2. For front and side clearance requirements (for
access during installation, maintenance and
troubleshooting), see Figure #2.
3.
Location
of
the steam distributor should be
minimum
of
36" above the humidifier.
4.
DO NOT locate humidifier any further than
absolutely necessary from steam distributor
location. Net output will
be
reduced as a result
of
heat loss through steam hose (see
Engineering Manual, Form # -1630). Also,
increased static pressure (over
7"
W.
C.) will
result
in
steam leaking down the drain.
Consult factory if this situation occurs.
5.
Where possible, mount humidifier at a height
convenient for servicing.
6.
Wall mounting brackets (provided with GH
100) should
be
securely attached open edge
upwards, horizontal, using field-supplied
fasteners (minimum offour
3/8"
diameter
fasteners
in
each bracket). Attach
to
a
vertical, solid surface. Put a security bolt
through the hole provided
in
the back of the
cabinet so that the unit cannot
be
bumped off
the wall bracket. See Figure #3.
Figure
#3
c
7.
Make sure humidifier
is
mounted level. Iffloor
mounted adjust using leveling legs.
8.
The GH 100 model
is
equipped with
adjustable leveling legs which may be
removed for mounting the unit
on
an optional
GH stand. Maximum travel of legs
is
2"
9.
The GH 200,
GH
300 and
GH
400 are
equipped with adjustable leveling legs which
have a maximum travel of
2".
-These legs may
be
removed
to
allow
mounting
of
an
optional stand.
- 4 -
-These legs may
be
removed and replaced
by
longer legs. Factory approval is needed.
-Removal or adjustment
of
legs requires the
square end of a
3/8"
socket driver.
10. Optional stands are available for all GH Series
humidifiers. Refer to Shop Drawing Package,
Form # 273 for details and part numbers.
15
Clearances around the unit should also be
maintained for good access the gas humidifier.
3 feet clearance
is
needed
on
the right side of
the enclosure for GH100/200, 4 feet is needed
on
the right side of the enclosure for the
GH300/400. The front requires 3 feet
clearance for
ail
capacities.
16.
DO
NOT mount humidifier on hot surfaces.
17.
DO
NOT mount humidifiers
in
an
area where
freezing may occur.
18. If humidifiers
are-
mounted on roof, a properly
ventilated, temperature controlled, (above
freezing), weatherproof enclosure. Consult
your local representative for more information
on
Nortec's enclosure.
19.
DO
NOT mount humidifiers on vibrating
surface. Consult factory.
20.
In
earthquake prone
are.:Js
do not wall mount.
Use the existing wall mount brackets
to
fasten
unit
to
the wall with it sitting
on
the floor.
Maintain spacing for air openings. (See
"Installation" item
8).
NOTE FOR OUTDOOR ENCLOSURE:
Optional outdoor enclosure can also be used;
unit
is
factory mounted inside the enclosure.
The enclosure should be installed at a secure
distance from any air or exhaust system. (also
see local code)
The enclosure should be bolted down or
secured if it
is
to
be
exposed
to
high winds.
Iflifting
the
enclosure
on
the roof using a
forklift, lift under the unit at cross members for
stability. (Strapping belts can also be used.)
GAS PIPING
Installation of piping must
be
in
accordance with
local codes, and ANSI Z233.1, "National Fuel Gas