SALUPO MULTIPLUS 2 Manuel

INSTRUCTION AND INSTALLATION MANUAL
Direct starting electronic control panel 2 motors for clean water and sewage with display
and general disconnecting switch with door lock.
SA694.xx / SA697.xx
rev.5 11/01/2023
MULTIPLUS 2

INDEX
20
1. General instructions for installing
2. Warnings
3. Application examples
4. Wiring diagrams
4.1 Wiring diagram SA694.xx
4.2 Wiring diagram SA697.xx
5. Programming
5.1 Fast programming
5.2 Application 4-20mA bar
5.2 Application pressure booster
5.3 Application 4-20mA meters
5.3 Application sewage
5.4 Advanced programming
6. General functioning of the control panel
6.1 General functioning
6.2 Application pressure booster
6.3 Application clean water
6.4 Application sewage
6.5 Application 4-20mA bar
6.6 Application 4-20mA meters
9. Troubleshooting and proposed solutions
7. Motors maintenance
10. Alarm messages
11. Disposal of electrical & electronic equipment
12. Declaration of conformity CE y UK
22
29
38
38
27
26
31
31
32
33
36
8. Data logger
8.1 Alarm data logger
8.2 Event data logger
35
35
37
32
33
28
26
21
21
23
24
25
13. Warranty certificate
39
.1 7 Motors maintenance programming
. 7 2 Motors maintenance messages 34
34

ENGLISH
Eliminate whatever metal and/or plastic impurity which could happen to fall inside the box (screws,
washers, dust…).
When connecting electric cables, follow the wiring diagrams.
Make sure power supply is protected up to standard depending on application. The power of the
motor has to be within the control panel's limits of use.
When fixing the cables in the terminal board use tools of correct size to avoid damaging the metal
feed clamps and their sockets.
Before acting upon anything inside, disconnect power supply. Regulation procedures must be
carried out by qualified personnel. In case protections intervene verify the cause of the problem
before resetting.
If necessary substitute the various components only with those having the same characteristics and
components as the originals.
It is the installer' s duty to verify the device after the installation although it has already
undergone regular testing by the manufacturer.
Install the control panel in an environment appropriate to its IP65 degree of protection. To fix the
enclosure, use the brackets for the boxes 03-04 and the special predispositions for the remaining
boxes. In order to fix the box, use the appropriate holes which are present or suggested on the
bottom. Pay particular attention to not touching or damaging any components while fixing the box.
The manufacturer is released from all responsibilities for accidents to things or people, which
derive from misuse of the devices by unauthorized personnel or from lack of maintenance
and repair.
1. GENERAL INSTRUCTIONS FOR INSTALLING
2. WARNINGS
Risk of electric shocks if not complied with the requirements.
ELECTRIC SHOCKS
DANGER
Risk of personal injury and property if not complied with the requirements.
WARNING
Before installing and using the product read this book in all its parts. Installation and maintenance must be
performed by qualified personnel in accordance with current regulations.
The manufacturer will not be held responsible for any damage caused by improper or prohibited use of this
control panel and is not responsible for any damages caused by an incorrect installation or maintenance of the
plant. The use of non-original spare parts, tempering or improper use, make the product warranty null.
To operate inside the control panel use tools of correct size to avoid damaging the sockets.
WARNING
Be sure that the power of the motor is within the control panel range.Install the control panel in an environment
appropriate to its IP 65 degree of protection.
Before carrying out any intervention, make sure that the control panel is not powered.
In order to fix the box use the appropriate holes present on the bottom, don't damage internal components and
eliminate any working debris inside the box.
Do not attempt operations when the control panel is open.The control panel must be connected to an efficient
earthing system.
In the case of protections eliminate the cause of the malfunction before the restoration.
DANGER
3
21

