SPECIFICATIONS
Power supply Power 15-30VDC/24VAC (1), 50/60Hz, 4w max, 160mA max.
Wiring Conductor 14-24 AWG, Minimum 600V, 75°C
Terminal Torque 0.5 N•m
Outputs (Analog)
2 Programmable Outputs 0-10V (default), 0-5V, 4-20mA (selectable)
CO Output Scaling 0-200ppm (default), 0-500ppm (menu selectable)
NO Output Scaling 0-10ppm (default), 0-10ppm (menu selectable)
CO2 Output Scaling 0-10,000 ppm (default), 0-10,000 ppm (menu selectable)
Propane/Methane/Hydrogen Output Scaling 0-50% LEL (default), 0-50% LEL (menu selectable)
Oxygen Output Scaling 0-25% Vol (default), 0-25% Vol (menu selectable)
Refrigerant Output Scaling 0-1000 ppm (default), 0-1000 ppm (menu selectable)
H2S Output Scaling 0-100 ppm (default), 0-100 ppm (menu selectable)
Ammonia NH3 Output Scaling 0-100 ppm (default), 0-100 ppm (menu selectable)
Temp Output Scaling (optional) -20 to 85ºC
Output (BACnet/Modbus)
RS-485 BACnet MS/TP, Modbus RTU, Modbus ASCII
Baud Rates 9600, 19200, 38400, 57600, 76800, 115200
RS-485 Loading 1/4 unit
Trouble Relay Trouble relay characteristics N.C. 1A@24VAC/30VDC(50/60Hz)(No Mains Connection)
Alarm Relay Alarm relay characteristics N.O. 1A@24VAC/30VDC(50/60Hz)(No Mains Connection)
LED’s Green, Yellow, Red Green = Normal, Yellow = Relay, Red = Alarm
Audible exposure alarm 85dB@4” Piezo transducer 30 minutes above alarm set-point per UL2034 (menu selectable)
CO Sensor Performance
Type Electrochemical
Accuracy ±5% of Default Range, ±5% of Reading Above 200ppm
Resolution 1ppm
Life expectancy 7 years
Recommended Calibration Annual
Recommended Height 3 to 6 feet; coverage 5000-7500 sq ft.
NO Sensor Performance
Type Electrochemical
Accuracy ±5% of Default Range, ±5% of Reading Above 20ppm
Resolution 0.1ppm
Life expectancy 7years
Recommended Calibration Annual
Recommended Height 3 to 6 feet; coverage 5000-7500 sq ft.
CO Sensor Performance
Type Non-dispersive Infrared (NDIR)
Accuracy
±(30ppm +3% of reading) (400-2000ppm), @-10-50°C
±(50ppm +5% of reading) Standard (2000-5000ppm), @-10-50°C
±(50ppm+3% of reading) Dual Channel (2000-5000ppm), @-10-50°C
±(100ppm+10% of reading) (5000-10000ppm), @ 0-50C
Drift with ABC disabled 35ppm/month (6) (Standard) 5ppm/month (6) (Dual Channel)
Range 0-2000/5000ppm; Programmable up to 10,000ppm
Response time 30s
Sample rate 1s
Recommended Height 3 to 6 feet; coverage 5000-7500 sq ft.
(1) One side of transformer secondary is connected to signal common. Dedicated transformer is recommended. No mains circuit connection allowed. In addition,
it is required to use an isolated power supply that is certied by a national or international standard (i.e. UL). Use of a Class 2 LPS power supply or greater is
required.
(2) Carbon Monoxide full scale is 1000 ppm.
(3) Nitrogen Dioxide full scale is 30 ppm.
(4) Accuracy of CO reading may be reduced at temperatures below 14ºF (-10C).
(5) It is not recommended to de-activate ABC (auto-calibration) except for continuously occupied spaces or greenhouses. Drift ratings may vary based on
environment.