
7
piping) train and burner. All piping should be designed, supported and installed to avoid any
piping weight transmitted to the boiler / burner connections.
CAUTION: THE BOILER IS NOT DESIGNED TO SUPPORT EXTERNAL PIPING LOADS.
2.3.2 Process Flow Connections
The process system feedwater and steam connections are shown on the boiler dimensional
drawing. The necessary code valves for feedwater, steam supply, and blowdown are normally
supplied with the boiler. To allow for inspection and cleaning, the drain valve can be opened
after the boiler is isolated and de-energized.
2.3.3 Safety Relief Valve(s)
A connection is provided in the top of the boiler for the relief valve(s). The relief valve
discharge piping must be, as a minimum, the same size as the safety valve discharge opening.
All safety valve discharge piping must be independently supported with no weight carried by
the valve. Over-tightening screwed joints can distort valve seats. Pipe the relief valve outlet(s)
to the floor drain (Section IV boilers) or to overhead discharge outside safely away from
personnel (Section I boilers).
2.3.4 Boiler Air Vent / Expansion Tank Connection
The boiler is provided with a 3/4” vent valve located on the top of the low water cutoff bridle.
This connection is for venting air on boiler filling operations and hydrostatic testing.
2.3.5 Drain Connection
A drain valve is installed at the boiler drain connection. Piping, the same pipe size as this valve,
should be routed to a suitable drain point. Drain piping should be terminated within two feet
from the drain valve for easy viewing.
2.4 Fuel Supply Piping
2.4.1 General
The installation must conform completely to the requirements of the authority having
jurisdiction, or in absence of such, requirements shall conform in the U.S. to the current
National Fuel Gas Code, ANSI Z223.1, or in Canada to the current Installation Code for Gas
Burning Appliances and Equipment code (CAN/CGA B139-M91), or Oil Burning Equipment code
(CSA B139-M91), and applicable regional regulations for the class; which should be followed
carefully in all cases. Consult the local gas utility company for inspection and authorization of
all gas supply piping and flue connections. The regulator vent line must be vented to outside of
the building on any boiler equipment with electric gas pilot ignition.
2.4.2 Gas Supply Connections
Gas supply connections must comply with the National Fuel Gas Code (NFPA 54). Gas pressure
must be regulated to the required pressure for the burner. (Standard (Power Flame burners
require a range of 5 –12 inches of water pressure.) Consult the local gas company for all
inspection and authorization of all gas supply piping and flue connections. Gas connections
should be made with unions or flanges so that the boiler gas train components and burner may
be easily removed for service, if necessary. A
drip leg or sediment trap must be installed in the gas supply line near the connection to the
burner gas valve train.