INITIAL SET UP
Wire the unit per the installation instructions and connect
power to the battery sense terminals. The SET SYSTEM
VOLTAGE screen should be displayed on the front panel. Press
ENTER to select that screen, then use the scroll wheel to select
the NOMINAL BATT V line, press ENTER to select, and then
adjust the encoder knob to select 12, 24 or 48V as required.
Press ENTER to select. The unit disconnect and reconnect
thresholds will now be set to the factory default levels for that
battery voltage.
Normally this is the only setting required on the unit unless
custom disconnect or reconnect points are desired, or the
internal LVD contactor is to be manually set to open or closed.
The external battery service disconnect switch may now be
closed, allowing the load to be powered through the LVD unit.
ALARMS
The Form-C alarm contact on the back panel is triggered for LVD
trip, Over Current trip, or internal Over Temperature trip. The
main LVD contactor will open for all alarm conditions, and must
be manually re-set for an Over Current event by setting the LVD
Mode back to AUTO.
Alarm Screens: (any button press will return to home screen)
SPECIFICATIONS
Battery Voltage: 10 to 65V
Maximum Load Current: 200A (12/24V), 100A (48V)
Auto Overload Disconnect Current: (+/- 5%)
12/24V System setting 220A
48V System setting 110A
Display Accuracy (V): +/- 2%
(Amps): +/- 5%
LVD Delay (approx. time to switch state) 3s
Operating power (Tare loss): < 1W
Alarm Contact (Form-C): 0.5A, 125Vac/dc max
Dimensions: (inches)
LIMITED WARRANTY
ICT Ltd. warrants to the original consumer purchaser that this
product shall be in good working order, free from defects in
materials and workmanship, for a period of three (3) years from
the date of purchase. Should failure occur during the above
stated time period, then ICT will, at its option, repair or replace
this product at no additional charge except as set forth below.
All parts, whether for repair or replacement, will be furnished
on an exchange basis. All exchange pieces become the property
of ICT. This limited warranty shall not apply if the ICT product
has been damaged by unreasonable use, accident, negligence,
disaster, service, or modification by anyone other than the ICT
factory.
Limited warranty service is obtained by delivering the product
during the above stated three (3) years warranty period to an
authorized ICT dealer or ICT factory and providing proof of
purchase date. If this product is delivered by mail, you will
insure the product or assume risk of loss or damage in transit,
and prepay shipping charges to the factory.
Every reasonable effort has been made to ensure that ICT
product manuals and promotional materials accurately describe
ICT product specifications and capabilities at the time of
publication. However, because of ongoing improvements and
updating of ICT products, ICT cannot guarantee the accuracy of
printed materials after the date of publication and disclaims
liability for changes, errors or omissions.
If this ICT product is not in good working order, as outlined in
the above warranty, your sole remedy shall be repair or
replacement as provided above. In no event will ICT be liable for
any damages resulting from the use of or the inability to use the
ICT product, even if an ICT employee or an authorized ICT
dealer has been advised of the possibility of such damages, or
for any claim by any other party.
ICT reserves the right to make changes without further notice to
any products or documentation for improvement of reliability,
function, or design.
ICT Ltd. does not recommend use of its products in life support
applications wherein a failure or malfunction of the product
may directly or indirectly threaten life or cause injury. The user
of ICT products, which are to be used in life support applications
as described above, assumes all risks of such use and
indemnifies ICT against all damages.
INNOVATIVE CIRCUIT TECHNOLOGY LTD.
26921 Gloucester Way
Langley, British Columbia, Canada V4W 3Y3
T 604.856.6303 F604.856.6365 www.ict-power.com