 20
5.2 Preliminary determination steps 20
6. Emergency Situations 21
R2428_Operating_Manual_13.05.2021.indd 3R2428_Operating_Manual_13.05.2021.indd 3 17.5.2021 11:35:4217.5.2021 11:35:42

Symbol in label, manual and product
Caution! Warning! Reminding.
Safety related information.
Risk of battery system failure or life cycle reduces.
Do not reverse connection the positive and negative.
Do not place at the children and pet touchable area.
Warning electric shock.
Warning Fire.
Read the product and operation manual before operating the
battery system!
Grounding.
Recycle label.
R2428_Operating_Manual_13.05.2021.indd 4R2428_Operating_Manual_13.05.2021.indd 4 17.5.2021 11:35:4317.5.2021 11:35:43

1. Safety Precautions
Reminding
1. It is very important and necessary to read the user manual carefully (in the acces-
sories) before installing or using battery. Failure to do so or to follow any of the in-
structions or warnings in this document may result in electrical shock, serious injury,
or death, or can damage battery, potentially rendering it inoperable.
2. If the battery is stored for long time, it is required to charge it every six months, and
the SOC should be no less than 90%;
3. Battery needs to be recharged within 12 hours, after fully discharged;
4. Do not expose the battery module and cables in an outdoor environment;
5. All the battery terminals must be disconnected for maintenance;
6. Please contact the supplier within 24 hours if there is something abnormal.
7. Do not use cleaning solvents to clean battery;
8. Do not expose battery to ammable or harsh chemicals or vapors;
9. Do not paint any part of battery, include any internal or external components;
10. Do not connect battery with PV solar wiring directly;
11. Any foreign object is prohibited to insert into any part of battery.
12. The warranty claims are excluded for direct or indirect damage due to items above.
Warning
1.1 Before Connecting
1. After unpacking, please check product and packing list rst, if product is damaged
or lack of parts, please contact with the local retailer;
2. Before installation, be sure to cut off the grid power and make sure the battery is in
the switch-off mode;
3. Wiring must be correct, do not mistake the positive and negative cables, and en-
sure no short circuit with the external device;
5
R2428_Operating_Manual_13.05.2021.indd 5R2428_Operating_Manual_13.05.2021.indd 5 17.5.2021 11:35:4317.5.2021 11:35:43

4. It is prohibited to connect the battery and AC power directly;
5. The embedded BMS in the battery is designed for 24VDC system, please DO NOT
connect battery in series;
6. Battery system must be well grounding and the resistance must be less than
100mΩ;
7. Please ensured the electrical parameters of battery system are compatible to relat-
ed equipment;
8. Keep the battery away from water and re.
1.2 In Using
1. If the battery system needs to be moved or repaired, the power must be cut off and
the battery is completely shut down;
2. It is prohibited to connect the battery with different type of battery.
3. It is prohibited to put the batteries working with faulty or incompatible inverter;
4. It is prohibited to disassemble the battery (QC tab removed or damaged);
5. In case of re, only dry powder re extinguisher can be used, liquid re extinguishers
are prohibited;
6. Please do not open, repair or disassemble the battery except staffs from TAB or
authorized by TAB. We do not undertake any consequences or related responsibility
which because of violation of safety operation or violating of design, production and
equipment safety standards.
6
R2428_Operating_Manual_13.05.2021.indd 6R2428_Operating_Manual_13.05.2021.indd 6 17.5.2021 11:35:4317.5.2021 11:35:43

