User Manual 03User Manual 02
Product parameters Connection type
Type ASD25DC
Pole 4P
Installation Fixed
Rated current(A) 800A/1000A/1250A/1600A/2000A/2500A
Rated Maximum Volatge(V) DC1500
Short circuit withstand current (kA) 120/150
Operating time(ms) Max.openning time Max.openning time ≤30
Max.closing time Max.closing time ≤70
Life cycle(time) Mechanical 12500
Electrical 2000
External dimensions
Inches(mm) H×W×D
800A-2000A 15.43×18.31×17.01 (392×465×433)
2500A 15.43×18.31×18.78 (392×465×477)
Enclosure dimensions
Inches(mm) H×W×D
21.73×23.62×13.86 (552×600×352)
Ventilation Area Top: 18183mm²
TypeC
Upper Supply Lower supply
TypeD
Environmental conditions
Ambient temperature
Altitude
Humidity
Rated
Current(A)
Temperature(℃)
Horizontial type Vertical type
<40 45 50 55 60 65 70 <40 45 50 55 60 65 70
800 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100% 100%
1600 100% 100% 100% 100% 100% 95% 90% 100% 100% 100% 100% 100% 100% 100%
2000 100% 100% 100% 100% 95% 90% 85% 100% 100% 100% 100% 100% 95% 93%
2500 100% 100% 100% 95% 90% 85% 80% 100% 100% 100% 100% 95% 93% 90%
Altitude(m)
<2000 3000 4000 5000
Rated Voltage(V) 1xIn 0.9xIn 0.8xIn 0.7xIn
Rated Current(A) 1xIn 0.98xIn 0.96xIn 0.94In
ASD25DC air switch disconnector can operate in -40℃~ 70℃environmental conditions.
ASD25DC air switch disconnector can operate at higher temperatures than the reference temperature 40℃,in this case,the derating
coefficients shown in the table must be applied.
ASD25DC air switch disconnector do not undergo changes in rated performance up to 2000m.Beyond this altitude ,the derating
coefficients shown in the table must be applied.
The relative humidity does not exceed 85% at 40℃,the monthly average maximum of relative humidity in the wettest month
does not exceed 90%.
The effect of surface condensation caused by temperature changes on product performance should be taken into consideration.
*Configuration C for ungrounded system only
*Configuration D for either grounded or ungrounded in PV system
Load
+(-) -(+)
Load
+(-)
-(+)
Load
+(-) -(+)
Load
+(-)
-(+)