Oxygen X-Air C200 Manuel utilisateur

Rev 1.6 2019.06
INSTALLATION AND OPERATION MANUAL
Heat Recovery Unit OXYGEN X-Air C200

1

2
CONTENTS
1. TRANSPORTATION AND STORAGE OF EQUIPEMENT .......................................................................................3
2. UNIT PACKAGE ..................................................................................................................................................4
3. SAFETY REQUIREMENTS ...................................................................................................................................5
4. EU DECLARATION OF CONFORMITY .................................................................................................................6
5. TECHNICAL DATA ..............................................................................................................................................7
5.1. Performance characteristics .................................................................................................................8
5.2. Performance and power consumption .................................................................................................8
5.3. Sound characteristics ............................................................................................................................9
5.4. Dimensions and weight ..................................................................................................................... 10
6. FUNCTIONALITY ............................................................................................................................................. 11
7. INSTALLATION OF THE UNIT .......................................................................................................................... 12
7.1. Selecting the mounting location ........................................................................................................ 12
7.2. Installation incline ............................................................................................................................. 12
7.3. Connecting ducts ............................................................................................................................... 13
7.4. Installing the maintenance and servicing hatch ................................................................................ 14
7.5. Connecting the condensate drain ..................................................................................................... 15
8. CONNECTION OF THE UNIT ........................................................................................................................... 16
8.1. Connecting electric circuit ................................................................................................................. 16
8.2. Connecting the control panel ............................................................................................................ 17
8.3. Connector of comfort functions ........................................................................................................ 18
8.4. Control board electrical wiring diagram ............................................................................................ 19
8.5. Description of control board contacts ............................................................................................... 20
9. OPERATION OF THE UNIT .............................................................................................................................. 21
9.1. Control panel with a knob ................................................................................................................. 21
9.1.1. Operating state indicator .............................................................................................................. 21
9.1.2. Air filter replacing / anti-frost protection indicator ...................................................................... 21
9.1.3. Failure indicator ............................................................................................................................. 22
9.1.4. Additional system settings............................................................................................................. 23
9.2. Control panel with touchscreen display ............................................................................................ 25
9.2.1. Standby mode ................................................................................................................................ 25
9.2.2. Main screen ................................................................................................................................... 26
9.2.3. Settings menu ................................................................................................................................ 27
9.2.4. Setting up weekly operation program ........................................................................................... 27
9.2.5. Failure indication ........................................................................................................................... 28
9.3. Replacing of air filters ........................................................................................................................ 29
10. MAINTEINANCE AND WARRANTY ................................................................................................................. 31
11. CONTACTS ...................................................................................................................................................... 32

3
1. TRANSPORTATION AND STORAGE OF EQUIPEMENT
Heat Recovery Unit (hereinafter – the Unit) is prepared for transportation and storage. Packaging
materials ensure protection against exposure to environment, dust and humidity. The Unit must be
properly secured during transportation to protect it against possible housing deformation or other
mechanical damage.
Transportation conditions:
-20oC - +40oC.
Long-term storage conditions:
+5oC - +40oC, relative air humidity <= 60%.
IMPORTANT! Sender does not assume any obligations towards damage or loss of the Unit or its part, if
there is no a corresponding record in the consignment document!
CONSIGNMENT ACCEPTANCE:
Carefully check the received consignment – make sure that the number of packages matches with
the consignment documentation. Upon noticing any non-conformity or damage of the package
(tears, dents or compressed box, detached or reattached packaging tape), inform the courier
immediately and indicate the disrepancies or damages in the consignment document.
Verify if the right product was delivered. Upon noticing any non-conformity, inform the Sender
immediately.
Verify if all the supplementary parts listed were delivered. In case of any doubt, contact the Sender
immediately.
Do not attempt to repair the Unit, damaged during the transportation by yourself!

4
2. UNIT PACKAGE
Heat Recovery Unit Oxygen X-Air C200 1 pc.
Control panel 1 pc.
Contol panel connection cable, 10m 1 pc.
Fastening elements:
L-shaped horizontal installation bracket 4 pcs.
Bolt (type M5), 8 mm 8 pcs.
Spring washer (type M5) 8 pcs.
Condensate drain nozzle, Ø32 1 pc.
Condensate drain gasket, Ø20 1 pc.
Installation manual 1 pc.

5
3. SAFETY REQUIREMENTS
Carefully read and follow safety requirements provided below before installing and while operating the
Unit:
Do not discard the Installation and operation manual, keep it for future reference.
The Unit should be installed and operated in compliance with this Installation and operation
manual, following the requirements of effective legislation and standards.
When connecting the Unit to mains supply, grounding must be installed in compliance with
requirements of effective legislation and standards.
To prevent accidents and potential damage to the Unit, it should be installed, connected,
maintained and repaired only by qualified technician. Never attempt to do this by yourself!
Turn off the Unit by using Control panel and wait for fans to stop completely before replacing air
filters.
Turn off the Unit by using Control panel, wait for fans to stop completely and disconnect the Unit
from mains supply before performing any maintenance.
Before connecting the Unit make sure that no items will get sucked into the its air intake openings!
Children may only use the Unit under adult supervision.
The Unit is not intended to be used by persons (including children) with reduced physical, sensory
or mental capabilities, unless they have been instructed to use of the Unit and under constant
supervision of person held responsible for their safety.
Only original supplementary parts and consumables, certified by manufacturer should be used.
The Unit package (cardboard, plastic, foam polystyrene) can pose hazard to children. Dispose of
or recycle the package elements!
Disused Unit should be disposed of in accordance with requirements of legislation on handling
of waste electrical and electronic equipment.
IT IS PROHIBITED to operate the Unit with damaged mains supply cable! Switch off the power
circuit-breaker to disconnect mains supply and contact a qualified technician or manufacturer
service centre immediately upon noticing such damage.
IT IS PROHIBITED to attempt the repair of the damaged Unit or its part, to open its cover! Contact
a qualified technician or manufacturer service centre.

