SEDM-D
Smoke extraction damper-multi
Technical Documentation
Installation, Commissioning, Operation, Maintenance and Service Manual
TPM 155/22
Version 2023-06-07

Smoke extraction damper - SEDM-DPage 2 Version 2023-06-07
TPM 155/22
These technical specifications state a typerange of manufactured sizes and models of smoke extraction dampers SEDM-D
It is valid for production, designing, ordering, delivery, maintenance and operation.
CONTENT
I. GENERAL.....................................................................................................................................................................................3
Description..............................................................................................................................................................................3
II. DESIGN.......................................................................................................................................................................................5
Hand-operated designs...........................................................................................................................................................6
Rearming motor designs.........................................................................................................................................................6
Grilles designs.........................................................................................................................................................................9
Electric parameters, wiring diagram.....................................................................................................................................11
III. DAMPER CONTROL.................................................................................................................................................................13
IV. DIMENSIONS...........................................................................................................................................................................15
Technical parameters............................................................................................................................................................16
V. INSTALLATION.........................................................................................................................................................................18
Placement and Installation...................................................................................................................................................18
Statement of installations.....................................................................................................................................................19
Installation procedure...........................................................................................................................................................20
Cable connection...............................................................................................................................................................21
Shock absorber..................................................................................................................................................................22
Installation frame..............................................................................................................................................................22
Installation - shaft from concrete or aerated concrete.....................................................................................................25
Installation - shaft from fire-resistant panels....................................................................................................................27
VI. TECHNICAL DATA....................................................................................................................................................................29
Pressure loss.........................................................................................................................................................................29
VII. MATERIAL, FINISHING............................................................................................................................................................30
VIII. TRANSPORTATION, STORAGE AND WARRANTY...................................................................................................................30
Logistic terms........................................................................................................................................................................30
Warranty...............................................................................................................................................................................30
IX. ASSEMBLY, ATTENDANCE AND MAINTENANCE......................................................................................................................31
Entry into service and revisions.........................................................................................................................................31
X. ORDERING INFORMATION.......................................................................................................................................................31
Data label..............................................................................................................................................................................31
Ordering key.........................................................................................................................................................................32
Smoke extraction dampers SEDM-D..................................................................................................................................32
Accessories........................................................................................................................................................................33
Spare parts.........................................................................................................................................................................33

Page 3Version 2023-06-07 Smoke extraction damper - SEDM-D
TPM 155/22
I. GENERAL
Description
Smoke extration dampers SEDM-D (hereinafter named also
simply as „the dampers“) are intended to be used in multi
compartment smoke control systems in vertical duct (shaft)
installations.
In normal situation, the dampers remain closed (stand-by
position). Upon an activation signal emitted either in the
event of a fire, or during a functional test, the dampers of
given compartments open in order to allow smoke and heat
from the fire to be extracted outside the building. SEDM-D
dampers open to the inside of the duct. The dampers opened
during functional testing may be put back to the stand-by
(closed) position by hand, or by using an optional electric
rearming motor.
The dampers consist of a single calcium-silicate blade
reinforced by steel crossbeams hanged on spring-equipped
hinges, combined calcium-silicate and aluminum frame, a
cold seal (silicon gasket) and a carbon based thermo-
-expanded hot seal, electrically activated restraint
mechanism equipped by a permanent magnet with an
electric coil, optional with end switches and optional electric
rearming motor, and a metallic grille.
The dampers may be installed to the shaft directly using
fire-resistant mastic, mortar, gypsum or using an optional
installation frame.
SEDM-D dampers are characterized by
■Zero power consumption in stand-by position
■Instant opening and fast closing
■Small built-in dimensions
■Light design of high fire and pressure resistance
■Large effective area
■Room protected from moving parts
■Wide range of damper dimensions
■Wide range of colours available
■Easy installation also into thin shaftwall materials
■Availability of spare parts