5
3. APPLICATION EXAMPLES
Below are some practical examples of applications that can be implemented with the MULTIPLUS 2
control panel.
COMPONENTS KEY
22
Float switch for clean water
Float switch for sewage water
Level probe
Pressure switch
4-20mA pressure transducer
4-20mA piezoresistive probe
4-20mA bar
COM
MIN
MAX
TRANSD.
4-20m A
ANALOG
4-20 mA
KLIX1
KLIX2
+
-
COM
6
COM
MIN
MAX
4-20mA meters
ALARM
G.ALAR
KLIX1
KLIX2
ANALOG
4-20 mA
+
-
COM
7
PIEZOR.
4-20m A
CLEAN WATER
PRESSURE BOOSTER
COM
KLIX1
PR.STA
PR.EME
COM
KLIX2
COM
MIN
MAX
3
MIN
MAX
G.MIN
KLIX1
G.MIN
G.MAX1
G.MAX2
KLIX2
COM
START/
STOP 1
START/
STOP 2
4
G.MIN
KLIX1
G.MIN
G.MAX1
G.MAX2
G.ALAR
KLIX2
COM
START/
STOP 1
START/
STOP 2
ALARM
SEWAGE
5
KLIX1
G.MAX2
G.ALAR
KLIX2
COM
COM
MAX1
MAX2
ALARM
MIN
COM
MIN
MAX
STOP
START 1
START 2
KLIX1
G.MIN
G.MAX1
G.MAX2
G.ALAR
KLIX2
COM
ALARM
WHITE WATERS BLACK LIQUOR

ENGLISH
Max 10 mm²
(M4)
0,8Nm
10 mm
Max 4 mm²
(M3)
0,5Nm
9,8 mm
Max 2.5 mm²
(M3)
0,5Nm
8,3 mm
+ BROWN
- WHITE
4. WIRING DIAGRAMS
4 Wiring diagram.1 SA694.xx
POWER SUPPLY
230 Vac 50/60 Hz
MOTOR 2
M
1
1 2
G.MIN
COM
MIN
COM
MAX
G.MAX1 G.MAX2 G.ALAR
PR.STA PR.EME
KLIX1
COM
KLIX2
N.C.
N.O.
COM
ALARM
MOTOR 1
M
1
U V AVV.
MOTOR 1 U V AVV.
MOTOR 2
3 4 5 6 7 8 9 10 11 14 15 16
SIREN 12V FLASHING
LAMP 12V
12 13
+ -
ANALOG
4-20mA
7-8 ALARM FLOAT SWITCH OR EMERGENCY PRESSURE SWITCH
12-13 INPUT 4-20mA
11 MOTOR KLIXON 2
KEY
5-6 MAX2 FLOAT SWITCH OR START PRESSURE SWITCH
10 MOTOR KLIXON COMMON
3-4 LEVEL PROBES OR MAX1 FLOAT SWITCH
9 MOTOR KLIXON 1
1-2 LEVEL PROBES OR MINIMUM FLOAT SWITCH
14-15-16 PURE CONTACT ALARM OUTPUT (MAX 5A)
23
+ RED
- BLUE
EXPANSION BOARD
PIEZORESISTIVE LEVEL TRANSMITTER 4-20mA WIRINGPRESSURE TRANSDUCER WIRING
CAPACITORS
1 2
G.MIN
COM
MIN
COM
MAX
G.MAX1
3 4
COM
MIN
MAX
1 2
G.MIN
COM
MIN
COM
MAX
G.MAX1
3 4
G.MIN
PRESSURE BOOSTER
OR 4-20mA bar

Max 10 mm²
(M4)
0,8Nm
10 mm
Max 6 mm²
(M4)
2,5Nm
10 mm
Max 2.5 mm²
(M3)
0,5Nm
8,3 mm
+ BROWN
- WHITE
4. WIRING DIAGRAMS
4.2 SA697.xxWiring diagram
1 2
G.MIN
COM
MIN
COM
MAX
G.MAX1 G.MAX2 G.ALAR
PR.STA PR.EME
KLIX1
COM
KLIX2
N.C.
N.O.
COM
ALARM
SIREN 12V FLASHING
LAMP 12V
3 4 5 6 7 8 9 10 11 14 15 16
R
MOT1
S R S R S T
MOT2 SUPPLY
+ -
ANALOG
4-20mA
12 13
L1 L2 L3
U1
V1
W1
U2
V2
W2
M
3M
3
MOTOR 1 MOTOR 2
POWER SUPPLY
400 Vac 50/60 Hz
24
+ RED
- BLUE
KEY
7-8 ALARM FLOAT SWITCH OR EMERGENCY PRESSURE SWITCH
10 MOTOR KLIXON COMMON
3-4 LEVEL PROBES OR MAX1 FLOAT SWITCH
1-2 LEVEL PROBES OR MINIMUM FLOAT SWITCH
5-6 MAX2 FLOAT SWITCH OR START PRESSURE SWITCH
14-15-16 PURE CONTACT ALARM OUTPUT (MAX 5A)
9 MOTOR KLIXON 1
11 MOTOR KLIXON 2
12-13 INPUT 4-20mA
EXPANSION BOARD
PIEZORESISTIVE LEVEL TRANSMITTER 4-20mA WIRINGPRESSURE TRANSDUCER WIRING
1 2
G.MIN
COM
MIN
COM
MAX
G.MAX1
3 4
COM
MIN
MAX
1 2
G.MIN
COM
MIN
COM
MAX
G.MAX1
3 4
G.MIN
PRESSURE BOOSTER

