4 – FS 345 Door Controls / Rev. A 0.0
Low voltage
− DINEN60335-1(Householdandsimilarelectricalappli-
ances-Safety-Part1:Part1:Generalrequirements)
− DINEN60335-2-103(Householdandsimilarelectrical
appliances-Safety-Part2-103:Particularrequirementsfor
drivesforgates,doorsandwindows)
CommitteeforWorkplaces(ASTA)
− ASRA1.7(Workplaceregulation“Doorsandgates“)
General safety instructions
− Toenablefault-freeoperationtobeguaranteed,itis
imperative that the rechargeable battery be replaced after
every two years of operation. If this maintenance instruc-
tionisdisregarded,thefunctionalsafetyofthesystemand
thus also the safety of buildings and persons cannot be
guaranteed.
− Toensurethatthesystemalwaysfunctionsconsistently,the
realarmfunctionmustbecheckedonceeveryfourweeks.
In order to check at the same time that the rechargeable
batteryalsofunctionscorrectly,thecontrolmustbediscon-
nectedfromthemains.Inthisway,theemergencyfunction
can be checked to ensure that the door is closed automati-
cally by the auxiliary motor.
− Emergencyoperationisnotpossibleifthereisafaultinthe
safety circuit of the door operator.
− Toavoidadeepdischargeoftherechargeablebattery,the
batteryshouldnotbeconnectedtotheFS101unituntil
thesystemisputintooperationforthersttime.Ifdeep
dischargeoccurs,thebatterycannotberechargedagain
and must be replaced immediately.
4. Overview of products
4.1 Product description
TheFS345controlcanbeusedinconnectionwithFDF,FT,
FTAandFDSre-protectiondrivesaswellaswithhydraulic
drives.InversionFS345HY,hydraulicdrivesareused.
TheFS345controlconsistofaCS300FSdoorcontrolunit,
anFS101auxiliarycircuitboardandarechargeablebattery
foremergencypowersupply,magneticcouplings,DC-operat-
edmotors,24Vmotorbrakes.
Incaseofreorpowercuts,theemergencyrechargeable
battery provides the energy required for the auxiliary motor
to close the door or for the motor brake to hold the door in
position.
Theremodeistriggeredbyacontinuouscommandinthe
realarmcontactoristimeactivatedifthemainspowersup-
plyfails.Inthecaseofre,thedoorcloseswiththeclosing
edgesystemdeactivated,or,optionally,withtheclosingedge
activated.
4.2 Various options
ThefollowingmodelsofFS345controlcanbesupplied:
− FS345controlfordeadmanoperation
− FS345controlforautomaticoperation
− FS345controlforautomaticoperationwiththeclosing
edgesystemactivatedinthecaseofre
The following housing models are available:
− HousingwithOPEN-STOP-CLOSEbuttons
− HousingwithON/OFFkeyswitch
− Housingwithmainswitch
− HousingwithemergencyOFFswitch
The operating instructions describe the connection options
andmodelsoftheFS345control.
General safety instructions