Smoke extraction damper - SEDM-DPage 4 Version 2023-06-07
TPM 155/22
Specifications
■Dimensions width B x height H
■from 300x300 mm up to 700 x 1100 mm by 5 mm - hand-operated design
■from 350x385 mm up to 700 x 1100 mm by 5 mm - rearming motor design
■Total depth of 90 mm (built-in depth 80 mm) without grille
■Grilles of 77% to 95% effective cross section available
■Opening and securing within 5 seconds; closing in less than 30 seconds
■Activation signal – pulse of length of 1 s min 24 V DC, or 48 V DC
■Universal 24/48 V rearming motor (optional)
■Degree of protection IP42 (electric part)
■In acc. with Regulation (EU) 305/2011 (CPR), EU Directive (EU) 2014/30/EU (EMC), Directive (EU) 2011/65/EU (RoHS)
■CE certification according to EN 12101-8
■Tested according to EN 1366-10
■Classified according to 13501-4 + A1
■Fire resistance cf. tab. bellow
■Pressure class 3 (underpressure 1500 Pa / overpressure 500 Pa)
■Closed blade tightness class 3 according to EN 1751
■Certificate of Constancy of Performance No. 1391-CPR-2023/0030
■Declaration of Performance No. PM/SEDM-D/01/23/1
■EU Declaration of Conformity No. PM/SEDM-D/03/23/2
■Efectis France Test report on fitness for use of mechanisms No. EFR-22-0000822
■In accordance with NF 61.937-1 and NF 61.937-10
Classification of Dampers
Vertical duct (shaft) contruction Classification**
Concrete or aerated concrete of thickness min. 70 mm, with or without
installation frame EI 120 (ved i↔o) S1500C300AAmulti
Selected light smoke extraction duct panels of given thickness*, with or
without installation frame
EI 120 (ved i↔o) S1500C300AAmulti, or
EI 90 (ved i↔o) S1500C300AAmulti, or
EI 60 (ved i↔o) S1500C300AAmulti, depending
on panel material and thickness*.
* → see page 19 for the variety of shaft panel materials and
thicknesses and installation details with corresponding
damper fire resistance class.
** The classification applies only to the damper equipped
with a grille.

Page 5Version 2023-06-07 Smoke extraction damper - SEDM-D
TPM 155/22
SEDM-D rearming motor designSEDM-D hand-operated design
Operating conditions
Both declared performance and faultless operation are ensured under the following conditions:
■The damper equipped with one of the grilles available
■Maximum vacuum up to 1500 Pa or overpressure up to 500 Pa
■Rearming shall be carried out without air flow and without air pressure
■The dampers are suitable for vertical installation only
■Range of activation voltage and rearming motor supply voltage shall be respected; dimensioning of voltage sources and of
connecting cables shall fit the electrical parameters of the damper
■Connecting cables shall not physically impede free movement of moving parts and sub-asemblies
■Damper shall be always kept closed with the exception of short periods of installation, commissioning and functional tests
■The rearming motor shall not be used to act against the air pressure or another external force
■Dampers are designed for macroclimatic areas with mild climate according to EN IEC 60 721-3-3 ed.2., class 3K22.
(Environment 3K22 is typically protected place with regulated temperature) and with a temperature range of -25°C to 50°C
Connecting cables shall be guided from a pre-punched hole in
one of the corners of the damper frame to the junction box
using delivered cable clips. The junction box contains a
universal 10-position screw terminal. Damper supply voltage
and terminal block positions are printed inside the junction
box. Depending on the damper design configuration and
connecting cables available, some terminal positions may
stay void. Aditional junction box with 6-position screw
terminal is present for bipolar end-switch module.
The damper is equipped with a restraint mechanism keeping
the damper closed. The restraint mechanism includes a
permanent magnet combined with an electric coil with
magnetic poles opposite to those of the permanent magnet.
In case of the activation of the damper, the coil magnetic field
compensates the magnetic field of the magnet and thus, the
restraint mechanism lets the damper open. The activation
signal represents a simple switching the voltage ON. The
damper may be equipped with position end-switch module
with end-switches indicating the damper blade position open
or closed. The damper is manufactured in hand-operated
rearming design or electric motor rearming design. Rearming
means getting the damper blade from the position open
(security) to the position closed (stand-by).
II. DESIGN