ENGLISH
APPLICATION
PRESSURE BOOSTER
LANGUAGE
ENGLISH V3.0
APPLICATION
PRESSURE BOOSTER
LANGUAGE
ENGLISH V3.0
LANGUE
FRANCAISE V3.0
LINGUA
ITALIANO V3.0
PRESSING IT YOU WILL SEE THE REMAINING PART
OF THE PARAMETERS THAT CAN BE SET
ACCORDING TO THE APPLICATION CHOSEN:
PRESS. BOOSTER = SEE CHAPTER 5.2
CLEAN WATER = SEE CHAPTER 5.3
SEWAGE = SEE CHAPTER 5.4
4-20mA bar = SEE CHAPTER 5.5
4-20mA meters = SEE CHAPTER 5.6 }
SETUP PRESS
PAG + MAN 10s +
MOT. 1 AUTO-LEAR.
ENTER TO START
5.1 Fast programming
5. PROGRAMMING
ON
NO LOAD
MOT. 1 AUTO-LEAR.
13.2 A 0%
MOT. 2 AUTO-LEAR.
13.2A 0 %
MOT. 1 AUTO-LEAR.
COMPLETED
IN THIS STAGE THE MOTHERBOARD STARTS FOR
APPROXIMATELY 30s THE MOTOR RECORDING THE
PARAMETERS AUTOMATICALLY
THE MOTHERBOARD HAS CORRECTLY PERFORMED
THE AUTO-LEARNING PROCEDURE
25
APPLICATION
SEWAGE
APPLICATION
CLEAN WATER
APPLICATION
4-20mA bar
APPLICATION
4-20mA meters
MOT. 2 AUTO-LEAR.
COMPLETED
MOT. 2 AUTO-LEAR.
ENTER TO START
PRESSING IT FOR MORE THAN 1s YOU GO OUT
OF THE SETUP AND THE PARAMETERS
ARE STORED IN THE MEMORY
POSSIBLE ANOMALIES DURING THE AUTO-LEARNING PHASE
THE MOTHERBOARD
DOES NOT DETECT
ANY CONNECTED
MOTOR
THE ABSORBED
CURRENT EXCEEDS
THE MAXIMUM
ALLOWED THRESHOLD
MAXIMUM CURRENT
> -- A
It is used to scroll forward through the setup pages
It is used to increase the value of a parameter
It is used to scroll back through the setup pages
It is used to reduce the value of a parameter
Pressed it allows to enter the selected parameter
Pressed confirms the set value
Pressed it exits the parameter
IGNITION
CONTROL PANEL

5.3 Application sewage
5.2 Application pressure booster
5.1
5.1
PROBES SENSITIV.
1Okohm
IT IS USED TO SET
MANUALLY THE PROBES
SENSITIVITY VALUE
RANGE 0 ÷ 100kohm
PROBES SENSITIV.
1Okohm
PROBES SENSITIV.
1Okohm
IT IS USED TO SET
MANUALLY THE PROBES
SENSITIVITY VALUE
RANGE 0 ÷ 100kohm
PROBES SENSITIV.
1Okohm
BY PRESSING IT YOU RETURN
TO THE FIRST SETUP SCREEN;
SEE CHAPTER 5.6
BY PRESSING IT YOU RETURN
TO THE FIRST SETUP SCREEN;
SEE CHAPTER 5.6
PRESSING IT FOR MORE THAN
1s YOU GO OUT OF THE SETUP
AND THE PARAMETERS ARE
STORED IN THE MEMORY
PRESSING IT FOR MORE THAN
1s YOU GO OUT OF THE SETUP
AND THE PARAMETERS ARE
STORED IN THE MEMORY
5. PROGRAMMING
26

