LK-CP64X Control Panel (6A)
¢Terminal
03 04
Symbol
Descripon
Symbol
Descripon
L
AC live wire
FSO
Fire signal output
N
AC null wire
FOO
Fire output NO
E
AC earth wire
FOC
Fire output NC
V+
24VDC input posive
24V
24VDC+ output
V-
24VDC input negave
FSI
Fire signal input
M+
24VDC motor posive
COM
Sensor COM
M -
24VDC motor negave
S+
Slave control up
MU
Manual switch up
S-
Slave control down
MS
Manual switch stop
12V
DC12V+ output
MD
Manual switch down
WRD
Rain sensor down
MG
Manual switch GND
T/H
T/H signal
Power Supply V+
L
V-
N
E
MG MD MS MU M1+ M1- M2+ M2- M3+ M3-M4+ M4- V- V+
FSO
FOO
FOC
24V
FSI
COM
S+
S-
12V
WRD
T/H
Control Board
ON
Y
N
S-TH
¢Manual control
—Aer power on all the LEDs light for 1 second and turn off, the power indicator LED
normally on
—Press reset buon, all the LEDs light for 1 second and turn off, reset successfully
—L2 will be explosion-flashing aer controller receives fire signal
—External manual switch is equivalent to controller panel switch
—The maximum running me of the motor is 5 minutes
.
.
£Group control
—By default, L1 is normally on, the rest LEDs are off as group control status
—Press UP buon, the windows open, LED turns on, turns off aer 5 seconds
—Press DOWN buon, the windows close, LED turns on, turns off aer 5 seconds
—Press STOP buon, ,the motors stop, LED turns on, LED turns off aer 1 second
£Channel control
—Press channel selecon keys the corresponding LED lights, channel selected
—Press the channel selecon buon again or no operaon on controller thin 10 seconds,
LED turns off, channel unselected
—In the process of opening/closing the current window, you can select another channel(s)
to drive the window
.
—Can be used as a master controller, a slave controller or play a dual role of master & slave
controller at the same me
—As a master controller, connects to the motors or slave controllers to drive them
—As a slave controller, input terminals S+ and S- are connected to the output terminals M+
and M- of the master controller to receive the instrucons to drive motors, or drive the
motors independently
—Play a dual role of master & slave controller, not only controlled by higher-level controller,
but also drive motors or lower-level controllers independently
—No maer master, slave or both, it can process all the external signals such as manual
switch, remote and sensors
—Cascade use of the controller, if the master controller connected to an external sensor
(such as smoke sensor, wind and rain sensor, etc.), the slave controller MUST NOT use
inching mode, in case the master controller received the smoke signal to open the
window, the slave controller will open the window for a very short moment and stop
¢Cascaded control

www.linkayl.com Copyright © Linkayl Technology Limited
LK-CP64X Control Panel (6A)
05 06
¢Remote control
—The controller encodes by 433MHz learning code, can store 10 sets of transmission codes
—The controller defaults to mulple channel, single channel controler has the same way as
mulple channel one
.
£Matching code
—Power the controller on, choose the channel(s) you want to set, can be set to any
combinaon of channel 1-4
—Pressing STOP buon on controller for 5 seconds
—LED flashes 3 mes and turns off
—Choose the channel you want to set on the remote
—Press UP within 15 seconds
—LED flashes 3 mes and turns off
—Code matched successfully
.
£Clearing single code
—Power the controller on
—Keep pressing STOP key on the controller for 5S
—LED flashes 3 mes and turns off
—Press DOWN buon on the remote within 15 seconds
—LED flashes 3 mes and turns off
—Code cleared successfully
.
£Clearing all codes
—Power controller on
—Pressing STOP /DOWN buon on the controller for 5 seconds
—LEDs flash 3 mes and turn off
—All the codes will be deleted aer this operaon
¢Signal control
.
.
£Reset and shielding
—Manual signal. Control the window by the buons on itself, external dry contact manual
switch and RF remote
—Cascaded signal. As a master controller sends signal to the slave controller, can also be
used as slave controller to receive the signal from the master controller to drive the
window
—Fire signal. Capable of receiving a signal from fire center, smoke sensor, gas detector open
the window automacally, send feedback signal to fire centre
—Rain signal. Aer receiving the signal of rain sensor close the window
—Temperature/humidity signal. Control the window by processing external
temperature/humidity sensor
—Aer manual signal processed controller receives input signal in real me
—Aer processing the signal from fire centre, smoke sensor or gas detector, the controller
immediately shields all the input signals, the controller must be reset by pressing K1
manually
—Aer wired rain sensor signal processed, the controller shields lower priority signal, only
receives the higher priority signal unl reset or manual signal processed
—Aer T&H sensor signal processed, the controller is in the reset state
—If the controller is not connected to a temperature and humidity sensor, the T/H port
must be shielded (put opon switch to “Y” posion)
£Signal and priority
Priority
Signal
Device
1
Manual signal
Panel buons, manual switch, remote, master controller
2
Fire signal
Smoke sensor, gas detector
3
W/R signal
Wired wind rain sensor
4
T/H signal
Temperature sensor, humidity sensor

