Core IO 40 Multi Manual innon.com
9
Digital Inputs
Digital Inputs can have a clean/volt free contact connected to Core IO to read its open/closed status.
Each digital input can be congured to be either:
• Digital Input direct
• Digital Input reverse
• Pulse input
While the “direct” and “reverse” mode would basically return status “False (0)” or “True (1)” when
the contact is either open or closed, the third mode “pulse input” is used to return a counter value
increasing by 1 unit every time the digital input closes.
A dedicated chapter on the pulse input topic is available later in this manual.
The pulse input can count eectively up to a frequency of 100Hz, with 50% duty cycle.
Digital Outputs (Relay)
The Digital Outputs are driven by relays.
Each Digital Output can be congured to be either:
• Digital Output direct
• Digital Output reverse (eectively reversing the logic of the output status)
For every Digital Output it is possible to congure the desired status when the “Watchdog”
function is triggered (BEMS oine for over a timeout delay).
CONFIGURE I/O