4
2
3 Installation.
31.of CommissioningConcept
The following steps are required or a new project or a modified project:f
①After wiring of lamps and input devices, turn on the all devices and lamps.
Please refer to chapter 3.3 and 3.4 for electrical wiring.
Please refer to chapter 4.3.1.2 for the DLC software to set ECG parameters.
②After scanning the devices on the bus and assigning short addresses
through the DLC software, then set the parameters of the ECGs, such as
maximum level, minimum level, fade rate/time, power on level, system failure
level, group and scene.
③Set the logical relationship between the controlling party (input device, and
timing event) and the controlled party (lamp, relay ) on theand sequence
effect interface, and download it to DLC-02.
Effect configuration
Wring of the DALI-2 devices
(or devices to the relays)
New initialization and lamp
parameter setting
For the DLC software to set effect, please refer to chapter 4.4.
• Electric power bus configuration
• DALI bus configuration
• Lamp installation
• Basic settings and DALI bus basic test
• settingsNew initialization
• Basic settings of lamps
Rename/Max. level/Min. level/fade time…..
• connectionEffect
• Effect setting
ON-OFF/Dimming/Timer…..
The following example shows how to scan the lamps and input devices on
the bus to the software interface through the DLC software.
Suppose bus A is connected to two lamps and an input device, and bus B
is connected to a lamp.
Step 1: After connecting the computer and DLC-02 with a USB cable, open
the DLC software and click "Connect" to ensure the normal
communication between the computer and DLC-02.