www.linkayl.com Copyright © Linkayl Technology Limited
LK-CP64X Control Panel (6A)
07 08
—Please read the following instrucons carefully before installing this product
—Installing this product must comply with the effecve local electricity specificaons
—The control system must be installed by the professional
—The main power must be cut off before wiring to ensure safe operaon
—Addive maximum output power MUST NOT exceed the total rated power of the
controller
—Do not use metal objects to touch or cover the controller, otherwise it will affect the
remote control signal recepon
—The maximum transmission distance of the wireless signal can reach 50 meters or more
in the open condion
—The distance between the controller and ground should be more than 1.5 meters
—The distance between the controller and ceiling should be more than 0.3 meters
—The distance between the controller and motor should be more than 1.5 meters
—Avoid stac interference and prevent stac damage to electronic components
—Please use the so wire and cable, aer installaon ensure that the cable carrier is not
affected by the longitudinal tension
—An external sensor must use a product that is compable with this controller
—Non-professionals is not allowed to disassemble the controller. If any funcon is bnormal,
please contact your local dealer
.
¢Installaon instrucon
¢Stroke memory
—The controller can set and memorize the opening stroke. Upon the stroke set, the
window opening signal is triggered once, the motor will run the memorized stroke one
me
—The default memorized stroke runs for 5 minutes
—Press both of UP /DOWN buons on the controller for 3 seconds, LEDs flash 3 mes and
off, successfully entered the stroke memory seng state
—In the stroke memory seng state, the manual keys are forced to the connued-run
mode, the remote control keys are forced to the inching mode
—Select the channel(S) to be set, the default is all selected, all the channel indicators light.
Press the channel selecon key(s), the indicators light, press the channel selecon key(s)
again the indicator is off, it is deselected. The seng is invalid without operaon in 15
seconds
—Aer the channel selected, determine the stroke that needs to be memorized by pressing
the manual key or the remote control key by moving or jogging
—The memorized stroke can be set to one channel or any combinaon of channel
—Aer the memorized strokes determined, turn on all the channel indicators for seng the
memorized stroke. Press both of UP /DOWN buons on the controller for 3 seconds, LEDs
flash 5 mes and off, the memorized strokes of all channels set successfully and exit the
stroke memory seng state, manual buons and remote control buons restored to the
original mode
—In stroke memory seng state, no operaon is performed within 15 seconds, LEDs flash 3
mes slowly and off, the stroke memory seng state is automacally exited, and the last
memorized stroke is retained
—Stroke memory can be set repeatedly. The controller only retains the last successful
stroke value and automacally clears the previous one
—In stroke memory seng state, press both of STOP /DOWN buons on the controller for
3 seconds LEDs flash 3 mes the memorized stroke is deleted and restored to the default
output for 5 minutes
—When the memorized strokes of master controller and slave controller are not the same,
the master controller will run its own memorized stroke. The slave controller will run the
shorter stroke when it receives the cascade signal from the master controller
—The memorized stroke set for each channel is retained in case the controller is powered
down or reset
—When closing the window, the output me is 5 minutes
¢Control mode
—Controller has inching mode and connued-run mode which is default
—In the connued-run mode, press UP or DOWN buon less than 1.5 seconds, the motor
will run connuously, press UP or DOWN buon more than 1.5 seconds, the motor will
stop aer running a very short moment
—In the inching mode, press UP or DOWN buon less than 1.5 seconds, the motor will stop
aer running a very short moment, press UP or DOWN buon more than 1.5 seconds,
the motor will run connuously
—Only the manual buons on the panel, manual switch, remote control and cascade signal
have inching mode
—Keep pressing both of UP and STOP buon on the controller for 5 seconds, LEDs flash 3
mes and turn off it's inching mode for the controller, repeat the operaon the controller
turns to connued-run mode
Ce manuel convient aux modèles suivants
3
Autres manuels LinkAYL Panneau de contrôle

LinkAYL
LinkAYL LK-UP211 Manuel utilisateur

LinkAYL
LinkAYL LK-FP3 Manuel utilisateur

LinkAYL
LinkAYL LK-UP22 Series Manuel utilisateur

LinkAYL
LinkAYL LK-CP711-30A Manuel utilisateur

LinkAYL
LinkAYL LK-CP611 Manuel utilisateur

LinkAYL
LinkAYL LK-CP63 Series Manuel utilisateur

LinkAYL
LinkAYL LK-UP24 Series Manuel utilisateur

LinkAYL
LinkAYL LK-CP62 Series Manuel utilisateur

LinkAYL
LinkAYL LK-CP63X Series Manuel utilisateur