INSTALLATION INSTRUCTIONS
MLX
MULTI-LINX LED Fixture
Modular Linkable Linear Fixture
www.jescolighting.com
Tech Support: 855.592.0029
Instruction sheet subject to change without prior notice.
15 Harbor Park Drive
Port Washington, NY 11050
Main Line: 800.527.7796
Fax Line: 855.265.5768
219 South 6th Ave
City of Industry, CA 91746
Main Line: 855.654.0110
Fax Line: 626.333.2955
Designed, Developed and
Assembled in the U .S.A
Page 1 of 8
JW 06/14/2017
MULTI-LINX
Please read and save these instructions. Read carefully before using product. Protect yourself and others by observing all
safety information, warnings and cautions. Failure to comply with instructions could result in personal injury and/or damage
to product or property. Please retain instruction sheet for future reference.
IMPORTANT SAFETY INSTRUCTIONS
Read completely before beginning. If you feel you do not have adequate electrical wiring experience, have this installed by
a qualied licensed electrican.
All electrical connections must be in accordance with local codes, ordinances and the National Electric Code. This product
operates on 120V AC; always conrm the maximum wattage of the linear xture does not exceed the maximum wattage of
the circuit it is connected to. If you are unfamiliar with methods of installing electrical wiring, secure the services of a qualied
licensed electrician.
Read and follow all safety instructions.
Read completely before beginning. If you feel you do not have adequate electrical wiring experience, have this
installed by a qualied licensed electrician.
All electrical connections must be in accordance with local codes, ordinances and the National Electric Code.
This product operates on 120V AC; always conrm the maximum wattage of the linear xture does not exceed the
maximum wattage of the circuit it is connected to. If you are unfamiliar with methods of installing electrical wiring,
secure the services of a qualied licensed electrician.
Do not install the linear xture if any damage is seen on the product or power cables.
Prior to starting the installation, disconnect the power by turning off the circuit breaker or removing the appropriate
fuse. (Turning off power using the light switch is not sufcient to prevent electrical shock).
1.
2.
3.
4.
5.
TURN OFF ELECTRICITY
at main fuse box (or circuit breaker box)
before beginning installation by switching
circuit breaker off or removing fuse.
MIN 90º C SUPPLY CONDUCTORS.
MOUNTING OPTIONS
FOR ELECTRICAL CONNECTION, SEE PAGE 8
Surface Mounting with Clips
Single or Multiple xtures connected
linearly. (See page 7)
Single or Linearly Connected
Ceiling Mounting with Cables
Single or multiple xtures connected
linearly. (See page 2)
Multiple Side-by-Side
Ceiling Mounting with Cables
Multiple xtures connected side-by-side.
(See page 4)
RATED 120 VOLT AC
20W per 2 feet xture (15units MAX)
40W per 4 feet xture (7 units MAX)
80W per 8 feet xture (3 units MAX)
CONSULT A QUALIFIED ELECTRICIAN TO
ENSURE CORRECT BRANCH CIRCUIT
300W MAX
connected run