Smoke extraction damper - SEDM-DPage 6 Version 2023-06-07
TPM 155/22
■Hand-operated rearming design with a magnet voltage of
24 V DC and with two end switches signaling of the
damper blade position "CLOSED" (STAND-BY) and "OPEN"
(SECURITY).
■Electric motor rearming design with a magnet voltage of
24 V DC, with two end switches signaling of the damper
blade position "CLOSED" (STAND-BY) and "OPEN"
(SECURITY).
■Hand-operated rearming design with a magnet voltage of
24 V DC and with two pairs of end switches signaling of
the damper blade position "CLOSED" (STAND-BY) and
"OPEN" (SECURITY).
■Electric motor rearming design with a magnet voltage of
24 V DC, with two pairs of end switches signaling of the
damper blade position "CLOSED" (STAND-BY) and "OPEN"
(SECURITY).
■Hand-operated rearming design with a magnet voltage of
48 V DC without end switches. This design is not in
accordance with NF 61.937-1, and not in accordance with
NF 61.937-10.
■Electric motor rearming design with a magnet voltage of
48 V DC without end switches. This design is not in
accordance with NF 61.937-1, and not in accordance with
NF 61.937-10.
■Hand-operated rearming design with a magnet voltage of
48 V DC and with two end switches signaling of the
damper blade position "CLOSED" (STAND-BY) and "OPEN"
(SECURITY).
■Electric motor rearming design with a magnet voltage of
48 V DC, with two end switches signaling of the damper
blade position "CLOSED" (STAND-BY) and "OPEN"
(SECURITY).
■Hand-operated rearming design with a magnet voltage of
48 V DC and with two pairs of end switches signaling of
the damper blade position "CLOSED" (STAND-BY) and
"OPEN" (SECURITY).
■Electric motor rearming design with a magnet voltage of
48 V DC, with two pairs of end switches signaling of the
damper blade position "CLOSED" (STAND-BY) and "OPEN"
(SECURITY).
■Hand-operated rearming design with a magnet voltage of
24 V DC without end switches. This design is not in
accordance with NF 61.937-1, and not in accordance with
NF 61.937-10.
■Electric motor rearming design with a magnet voltage of
24 V DC and without end switches. This design is not in
accordance with NF 61.937-1, and not in accordance with
NF 61.937-10.
Design .24C2H Design .24C2M
Design .24C4H Design .24C4M
Design .48C0H Design .48C0M
Design .48C2H Design .48C2M
Design .48C4H Design .48C4M
Design .24C0H Design .24C0M
Hand-operated designs Rearming motor designs

Page 7Version 2023-06-07 Smoke extraction damper - SEDM-D
TPM 155/22
End switch G905-200S02D1
End switch module
End-switches
Type; configuration G905; (C-NO-NC)
Voltage ≤ 60 V DC
Switchable DC current
Contact resistance
Insulation voltage open contact
Cut-off power (DC)
Longevity – cycles
> 0.5 A
< 0.1 Ohm
> 500 V
> 10 W
> 1000
Microswitch AC rating
Microswitch degree of protection
230 V AC / 5 A
IP67
Compliance NF 61.937-1, NF 61.937-10
Colour NC
Colour NO
Colour C
■Wiring diagram of end switches → see page 12
■End switch module can be equipped with 2 end switches or with 2 pairs of end switches (both positions 2x) CLOSED,OPEN

Smoke extraction damper - SEDM-DPage 8 Version 2023-06-07
TPM 155/22
Rearming motor
Rearming motor
Nominal voltage
Voltage range
24 V / 48 V DC
20.4 … 57.6 V
Power input
Dimensioning
20 W
29 VA
Recommended switch-on time
Rearming time at room temperature
Longevity – cycles
Cycling period
40 s
< 30 s
≥ 300
min. 120 s
Maintenance maintenance free
Compliance NF 61.937-1, NF 61.937-10
■Rearming of the damper blade with electric motor. Rearming means getting the damper blade from the position open
(security) to the position closed (stand-by). This is not a safety function; this is purely a comfort function.
■Wiring diagram of the rearming motor → see page 12

Page 9Version 2023-06-07 Smoke extraction damper - SEDM-D
TPM 155/22
20 mm
26 mm (from the wall)
12 mm
12 mm (from the wall)
Grille G1
■Simple, the lightest grille made from a punched 2 mm Al sheet, 77% effective area.
Grille G2
■Design grille with aerodynamic profile louvers made from Al alloy, 77% effective area.
■The damper should be used with a protection grille G1, G2, G3 or G4.
■Grille G1 is not powder painted as standard. Can be powder painted, if specified in the ordering key.
■Grilles G2, G3, G4 are powder painted. If no colour is specified in the ordering key, the colour will be RAL 9010.
■Allen screws M5 and washers are used for G1, G2, and G4 grilles.
■Allen screws M4, hexagon head screws M5 and washers are used for G3 grilles.
■Fasteners are delivered with the grille.
■Dimensions for mounting of grilles → see page 15
Grilles designs

Smoke extraction damper - SEDM-DPage 10 Version 2023-06-07
TPM 155/22
2x screw M4 to OPEN OPEN to 90°
Can be removed
A
2x screw M4 to
secure the grille
B
Detail B Detail A - Back view
4x Frame hinge 31 mm (from the wall)
Grille G4
■Design grille made of steel (punched and drawn), 78% effective area.
25,5 mm
12 mm
14 mm (from the wall)
Detail A - Section view
22,5 mm
4x Screw M5 for
hanging the grille
Grille G3
■Design grille with thin louvers made from Al sheet, no visible bolts, easy to open and close, 95% effective area.
■The movable central part of the grille can be easily removed from the grille frame completely, and then put back easily.
■First hang the grille on four frame hinges (Detail A - back
view) using four M5 screws (Detail B - 4x M5 screw, 4x M5
nut and 8x washer), then secure the grille with two M4 screws.