ENGLISH
5.2 Application 4-20mA bar
5. PROGRAMMING
TRANSDUCER
10 bar
TRANSDUCER
10 bar
TRANSDUCER
16 bar
START PRESSURE
3.0 bar
START PRESSURE
3.0 bar
EMERG. PRESSURE
2.0 bar
DELTA PRESSURE
1.0 bar
DELTA PRESSURE
1.0 bar
IT IS USED TO SET THE
PRESSURE THAT ADDED TO
THE "START PRESSURE"
STOPS THE MOTOR
TRANSDUCER
25 bar
5.1
EMERG. PRESSURE
2.0 bar
IT IS USED TO SET THE NECESSARY
PRESSURE TO START THE
RESCUE MOTOR
27
IT IS USED TO SET THE FULL
SCALE OF THE TRANSDUCER
USED
IT IS USED TO SET THE
PRESSURE REQUIRED TO
START THE MOTOR
TRANSDUCER 10bar: 0.1 ÷ 8bar
TRANSDUCER 16bar: 0.1 ÷ 14bar
TRANSDUCER 25bar: 0.1 ÷ 23bar
TRANSDUCER 10bar: 0.1 ÷ 8bar
TRANSDUCER 16bar: 0.1 ÷ 14bar
TRANSDUCER 25bar: 0.1 ÷ 23bar
MINIMUM PRESSURE
OFF
MINIMUM PRESSURE
OFF
OFF EXCLUDES
MINIMUM PRESSURE
TRANSDUCER 10bar: 0.1 ÷ 8bar
TRANSDUCER 16bar: 0.1 ÷ 14bar
TRANSDUCER 25bar: 0.1 ÷ 23bar
MINIMUM PRESSURE
0.5 bar
TRANSDUCER 10bar: 0.1 ÷ 8bar
TRANSDUCER 16bar: 0.1 ÷ 14bar
TRANSDUCER 25bar: 0.1 ÷ 23bar
IT IS USED TO SET THE REQUIRED
PRESSURE BELOW WHICH THE
MOTORS STOP. AT THE MOTORS’
STARTING THIS PARAMETER IS
BYPASSED FOR 1 MINUTE
PROBES SENSITIV.
1Okohm
IT IS USED TO SET
MANUALLY THE PROBES
SENSITIVITY VALUE
RANGE 0 ÷ 100kohm
PROBES SENSITIV.
1Okohm
BY PRESSING IT YOU RETURN
TO THE FIRST SETUP SCREEN;
SEE CHAPTER 5.6
PRESSING IT FOR MORE THAN
1s YOU GO OUT OF THE SETUP
AND THE PARAMETERS ARE
STORED IN THE MEMORY

5. PROGRAMMING
5.3 Application 4-20mA meters
MAX 1 LEVEL
0.50 m
MAX 1 LEVEL
0.50 m
RANGE 0.10 ÷ 24.90mRANGE 1.0 ÷ 25.0m RANGE 0.05 ÷ 24.85m
IT IS USED TO SET THE WATER LEVEL
ABOVE WHICH THE MOTHERBOARD
STARTS THE FIRST MOTOR
RANGE 0.20 ÷ 25m
5.1
MAX 2 LEVEL
0.80 m
MAX 2 LEVEL
0.80 m
IT IS USED TO SET THE WATER
LEVEL ABOVE WHICH THE
MOTHERBOARD STARTS
THE SECOND MOTOR
RANGE 0.15 ÷ 24.95m
28
PROBE 4-20 mA
5.0 m
PROBE 4-20 mA
5.0 m
IT IS USED TO SET THE FULL
SCALE OF THE PROBE USED
MINIMUM LEVEL
0.50 m
MINIMUM LEVEL
0.50 m
IT IS USED TO SET THE WATER LEVEL
BELOW WHICH THE MOTHERBOARD
TURNS OFF THE MOTORS
ALARM LEVEL
1.00 m
ALARM LEVEL
1.00 m
IT IS USED TO SET THE WATER
LEVEL ABOVE WHICH THE
MOTHERBOARD ENABLES
THE ALARM OUTPUT
PRESSING IT FOR MORE THAN 1s
YOU GO OUT OF THE SETUP AND
THE PARAMETERS ARE STORED
IN THE MEMORY
PRESSED IT DISPLAYS THE
REMAINING PART OF THE
PARAMETERS SEE CHAPTER 5.6
Table des matières
Autres manuels SALUPO Système de contrôle