2. Introduction
R2428 lithium iron phosphate battery is one of new energy storage products developed and
produced under TAB’s quality requirements, it can be used to support reliable power for var-
ious types of equipment and systems. R2428 is especially suitable for application scene of
high power, limited installation space, restricted load-bearing and long cycle life.
R2428 has built-in BMS battery management system, which can manage and monitor cells
information including voltage, current and temperature, further provide protection base on
above information. The BMS can also balance cells during charging to extend cycle life.
Multiple batteries can connect in parallel to expand capacity and power in parallel for larger
capacity and longer power supporting duration requirements.
2.1 Features
◊The whole module is non-toxic, non-polluting and environmentally friendly;
◊Cathode material is made from LiFePO4 with safety performance and long cycle life;
◊Battery management system BMS)has protection functions including over-dis-
charge, over-charge, over-current and high/low temperature;
◊The system can automatically manage charge and discharge state and balance cur-
rent and voltage of each cell;
◊Flexible conguration, multiple battery modules can be in parallel for expanding ca-
pacity and power
◊Adopted self-cooling mode rapidly reduced system entire noise;
◊The module has less self-discharge, up to 6 months without charging it on shelf, no
memory effect, excellent performance of shallow charge and discharge;
◊Working temperature range is from -10°C to 55°C, (Charging 0~55°C; discharging
-10~55°C) with excellent discharge performance and cycle life;
◊Small size and light weight, standard of 19-inch embedded designed module is com-
fortable for installation and maintenance.
7
R2428_Operating_Manual_13.05.2021.indd 7R2428_Operating_Manual_13.05.2021.indd 7 17.5.2021 11:35:4417.5.2021 11:35:44

2.2 Specications
55
Communication
Working Temperature °C°C Charge
°C°C Discharge
Shelf Temperature °C°C
Ingress Protection
Humidity
Design life °C°F
R2428_Operating_Manual_13.05.2021.indd 8R2428_Operating_Manual_13.05.2021.indd 8 17.5.2021 11:35:4417.5.2021 11:35:44

2.3 Equipment Interface Instruction
R2428 Product Front Interface
Power / SW Switch
Power Switch: ON: the battery standby, no output. OFF: turn off the battery completely.
SW Switch: Press 2s to turn on or turn off battery
SOC
SOC light: 4 green LED to show the battery’s current capacity.
Alarm
Alarm light: YELLOW LED to show the battery has alarm, Combine with SOC LEDs to show
which kind of alarm in detail. Please check below table ‘LED Indicators Instructions’ for the
detailed denition.
Protection
Protection light: RED LED to show the battery is under BMS protection. Combine with SOC
LEDs to show which kind of protection in detail. Please check below table ‘LED Indicators
Instructions’ for the detailed denition.
LED Indicators Instructions
It`s important to check the detailed alarm/protection denition follow the below table for
trouble-shooting and maintenance service.
R2428_Operating_Manual_13.05.2021.indd 9R2428_Operating_Manual_13.05.2021.indd 9 17.5.2021 11:35:4517.5.2021 11:35:45

Pro-
tect
76%
75
Description
Turn off
Power off - - - -- -
Turn on Flash once.
Idle
Charge
Float charge
per sec.
Discharge
→
→ →
Soft start - -
working.
-
-
-
Protection
ADD Switch
ADD Switch: 4 ADD switches, Dip1 to denite different baud rate. ”0”and”1”,
refer to picture right. “0XXX” setup the baud rate 115200, and “1XXX” setup
the baud rate 9600.
The settings will be active only after restart the battery.
Using RS485: all batteries need to set the ADD switch. And should be the same.
Using CAN: the ADD switch has no inuence on CAN baud rate.
R2428_Operating_Manual_13.05.2021.indd 10R2428_Operating_Manual_13.05.2021.indd 10 17.5.2021 11:35:4517.5.2021 11:35:45
Table des matières
Autres manuels Tab Stockage
Manuels Stockage populaires d'autres marques

Spectra Logic
Spectra Logic T-Series Spectra T50e Manuel utilisateur

Panasonic
Panasonic LKM-F931-1 Manuel utilisateur

Tabernus
Tabernus Enterprise Erase E2400 Manuel utilisateur

Rocstor
Rocstor COMMANDER 3F series Manuel utilisateur

HP
HP P9000 Manuel utilisateur

Western Digital
Western Digital Ultrastar Data60 Manuel utilisateur