6
4. EU DECLARATION OF CONFORMITY
We, undersigned below, representing the manufacturer of ventilation equipment:
Sviezias oras, JSC
Birzelio 23-osios g. 23G
50220 Kaunas
LITHUANIA
confirm, that heat recovery ventilation device Oxygen X-Air C200 conforms to Europe Union standarts,
directives and regulations:
2009/125/EC – eco-design requirements for energy-related products
ES 1253/2014
2010/30/EU – labelling and standard product information of the consumption of energy and other
resources by energy-related products
ES 1254/2014
2011/65/EU – restriction of the use of certain hazardous substances in electrical and electronic
equipment (RoHS)
EN 50581(2012)
2014/35/EU – harmonization of the laws of the Member States relating to the making available on the
market of electrical equipment designed for use within certain voltage limits
LST EN 60335-1:2012 (EN 60335-1:2012)
LST EN 60335-1:2012/A11:2014
CEO Zilvinas Salialionis
10.05.2018, Vilnius

7
5. TECHNICAL DATA
a) Supplier's name or trade mark OXYGEN
b) Model identifier X-Air C200
c) Specific energy consumption (SEC), SEC class A
Warm climate kWh/m2.a
-15.7
Average climate kWh/m2.a
-40.0
Cold climate kWh/m2.a
-77.7
d) Declared typology Bi-directional,
residential ventilation
e) Type of drive installed or intended to be installed Variable speed drive
f) Type of heat recovery system Recuperative
g) Thermal efficiency of heat recovery % 81
h) Maximum flow rate m3/h 191
i) Electric power input of the fan drive, including
any motor control equipment, at maximum flow
rate
W 106
j) Sound power level (LWA) 49
k) Reference flow rate m3/s 0.0378
l) Reference pressure difference Pa 50
m) Specific power input (SPI) W/(m3/h) 0.353
n) Control factor 0.65
Control typology Local demand control
o) Declared maximum leakage rate:
internal % 2.31
external % 1.16
q) Position and description of visual filter warning See user’s manual
s) Internet address for pre-/dis-assembly
instructions
www.oxygen.lt
v) The annual electricity consumption (AEC)
Warm climate kWh/m2.a
1.9
Average climate kWh/m2.a
2.3
Cold climate kWh/m2.a
7.7
w) The annual heating saved (AHS)
Warm climate kWh/a 20.4
Average climate kWh/a 45.0
Cold climate kWh/a 88.0
According to commission delegated regulation (EU) No. 1254/2014

8
5.1. Performance characteristics
Graph. 1. Ventilation power dependence on the resistance of the installed ventilation system
5.2. Performance and power consumption
Power setting Resistance, Pa Air flow, m3/h El. outlay, W
100%
100 191 101
150 189 99
200 184 98
250 172 100
300 154 98
350 136 96
400 110 97
450 91 97
490 75 98
70%
50 140 46
100 130 46
150 114 44
200 85 44
250 61 41
50%
25 100 24
75 80 24
115 50 22
According to EN13141-7, with G4 class filters installed.
0
100
200
300
400
500
600
40 65 90 115 140 165 190
Pasipriešinimas, Pa
Air flow, m3/h
Performance curves
50%
70%
100%

9
5.3. Sound characteristics
Power
setting
Air duct
Sound power level (LWA)
Octave band, Hz Total
125 250 500 1000 2000 4000 8000
50%
Suppply 34.1
42.8 42.2 41.7 40.9 30.6 17.5 48.2
Extract 13.3
35.6 35 26.8 22.4 14.8 12.6 38.8
Outside 15.1
36.7 32.1 26.9 21.8 14.4 12.6 38.5
Exhaust 28.9
39.7 42 40.7 38.5 28.6 16 46.6
70%
Suppply 39 51.1 51.8 51.2 49.9 43.8 30.4 57.3
Extract 21.5
45.2 44.5 36.6 33.2 22.5 14.2 48.4
Outside 22 44.6 42.8 36.1 33.1 21.7 13.7 47.3
Exhaust 35.4
51.1 51.6 50.4 48.4 41.8 28.7 56.8
100%
Suppply 43 56.1 63.3 58.5 58.7 53.6 41.3 66.3
Extract 30.1
47.7 55.3 46.5 42.4 32.1 21.6 56.7
Outside 29.7
48.1 54.3 45.7 42.4 30.7 20.7 55.9
Exhaust 41.2
53.3 62 58.4 57.6 52.7 40 65.2
According to LST EN13141-7.
Autres manuels pour X-Air C200
1
Table des matières
Autres manuels Oxygen Système de chauffage

Oxygen
Oxygen X-Air C180 Manuel utilisateur

Oxygen
Oxygen TYPHON 2000 Manuel utilisateur

Oxygen
Oxygen X-Air C180E Manuel utilisateur

Oxygen
Oxygen X-Air V200E Manuel utilisateur

Oxygen
Oxygen X-Air V500 Manuel utilisateur

Oxygen
Oxygen X-Air V200 Manuel utilisateur

Oxygen
Oxygen X-Air V600 Manuel utilisateur

Oxygen
Oxygen X-Air V400E Manuel utilisateur

Oxygen
Oxygen X-Air C250 Manuel utilisateur

Oxygen
Oxygen X-Air C200E Manuel utilisateur