Lytemode Network Powered Hub User’s Guide
© 2008 Philips Controls. All Rights Reserved.

LYTEMODE NETWORK POWERED HUB USER’SGUIDE
1
Important Safeguards
Table of Contents
Customer Service .............................................................................................................................2
Lytemode System Overview ............................................................................................................3
Lytemode ILS Network Powered Hub Overview ...........................................................................4
Device Power Requirements .....................................................................................................5
Operation ...................................................................................................................................5
Installation .......................................................................................................................................6
Installing the Unit ......................................................................................................................6
Specifications ...................................................................................................................................8
When using electrical equipment, basic safety precautions should always be followed
including the following:
a) READ AND FOLLOW ALL SAFETY INSTRUCTIONS.
b) Do not use outdoors.
c) Do not mount near gas or electric heaters.
d) Equipment should be mounted in locations and at heights where it will not readily be
subjected to tampering by unauthorized personnel.
e) The use of accessory equipment not recommended by the manufacturer may cause an
unsafe condition.
f) Do not use this equipment for other than intended use.
g) Refer service to qualified personnel.
SAVE THESE INSTRUCTIONS.

CUSTOMER SERVICE LYTEMODE NETWORK POWERED HUB USER’SGUIDE
2
Customer Service
Technical and Sales assistance for Lytemode products are available worldwide.
Phone: +1-800-526-2731 (In the United States and Canada)
+1-214-647-7880 (Worldwide)

LYTEMODE NETWORK POWERED HUB USER’SGUIDE LYTEMODE SYSTEM OVERVIEW
3
Lytemode System Overview
The Lytemode System is designed to control architectural lighting by distributing both power and
intelligence. The system provides processing power and control at each respective Master or Remote
Station, eliminating the need for a central processor. Lytemode Master Stations provide individual
channel control, 13 scenes plus “Off,” adjustable fade times, and a graphic representation of channel
intensities. Multiple Master Stations may be linked together for control of up to 128 Channels and 13
preset scenes. By combining Lytemode Master Stations with Lytemode Remote Stations, the system
provides remote access to scenes, Master Raise/Lower control, Multi-room partition control, or Master
Station Lockout. Lytemode Master Stations are easily programmed using the front panel buttons,
without removing the Master Station from the wall, and without the need for a computer. Lytemode
Master Stations are compatible with both Lightolier Controls Insulated Gate Bipolar Transistor
(IGBT) Dimming Cabinets as well as Silicon Controlled Rectifier (SCR) Dimming Panels.
Lytemode products are controlled by the Intelligent Lytemode System (ILS) protocol. All Lytemode
control devices must be connected to the ILS system in order to interact properly, where they are
distinguished by a unique ID (or address). The ID identifies the device on the network and allows the
device to avoid network collisions when transmitting data.

LYTEMODE NETWORK POWERED HUB OVERVIEW LYTEMODE NETWORK POWERED HUB USER’SGUIDE
4
Lytemode Network Powered Hub Overview
The Lytemode Network Powered Hub (ILSLMHUB) provides DC Power across the Lytemode ILS
Network for the purpose of powering Master Stations, Remotes, and Interfaces. The Network Powered
Hub provides 1.5 amps each for four separate, electrically isolated Lytemode Network circuits. The
unit is equipped with separate compartments for Line Voltage wiring connections and Low Voltage
wiring connections. Terminal blocks for all connections are included. The Network Powered Hub can
be either wall-mounted or rack-mounted using the included reversible mounting brackets.
The Lytemode Network Powered Hub can be used to power large networks, to supply additional power
for very long cable lengths, or used as a redundant supply to ensure Lytemode Network reliability.
Multiple Powered Hubs may be connected to a Lytemode ILS Network.
Figure 1: Hub Interior View
NEUTRAL
LINE IN
GROUND
N/A
1 GND
2 AC LINE
3 AC NEUTRAL
Output + 4
Output +5
Output - 6
Output - 7
Input Power Connections - Terminal strip for
connection of Line, Neutral and Ground wiring.
High Voltage Compartment
Network Output Connections - Four terminal strips
for connection of CAT5e cables, which supply power to
the Lytemode devices in a daisy-chain configuration.
Low Voltage
Mounting Bracket (2) - Configurable
brackets for wall or rack mounting.
Compartment
INTERIOR VIEW
Power Supply

