5. Use the “ceiling level tolerance limit” indicator on the
Protective Cap to check for proper installation height.
Relocate the sprinkler fitting as necessary. If desired the
Protective Cap may also be used to locate the center of
the clearance hole by gently pushing the ceiling material
against the center point of the Cap.
6. After the ceiling has been completed with the 2 inch (50
mm) diameter clearance hole, use the Protective Cap
RemovalTool(Ref.Figure5)toremovetheProtectiveCap
and then push on the Escutcheon until its flange just
comes in contact with the ceiling. Do not continue to push
on the Escutcheon such that it lifts a ceiling panel out of its
normalposition. IftheEscutcheoncannotbeengaged with
the Sprinkler, or the the Escutcheon cannot be engaged
sufficiently to contact the ceiling, relocate the sprinkler
fitting as necessary.
MAINTENANCE AND SERVICE
The Celeste S220 must be maintained and serviced in ac-
cordance with the following instructions:
NOTES
It is the responsibility of the installing contractor to
provide a copy of this document to the owner or his
representative, and in turn, it is the obligation of the
owner to provide a copy of this document to a suc-
ceeding owner.
Wet pipe sprinkler systems must be maintained at a
minimum temperature of 40°F/4°C to prevent freezing
and bursting of the pipe and/or sprinklers.
Automatic sprinklers are not to be tested with a heat
source. Operation of the heat responsive element can
result.
Absence of an Escutcheon Plate may delay the time
to sprinkler operation in a fire situation.
Before closing a fire protection system main control
valve for maintenance work on the fire protection sys-
tem which it controls, permission to shut down the af-
fected fire protection system must be obtained from
the proper authorities and all personnel who may be
affected by this action must be notified.
Do NOT enclose sprinklers within drapes, curtains, or
valances.
Do NOT hang anything from the sprinklers.
Do NOT cleanse the sprinklers with soap and water,
detergents, ammonia, cleaning fluids, or other chemi-
cals. Remove dust, lint, cobwebs, cocoons, insects,
and larvae by gently brushing with a feather duster or
gently vacuuming with a soft bristle (i.e., dusting)
brush attachment.
Exercise suitable safety precautions in the use and
storage of highly flammable materials. The rapid rate
of fire development and spread of which can be
caused by such materials can reduce the ability of
the sprinkler system to aid in the control of a fire in
which they are involved.
The minimum vertical clearance between the tops of
free standing partitions, room dividers, cabinets, stor-
age racks, stock piles, etc., and the sprinkler deflector
is NOT to be less than the clearance given in Table C.
It is recommended that automatic sprinkler systems
be inspected and maintained in accordance with the
advice and suggestions given in NFPA 25.
Automatic sprinklers must never be shipped or stored
where its temperature will exceed 100°F/38°C and they
must never be painted, plated, coated, or otherwise al-
tered after leaving the factory. Modified or over heated
sprinklers must be replaced.
Care must be exercised to avoid damage - before. dur-
ing, and after installation.Sprinklers damaged by drop-
ping, striking, wrench twist/slippage, or the like, must be
replaced.
It is recommended that automatic sprinkler systems be in-
spected quarterly by a qualified Inspection Service.
The Celeste S220 must only be replaced with pendent
sprinklers which are listed for residential fire protection
service and which have the same nominal K-factor, the
same coverage area, and the same or lower flow ratings
(as indicated under “Hydraulic Design Criteria”).
When remodeling, such as by adding false beams or light
fixtures or changing the location of compartment walls,
first verify that the new construction will not violate the in-
stallation requirements stated under WARNINGS.Alter
the new construction and/or the sprinkler system to suit
the requirements of this document.
ORDERING PROCEDURE
Please Specify:
1. Celeste S220, K=3.9, Residential Flush Pendent
Sprinkler (#4387)
2. Sprinkler Wrench
(# 4947 Socket or #4948 Wrench & Socket)
3. Protective Cap Removal Tool (#4300)
Refer to Price List for a complete listing of Part Numbers
with respect to temperature ratings, finishes, replacement
escutcheons, etc.
AVAILABILITY AND SERVICE
Star Sprinkler Inc. products and devices are available
worldwide through a network of independent distributors.
Please contact Star Sprinkler Inc. for information and the
name and address of the Star distributor in your area.
STAR SPRINKLER INC.
1-3.2.40 Page 5