GENERAL WARNINGS
lInstallation and product use must conform to the directions in this manual.
lSolenoid powered outputs are rated to 5A max individually; however, the power input to the BMS card is
fused at 10A. Care must be taken not to exceed the 10A max input when installing with high-powered
solenoids.
lDo not jumper solenoid (-) terminals together under any circumstance; this compromises the safety-integ-
rity of the system.
lSafety Functions must be end-to-end proven during commissioning (e.g., when using a high-pressure
switch, ensure a high-pressure event triggers a lock-out).
INSTALLATION WARNINGS
lElectrical devices connected to the controller must meet local electrical codes, and be within voltage lim-
its specified in this manual.
lEnsure the enclosure is securely closed each time after opening. Improper closure may result in mois-
ture and or other environmental damage and may also compromise the integrity, and warranty of the
product.
lThe System must be connected appropriately to earth-ground to prevent electrocution.
lNo more than one conductor is to be used per contact point.
lProperly fuse field wiring to local codes.
lDo not disassemble or modify the cards in any way. The cards are not field repairable and must be sent
back to Profire for a replacement if damaged.
lCard installation shall be performed in accordance with local electrical code(s) by a capable electrician.
Installation and modification shall NOT be performed while the system is energized.
lFailure to provide a low-impedance path from the burner assembly to the PF2200 may result in acci-
dental electric shock, product damage, failure to ignite the pilot or failure to detect a flame.
lDo not connect wires or handle the electronics when powered.
lDo not modify the product once installed.
lBypass of safety function(s) is required to update software.
EXPLOSION HAZARD WARNINGS
lDo not disconnect power, open the enclosure, or otherwise service this product unless the area is known
to be non-hazardous.
lSubstitutions of components may impair suitability for specified zones.
lReplacement fuses must be ceramic and of a correct rating.
lAvoid unauthorized replacement of the fuse.