LYTEMODE NETWORK POWERED HUB USER’SGUIDE LYTEMODE NETWORK POWERED HUB OVERVIEW
5
Device Power Requirements
The following chart provides power requirements for Lytemode ILS devices.
Operation
Once connected to the house power service and Lytemode ILS Network, the Network Powered Hub is
ready for operation. To apply power to the ILS network, apply house power service to the unit. Refer to
“Installation” on page 6 for connection instructions.
Master Stations
ILSCL125ES 103mA Each
ILSCL165ES 116mA Each
ILSCL85ES 72mA Each
ILSCL45ES 59mA Each
ILSCL6MMES 20mA Each
ILSCLTS 350mA Each
ILSDMX45ES 60mA Each
ILSDMX85ES 75mA Each
ILSDMX125ES 105mA Each
ILSDMX165ES 120mA Each
Remote Stations
ILSCL8RES 20mA Each
ILSCL6RES 20mA Each
ILSCL2RES 20mA Each
ILSCL8RSPS 20mA Each
Interface Options
ILSCL232 25mA Each
ILSCLIM 10mA Each

INSTALLATION LYTEMODE NETWORK POWERED HUB USER’SGUIDE
6
Installation
The Network Powered Hub can be wall-mounted or rack-mounted using the included mounting
brackets. Knock-out holes in the unit’s housing can be used to route power wiring and network cables
as required.
Installing the Unit
To install: Step 1. Unpack unit and inspect for any signs of shipping damage.
Step 2. If necessary, reconfigure mounting brackets (supplied) for wall or rack mounting
as shown in Figure 2.
Figure 2: Configuring Mounting Brackets & Removing Covers
Step 3. Install unit.
Step 4. Remove covers from High Voltage and Low Voltage compartments.
WARNING: Ensure that power is removed from house service before connecting any wiring or cables
to the Network Powered Hub.
Step 5. Remove power from house service.
Housing
Low Voltage
Compartment
High Voltage
Compartment
Mounting Bracket
CONFIGURATION 1
CONFIGURATION 2
Screw (4)
Screw (4)
Screw (9)
Cover
Mounting
Bracket Cover

LYTEMODE NETWORK POWERED HUB USER’SGUIDE INSTALLATION
7
Step 6. As required, remove knock-out hole covers and route power input wires and
Lytemode ILS Network cables as shown in Figure 3.
Note: The Lytemode ILS Network consists of a single CAT5e cable connecting all Lytemode ILS
devices in a daisy-chain configuration. All units connect to the network using a 9-pin connector
(included).
Figure 3: Power and Lytemode ILS Network Connections
Step 7. Re-install compartment covers (Figure 2).
Step 8. Re-apply house power service.
NEUTRAL
LINE IN
GROUND
N/A
1 GND
2 AC LINE
3 AC NEUTRAL
Output + 4
Output +5
Output - 6
Output - 7
INTERIOR DETAIL
1 WH/OR (+ Data)
2 OR (- Data)
3SHIELD
4WH/GN(+Volts)
5 GN (Ground)
6WH/BL(+Volts)
7 BL (Ground)
8WH/BR(+Volts)
9 BR (Ground)
9-Pin Lytemode Network Connectors
PIN SIGNAL
Knock-out Hole
WARNING!
Remove power from house service before connecting
any wiring or cables to the Network Powered Hub.
Route Power Wires
Route Network Cables
Lytemode Network
Input Power Connections Connections (4)

SPECIFICATIONS LYTEMODE NETWORK POWERED HUB USER’SGUIDE
8
Specifications
Electrical:
• Input Power: 110-240VAC, 50-60Hz, 3.2 A, 1 Phase
• Output Power: 24VDC, 1.5 A per output (x 4 Separate Outputs)
• Number of Outputs: 4
• Temperature:
- Storage: -25° to 85° C
- Operating: 0° to 40° C
- Relative Humidity: 30-90% (non-condensing)