Enviro Maintenance Manual 2004
Remote wiring of KES Enviro units with Water Wash Hood and Panel
Figure 8
Filter Hood or Dry Grease Extractor: RPD10 Remote Panel
The KES unit off/on operation is controlled from RPD10 remote annunciation panel. The fan selector switch
on the RPD10 remote panel closes and sends power through terminals 5 & 4 to the LV10 J-Box to energize
the exhaust fan circuit. (The LV10 J-Box is mounted on the KES-ISH filter section). The “NORMAL”
operation pilot on the RPD10 remote kitchen annunciation panel energizes and after 30 seconds the KES
control circuit within the RPD10 remote panel is activated. The exhaust fan motor is energized through the
terminals 5 & 4 to the motor starter. See figure 8 for the RPD10 remote panel wiring and figure 9 for
dimensions.
JUMPER MUST BE IN PLACE AS NOTED TO OPERATE FROM BMS
OPTIONAL BMS START/STOP - 120V/1/60
CLOSE CONTACT ACROSS 20&21 TO START UNIT
OPEN CONTACT ACROSS 20&21 TO STOP UNIT
RPD10 CONTROL PANEL - 120V/1/60 - 15 AMPS
TO KES UNIT LV10 PANEL ON FILTER
POWER SUPPLY TO THE KES UNIT
MOTOR STARTER, 120V/1/60 - 2 AMPS
(OPTIONAL) POWER SUPPLY TO SUPPLY FAN
FIRE ANUNCIATION, 5 AMPS MAXIMUM, N/O
DRY CONTACT FOR BUILDING FIRE ALARM
(OPTIONAL) THREE (3) WIRES TO
MOTORIZED INLET DAMPER AND END
SWITCH, 120V/1/60 - 1 AMP
TWO (2) WIRES TO THE WET CHEMICAL
CONTROL HEAD, 120V/1/60 - 1AMP
LOGO!
2
2
Q3Q1
1 2
Q2
1 2 1 2
Q4
1 2
ESC OK
1
Q3
1
Q1
1 2
Q4
1 2
Q2
15 AMP CURCUIT BREAKER
AUX!
FAN SWITCH
I4I2LNI1 I3
01. 20. 03
Mo 09:00
I5 I6 I7 I8 LN
OVERIDE SWITCH
OFF/ON
RPD10A ELECTRICAL DATA
I1 I2 I3 I4
RUN/STOP
BOX - TEN (10) WIRES
120V/1/60 - 10 AMPS.
PANEL MOUNTING
FILTER
BOX FILTER
CLOGGED
WARNING
REMOVED
FILTER
CLOGGED
PREFILTER
CLOGGED
BAG FILTER
HOLES LOCATED
IN PANEL BACK.
OVERIDE
NORMAL
KES
OFF/ON
RPD10 DIMENSIONAL DATA
8.0"
FIRE
14.0"
POWER SUPPLY FROM BREAKER PANEL
CONTROL WIRING BY MECHANICAL CONTACTOR
FACTORY WIRING BY SPRING AIR SYSTEMS
POWER WIRING BY GENERAL CONTRACTOR
14 BOX FILTER CLOGGED
FIRESTAT - HIGH LIMIT
0DOR SPRAY UNIT
BMS START/STOP
LV10 RESET
FILTER OUT/LOW AIR
18
20&21
17
16
15
PREFILTER CLOGGED
BAG FILTER CLOGGED
KES FAN/NORMAL OPERATION
TERMINAL
5
13
12
1&4
LEGEND
DESCRIPTION
5"
RPD10 Wiring Schematic
Figure 9
TO RPD10 REMOTE
INTERLOCK BETWEEN KES-ISH LV10 AND KESF MOTOR STARTER
POWER SUPPLY
KES-ISH
TO KESF FAN UNIT
POWER SUPPLY
SB10C OR SB10H
WATER WASH
PANEL MODEL
WATER WASH PANEL
RPW10 PANEL FROM
THREE (3) WIRES TO
TO SB10 WASH PANEL
POWER SUPPLY
120V/1/60
EXHAUST DISCHARGE
DUCTWORK DUCTWORK AS REQUIRED
FIELD INTERCONNECTING
KESF
CONTROLLER
RPW10
EXHAUST INLET
DUCTWORK
J-BOX - 120V/1/60
THE RPW10 CONTROLLER
FROM THE KES-ISH LV10
TEN (10) WIRES FROM