After power on, the device will immediately send a version packet and an attribute report data.
The device sends data according to the default configuration before any other configuration.
Default setting:
Report MaxTime: 0x0E10 (3600s)
Report MinTime: 0x0E10 (3600s) // The current voltage value is detected every Min Interval by default
Battery Voltage Change: 0x01 (0.1V)
Shock Sensor Sensitivity: 0x14 (20) // Range: 0x00 to 0xFE ; 0xFF: Disable shock sensor
No Active Alarm Time: 0x003C (60 min.)
Start Hour: 0x00 (00:00 AM) // Range: 0x00 to 0x17 (00:00~23:00)
End Hour: 0x06 (06:00 AM) // Range: 0x00 to 0x17 (00:00~23:00)
Emergency button triggering:
By default, press the button briefly. After the red light flashes, release the button to report an alarm
Alarm status: 1 Normal state: 0
Long time static detection function:
R309 series has a long-time inactivity detection function.
When the vibration sensor on R309 detects that it has not detected an active state for more than the set time (default is 1
hour), it will report a static detection alarm.
At the same time, R309 supports turning off the long-time static detection alarm function within a specific time range
(default is 00:00-06:00), which is used to turn off the static detection function at night.
Note:
1. The pressing time of the alarm button can be configured through the command (0~4s)
2. The cycle of the device sending the data report is according to the default.
3. The interval between two reports must be the MinTime.
The device reported data parsing please refer to Netvox LoraWAN Application Command document and Netvox Lora
Command Resolver http://cmddoc.netvoxcloud.com/cmddoc